Manufacturer:B&R
-
Product Category:PLC Systems
-
Spare Part Number:X20AT2222
-
Weight:0.02 kg
-
Tariff Code:8537101190
-
Input channels:2
-
Sensor types:Pt100 / Pt1000
-
Sensor range:-200.0 to 850.0 degrees C
-
Temperature resolution:0.1 degrees C
-
Converter:16-bit sigma-delta
-
Measurement current:250 microamps +/-1.25%
-
Filter time:1-66.7 ms; configurable
-
Resistance ranges:0.1-4500 ohms /0.05-2250 ohms
-
Input filter:First-order;500 Hz
-
Isolation:Channels to bus; not between channels
-
Bus power:0.01 W
-
Internal I/O power:1.1 W
Information
- B&R X20AT2222 connects its configured field signals and diagnostic states to the automation task. Correct operation depends on retaining the installed hardware selection and the application settings together.
Sensor types: Pt100 / Pt1000
Sensor range: -200.0 to 850.0 degrees C
The 16-bit sigma-delta converter uses a constant measurement current of 250 microamps. Filter time is configurable from 1 to 66.7 ms. At the 50 Hz filter setting, conversion is 20 ms for one channel and 80 ms for two channels; these timings must be considered separately from the controller task period.
Input monitoring distinguishes lower limit, upper limit and open-circuit conditions. Invalid and fault values must be interpreted with the channel status rather than as real temperatures. Channels are isolated from the bus, but not from each other; terminal block and bus module are separate system components.
X20AT2222 Official Technical Excerpt
The original technical excerpt for B&R X20AT2222 covers identity, interface limits and configuration behavior. PDF · 10 pages.X20AT2222 Installation & Verification Guide
Apter Power installation and verification guide covering configuration retention, reconnection, functional tests and diagnostic recovery. PDF · 5 pages.
Application scope: Apply the exact hardware and software configuration to the assigned machine function. A similar connector or base family is insufficient to establish replacement compatibility.
Configured machine function
Each channel can select Pt100 or Pt1000 sensing, while the two- or three-wire arrangement is configured for the module. Internal linearization converts the sensor resistance to temperature with 0.1 degree resolution. Direct resistance measurement is also available in two ranges.Interface continuity
Connect sensor and sense leads according to the original wiring scheme. Maintain the intended lead-compensation arrangement for three-wire measurement.Diagnostic acceptance
Check the application response to an approved open-circuit or range simulation. Confirm that status and substitute values do not become valid process temperatures.Controlled restoration
Allow the selected filter and conversion cycle to settle. Compare both channels under stable input rather than assuming the controller cycle equals conversion time.
Record each channel sensor type and the module-wide two-/three-wire setting. Preserve the resistance or temperature operating mode, filter and assigned process point.
Prevent the affected loops from acting on disconnected-sensor fault values. Use the approved machine maintenance state and module exchange procedure.
Check for open circuits, damaged leads and incorrect two-/three-wire routing. Channel-to-channel isolation is not available to correct a wiring-reference error.
Load the retained sensor types, connection method and filter setting. Do not select Pt1000 solely to compensate for an incorrect resistance reading.
Apply an approved resistance or temperature reference and compare both channel values. Use the configured range and 0.1 degree temperature resolution when assessing results.
Allow the selected filter and conversion cycle to settle. Compare both channels under stable input rather than assuming the controller cycle equals conversion time.
Alternative Names
Technical notes
Measurement status: Treat the channel status and measured value as one result. Fault and out-of-range substitutions must be handled before the value is used by the application.
Filter trade-off: Choose the measurement filter with both mains-frequency rejection and channel update time in mind; the fastest setting is not automatically the best temperature measurement setting.
FAQ View All FAQ
-
Can X20AT2222 use Pt100 on one channel and Pt1000 on the other?Yes. Sensor type is configurable per channel. The two-/three-wire connection arrangement is configured for the module.
-
What temperature increment is represented by X20AT2222?Temperature values have a 0.1 degree Celsius resolution for both Pt100 and Pt1000 sensing.
-
How does the 50 Hz filter affect conversion on X20AT2222?The conversion time is 20 ms for one channel and 80 ms for two channels at the 50 Hz filter setting.
-
Can X20AT2222 report resistance directly instead of temperature?Yes. Direct resistance ranges are 0.1-4500 ohms and 0.05-2250 ohms, depending on the configured operating mode.
-
What excitation does X20AT2222 apply to the sensor circuit?The resistance measurement uses a 250 microamp constant current with a specified tolerance of+/-1.25%.
-
Are the two input channels of X20AT2222 isolated from one another?No. The channel side is isolated from the bus, but channel-to-channel isolation is not provided.
-
Why must software check status as well as the value from X20AT2222?Open circuit, range errors and invalid conversions use defined substitute digital values. Interpreting only the numerical value can mistake a fault code for temperature.
-
Which terminal blocks can be used with X20AT2222?X20TB06 is the intended 6-pin block; X20TB12 may also be used. The selected bus module and terminal block must be included separately in the system arrangement.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.