Technical specifications for 6ES7153-1AA03-0XB0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES7153-1AA03-0XB0
-
Weight:0.5512 lbs (0.25 kg)
-
Tariff Code:8537101190
-
Product type:IM 153-1 DP ST
-
System:SIMATIC ET 200M
-
Module capacity:Up to 8 S7-300 modules
-
Rated supply:24 V DC
-
Supply range:20.4-28.8 V DC
-
Current consumption:350 mA maximum at 24 V DC
-
Backplane output:5 V DC; 1 A maximum
-
Communication:PROFIBUS DP; RS 485
-
Transmission rate:Up to 12 Mbit/s; automatic detection
-
Connector:9-pin Sub-D socket
-
DP address:1-125
-
Power loss:3 W typical
-
Ingress protection:IP20
-
Operating temperature:0-60 °C horizontal; 0-40 °C vertical
Information
- Siemens 6ES7153-1AA03-0XB0. An ET 200M station uses the IM 153-1 as its network head; module order and address allocation remain part of the installed DP configuration.
System: SIMATIC ET 200M
Module capacity: Up to 8 S7-300 modules
Rated supply: 24 V DC
PROFIBUS DP uses an RS 485 interface with a 9-pin Sub-D socket and automatic baud-rate detection up to 12 Mbit/s. Permitted station addresses are 1-125. SYNC and FREEZE are supported; the direct-data-exchange role is sender.
The station accepts up to eight S7-300 modules. Input and output address space is 128 bytes each per module. STEP 7, COM PROFIBUS or a third-party master using the corresponding GSD can configure the station. IP20 protection and orientation-dependent temperature limits apply.
-
Siemens 6ES7153-1AA03-0XB0 technical reference
Original manufacturer data sheet - PDF, 3 pages. Exact-model technical characteristics and manufacturer product identification. -
Siemens 6ES7153-1AA03-0XB0 installation guide
Prepared by Apter Power - PDF, 5 pages. Installed-system review, configuration checks, commissioning and handover.
Configuration scope: Technical values apply to the complete 6ES7153-1AA03-0XB0 execution. Retain the actual installed configuration and applicable Siemens instructions.
-
Remote ET 200M I/O
Use the IM 153-1 as the PROFIBUS head of an ET 200M station. Keep the S7-300 I/O order aligned with the configured station. -
PROFIBUS machine networks
Integrate the station into an RS 485 DP segment. Retain the master configuration, station address and applicable SYNC or FREEZE requirements. -
Station power planning
Plan the interface supply and the I/O backplane budget together. Keep field-load power requirements separate from the interface backplane output. -
Installed-station service
Match the complete interface reference during an ET 200M replacement. Preserve address allocation, bus termination and the orientation-dependent cabinet temperature limits.
The ET 200M station accepts up to eight S7-300 modules. Retain their configured order and address allocation.
The nominal supply is 24 V DC, with a permitted range of 20.4-28.8 V DC.
The network interface uses PROFIBUS DP over RS 485 with a 9-pin Sub-D socket; TCP/IP is not supported.
The interface automatically detects the PROFIBUS transmission rate, up to 12 Mbit/s. All devices and cabling must meet the installed segment requirements.
The backplane output is 5 V DC at up to 1 A. Check the I/O-module power budget separately from field-load power.
The DP station address can be set within 1-125. Preserve the configured address to avoid changing master-to-station mapping.
Alternative Names
Technical notes
System relationship: An ET 200M station uses the IM 153-1 as its network head; module order and address allocation remain part of the installed DP configuration.
Configuration boundary: The operating range is 0-60 °C horizontally and 0-40 °C vertically. The enclosure rating is IP20.
Technical reference: Siemens 6ES7153-1AA03-0XB0 Data Sheet. Technical values apply to the complete 6ES7153-1AA03-0XB0 execution. Retain the actual installed configuration and applicable Siemens instructions.
FAQ View All FAQ
-
How many S7-300 modules can 6ES7153-1AA03-0XB0 connect?The ET 200M station accepts up to eight S7-300 modules. Retain their configured order and address allocation.
-
Which supply range applies to 6ES7153-1AA03-0XB0?The nominal supply is 24 V DC, with a permitted range of 20.4-28.8 V DC.
-
Does 6ES7153-1AA03-0XB0 use Ethernet for its DP connection?No. The network interface uses PROFIBUS DP over RS 485 with a 9-pin Sub-D socket; TCP/IP is not supported.
-
How is the baud rate selected on 6ES7153-1AA03-0XB0?The interface automatically detects the PROFIBUS transmission rate, up to 12 Mbit/s. All devices and cabling must meet the installed segment requirements.
-
What backplane power does 6ES7153-1AA03-0XB0 provide?The backplane output is 5 V DC at up to 1 A. Check the I/O-module power budget separately from field-load power.
-
Which station addresses are permitted for 6ES7153-1AA03-0XB0?The DP station address can be set within 1-125. Preserve the configured address to avoid changing master-to-station mapping.
-
Can 6ES7153-1AA03-0XB0 participate in SYNC and FREEZE?Yes. SYNC and FREEZE are supported, and direct slave-to-slave data exchange is supported in the sender role.
-
How does mounting orientation affect 6ES7153-1AA03-0XB0?The operating range is 0-60 °C horizontally and 0-40 °C vertically. The enclosure rating is IP20.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.