Technical specifications for 3IF771.9
-
Manufacturer:B&R
-
Product Category:PLC Systems
-
Spare Part Number:3IF771.9
-
Weight:0.34 kg
-
Tariff Code:8537101190
-
CAN interfaces:1
-
CAN controller:SJA1000
-
Host interface:aPCI
-
Maximum CAN bit rate:500 kbit/s
-
Cable length at 500 kbit/s:60 m maximum
-
Cable length at 250 kbit/s:200 m maximum
-
Cable length at 50 kbit/s:1000 m maximum
-
CAN termination:120 Ω
-
Power consumption:1.3 W total
-
Operating temperature:0–60 °C
-
Protection:IP20
-
Pin allocation:1 CAN_H; 2 CAN ground; 3 CAN_L; 4 shield
Information
- B&R 3IF771.9 adds a CAN communication path to a compatible aPCI controller while separating the CAN interface electrically from the PLC.
Network selection: Match the communication rate to the installed trunk and participating devices.
Service visibility: Separate transmit and receive indications support tracing of data exchange.
Node selection, bus timing and the physical cable form a coordinated network arrangement. A change to one participant can require corresponding changes in the other devices and the controller configuration.
Transmit and receive indicators expose activity in the two communication directions. They support troubleshooting alongside application status and known-value tests, rather than serving as a complete acceptance result.
3IF771.9 Official Data Sheet
B&R 3IF771.9: original manufacturer technical information covering the specified interfaces and operating limits. PDF · 4 pages.3IF771.9 Installation & Verification Guide
Apter Power guide covering host and node, can wiring, network reach, runtime and data, communication acceptance. PDF · 5 pages.
Application boundary: Network services and data mapping follow the installed application; the interface is not an independent protocol gateway.
Controller CAN expansion
A compatible aPCI host gains one CAN interface without using a separate external gateway.Machine network exchange
CAN participants transfer application data at a bit rate selected for the installed cable reach.Longer CAN trunks
A reduced bit rate supports longer cable routes within the specified 250 or 50 kbit/s limits.Runtime-controlled CAN services
Application communication depends on the compatible aPCI host and its Automation Runtime implementation.
Place equipment influenced by this CAN network in its maintenance state. Determine the expected response to communication loss before disconnecting the module; a silent CAN bus must not leave an uncontrolled actuator enabled.
Trace CAN_H, CAN ground, CAN_L and shield individually. Do not infer pin function from conductor color alone; compare the connector's numbered positions with the retained circuit diagram before insertion.
Measure or establish the installed cable route and select the documented speed/length combination. If the network exceeds the 60 m allowance at 500 kbit/s, correct the design rather than relying on intermittent successful traffic.
Restore the approved Automation Runtime project and restart according to the controller procedure. In an SG4 installation, allow the runtime-managed interface firmware loading to complete before evaluating application communications.
Retain the node address, bit rate, termination locations and successful data-test result. Resolve error counters or unstable communication before returning the connected equipment to its operating state.
Observe TXD/RXD activity and compare a known transmitted value with its destination. Check the return path as well; this distinguishes basic bus activity from correct application mapping and node selection.
Alternative Names
Technical notes
Operating boundary: CAN_H, CAN_L, ground and shield have distinct terminal positions.
Integration details: Match host compatibility, address, bit rate and termination before restoring communication.
FAQ View All FAQ
-
Why do flashing TXD and RXD LEDs on 3IF771.9 not prove correct process data?They show bus activity. Compare a known transmitted value with its intended receiver and return path to verify node selection, payload interpretation and application mapping.
-
How should the bit rate of 3IF771.9 be selected for an extended cable route?Select a supported rate and cable-length combination for the entire network. A short successful test at a higher rate does not demonstrate reliable operation over the installed trunk.
-
What should be checked before changing the address switches on 3IF771.9?Record the original address and compare the proposed address with every participating node and the controller project. A duplicate address or an unchanged software assignment can prevent the intended exchange.
-
Why should CAN ground and shield remain distinct at the 3IF771.9 connector?They have separate connector assignments. Swapping them changes the intended reference and shielding arrangement; trace numbered terminals instead of relying on conductor colors.
-
Can an SG3 firmware procedure be reused for 3IF771.9 in an SG4 controller?The runtime behavior differs. In SG4, interface firmware is loaded through Automation Runtime during restart; retain the correct host project and let that process finish before diagnosing communication.
-
How can termination be assessed when 3IF771.9 traffic is intermittent?Compare the installed termination arrangement with the CAN network drawing and verify the specified resistance across CAN_H and CAN_L. Correct the network arrangement before treating activity LEDs as proof of a healthy bus.
-
Does the isolated interface on 3IF771.9 eliminate wiring-reference checks?No. Isolation does not change connector pin assignments or the network's reference and shield requirements. Inspect those connections together with the receiving devices.
-
What distinguishes a host compatibility problem from a CAN wiring problem on 3IF771.9?First establish that the aPCI host and runtime recognize the interface. Once recognition is correct, trace node address, bit rate, wiring and a known application-data exchange.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-