Match the complete marking
Match the complete CP-A RU 1SVR427071R0000 order identity with the installed redundancy unit. Compare input/output terminals, cabinet spacing and any CP-A CM accessory.
-
Check the offered item before ordering
Request current photos of the full label, input/output terminals and fitted accessory. Compare the actual dual-source wiring and offered included items before ordering.
Technical specifications for CP-A RU 1SVR427071R0000
-
Manufacturer:ABB
-
Product Category:General Automation
-
Spare Part Number:1SVR427071R0000
-
Weight:1 kg
-
Tariff Code:8537101190
-
Redundancy inputs:2 independent DC channels
-
Rated input voltage:24 V DC
-
Input range, each channel:10–28 V DC without CP-A CM
-
Input range with CP-A CM:13–28 V DC
-
Rated input current:1–20 A per channel
-
Temporary input current:30 A per channel for 300 s
-
Rated output:24 V DC; 1–40 A
-
Output voltage drop:0.6 V typical; 0.9 V maximum
-
Temporary output current:60 A for 300 s
-
Output at 60 °C:40 A
-
Output at 70 °C:30 A
-
Derating above 60 °C:2.5% per kelvin to 70 °C
-
Reverse-feed resistance:<40 V
-
Protection rating:IP20 housing and terminals
-
Mounting:35 mm DIN rail; horizontal
-
Module spacing:10 mm horizontal; 50 mm vertical
-
Conductor size with ferrule:2.5–10 mm²
-
Conductor size without ferrule:0.5–10 mm²
-
Rigid conductor size:0.5–16 mm²
-
Stripping length:12 mm
-
Terminal tightening torque:1.2–1.5 N·m
-
Operating ambient:−25 to +70 °C; full load to +60 °C
-
Storage ambient:−40 to +85 °C
-
Optional monitor:CP-A CM 1SVR427075R0000; ordered separately
Information
- The CP-A RU sits between two independently supplied 24 V DC sources and the protected load. Internal diodes separate the input paths, while an optional CP-A CM adds per-input monitoring.
Failover behavior: The healthy source carries the full load after the other source is lost.
Optional monitoring: CP-A CM indicates channel undervoltage when separately fitted.
The unit has a typical 0.6 V diode drop, reaching 0.9 V maximum. At an ambient of 70 °C its output rating is 30 A rather than the 40 A available at 60 °C, so the cabinet heat and load must be reviewed together.
ABB requires horizontal DIN-rail mounting with the input terminals at the top and clear space for convection. The CP-A CM monitor is a separate accessory; its presence changes the permissible channel input range and adds status outputs.
CP-A RU 1SVR427071R0000 Original ABB CP-A RU Data Sheet
Original ABB order, connection, installation and rating pages. PDF · 6 pages.CP-A RU 1SVR427071R0000 Installation & Verification Guide
Model-specific dual-source wiring, terminal checks, failover tests and acceptance record. PDF · 2 pages.
Application scope: The unit decouples two sources for one load. Its base function is redundancy; input-voltage monitoring requires the separate CP-A CM accessory.
24 V DC redundant load
Connect two independent sources to INPUT 1 and INPUT 2 and the protected circuit to OUTPUT.Source-failure continuity
Test loss of each source separately and verify the healthy source sustains the full measured load.Optional undervoltage monitoring
Fit CP-A CM only when required and verify threshold and relay behavior for each channel.Cabinet replacement
Match full order code, conductor sizes, mounting clearance and the installed source ratings.
Prove both DC inputs de-energized before changing terminal wiring.
Compare INPUT 1, INPUT 2 and OUTPUT labels with the cabinet schematic.
Size output wiring for total load and use the specified terminal torque.
Mount horizontally and keep 10 mm side and 50 mm vertical clearance.
Check actual load voltage after the diode path.
Disconnect one source at a time under approved conditions and record output continuity.
Alternative Names
Technical notes
Input loading: Each channel is rated to 20 A continuously; size both sources for the complete critical load.
Output derating: Above 60 °C, use the published derating to 30 A at 70 °C.
Accessory boundary: CP-A CM is optional and must not be described as included with the base unit.
Installation: Follow the ABB polarity, mounting, clearance and conductor requirements.
FAQ View All FAQ
-
How should CP-A RU 1SVR427071R0000 be connected to two 24 V supplies?Connect each supply to its own input with the correct polarity and take the common load from OUTPUT. Compare the installation drawing before energizing.
-
Why must each source feeding CP-A RU 1SVR427071R0000 carry the entire load?The remaining source must carry the full load after the other source fails. Check the measured worst-case load against each supply rating.
-
How can CP-A RU 1SVR427071R0000 prevent a failed supply from pulling down the healthy one?Its internal decoupling diodes isolate the two input paths. During acceptance, confirm that loss of either source leaves the load supplied by the other.
-
What changes when a CP-A CM is fitted to CP-A RU 1SVR427071R0000?The accessory monitors each input and offers indication and relay outputs. Verify its presence and threshold setting; it is separate from the base redundancy unit.
-
What spacing is required around CP-A RU 1SVR427071R0000 in a cabinet?Keep at least 10 mm horizontally and 50 mm vertically, with the input terminals at the top. Check the actual neighboring hardware.
-
How should the output wiring of CP-A RU 1SVR427071R0000 be checked?Confirm polarity, conductor rating, fuse protection and the terminal torque. Record the output voltage under the expected load.
-
What current limit applies to CP-A RU 1SVR427071R0000 near 70 °C?The ABB rating falls from 40 A at 60 °C to 30 A at 70 °C. Review the cabinet temperature and worst-case load together.
-
What proof should be retained after replacing CP-A RU 1SVR427071R0000?Record both input voltages, the loaded output, source-loss tests for each channel, conductor torque and the final cabinet labels.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
CP-A RU 1SVR427071R0000Product Details -
3BHE036290R0005 GDC806 B05Product Details -
GJR5143600R0001-35TP90Product Details -
DO801 3BSE020510R1Product Details -
1KHL178025R0102P-COM02Product Details -
3BHE027867R0101Product Details -
APOW-01CProduct Details -
DFC02 DFC-02Product Details -
AFPS-11CProduct Details -
AINT-14CProduct Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.