Match the complete marking
Match the complete B&R 5AC901.BUPS-01 marking, hardware revision and selected configuration to the installed position. Check battery technology and battery arrangement against the installed configuration.
-
Check the offered item before ordering
Request label and connection photographs. Have your maintenance team compare the offered 5AC901.BUPS-01 with the installed equipment and applicable B&R instructions.
Technical specifications for 5AC901.BUPS-01
-
Manufacturer:B&R
-
Product Category:General Automation
-
Spare Part Number:5AC901.BUPS-01
-
Weight:2.55 kg
-
Tariff Code:8537101190
-
Battery technology:Valve-regulated lead acid, rechargeable
-
Battery arrangement:2 x 12 V, connected in series
-
Pack nominal voltage:24 V DC
-
Pack capacity:2.2 Ah
-
Battery temperature sensor:NTC
-
Typical charging current:0.88 A
-
Charging time, discharged battery:5 hours
-
Operating temperature:0 to 40°C
-
Storage temperature:-15 to 40°C
-
Relative humidity:25 to 85%, non-condensing
-
Maximum operating altitude:3000 m
-
Temperature alarm hysteresis:5°C
Information
- B&R 5AC901.BUPS-01 allows a compatible industrial PC UPS to bridge an interrupted supply while the operating system completes its configured shutdown sequence.
Battery arrangement: 2 x 12 V, connected in series
Pack nominal voltage: 24 V DC
An NTC temperature sensor allows the UPS to monitor the battery condition. Operation is specified from 0 to 40°C. Outside the permitted battery temperature range, both charging and backup operation are disabled; the temperature alarm has 5°C hysteresis.
This battery unit is intended exclusively for the 5AC901.IUPS-01 UPS module. Backup time depends on the connected load, state of charge, temperature and battery ageing, so no fixed runtime follows from the battery capacity alone.
5AC901.BUPS-01 Official Technical Excerpt
Original B&R technical material applicable to 5AC901.BUPS-01, covering function, interfaces and operating limits. PDF · 4 pages.5AC901.BUPS-01 Installation & Verification Guide
Apter Power field guide for the selected connection, configuration and functional tests. PDF · 5 pages.
Application scope: The technical values apply to this model in the specified installation and configuration. The examples below address the stated product function.
Controlled PC shutdown
Provide reserve energy for a configured shutdown when normal DC power is interrupted.Compatible UPS battery renewal
Replace the battery unit connected to a 5AC901.IUPS-01 without substituting an unrelated battery design.Temperature-supervised backup
Use the NTC measurement to supervise charging and availability of the backup path.Stored spare maintenance
Maintain charge and storage conditions so that a spare pack is ready for a planned UPS service.
Read the UPS label before connecting the battery pack.
Place the PC and process in an approved shutdown state.
Keep the NTC sensor connection with the battery power connection.
Measure temperature at the battery location rather than relying on cabinet-room temperature.
After installing a discharged pack, allow the specified five-hour charging interval before evaluating backup performance.
Use a controlled loss-of-input test only when the process can tolerate it.
Alternative Names
Technical notes
Separate backup energy from normal power: Place the PC and process in an approved shutdown state. Remember that disconnecting the normal supply alone may leave the UPS powered from its battery; follow the PC service isolation sequence before touching connections.
Allow the charging interval: After installing a discharged pack, allow the specified five-hour charging interval before evaluating backup performance. A partially charged battery can pass a connection check while still being unable to sustain the required PC shutdown.
Record the demonstrated reserve: Retain the installed UPS identity, charge interval, test load and shutdown result in the service record. Use the observed reserve and the process shutdown requirement to determine whether the backup system is ready.
FAQ View All FAQ
-
Does 5AC901.BUPS-01 provide 4.4 Ah because it contains two batteries?No. The two 12 V, 2.2 Ah batteries are connected in series, producing 24 V at 2.2 Ah.
-
Which UPS module accepts 5AC901.BUPS-01?The compatible UPS module is 5AC901.IUPS-01. The battery unit must not be treated as an interchangeable supply for other UPS designs.
-
What happens when 5AC901.BUPS-01 becomes too hot or too cold?Outside its permitted battery temperature range, the UPS disables charging and backup operation. The temperature alarm uses 5°C hysteresis.
-
How does the UPS detect the temperature of 5AC901.BUPS-01?The battery unit incorporates an NTC temperature sensor. Its connection must be preserved together with the power circuit.
-
How long should a discharged 5AC901.BUPS-01 be allowed to charge?The charging time is five hours under the specified charging conditions; typical charging current is 0.88 A.
-
Why is the backup duration of 5AC901.BUPS-01 load-dependent?Runtime changes with PC power demand, available charge, temperature and battery ageing. Capacity alone does not establish a guaranteed shutdown interval.
-
What storage maintenance does 5AC901.BUPS-01 require?Recharge the battery at least every six months during storage and keep it within the permitted storage temperature range.
-
Can 5AC901.BUPS-01 maintain its maximum service life at elevated temperature?Service life is specified up to five years at 20°C and depends on operating cycles. Higher temperature and repeated discharge affect battery ageing.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance