Technical specifications for 6ES5430-4UA12
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES5430-4UA12
-
Weight:0.42 kg
-
Tariff Code:8537101190
-
Input channels:32
-
Isolation:1 group of 32
-
Nominal voltage:24 V DC
-
Logical zero:−3 to 7 V
-
Logical one:13 to 33 V
-
Nominal input current:7 mA
-
Input delay:3 ms typical; 1.4–5 ms
-
Response time:6 ms typical; 4–10 ms
-
Maximum input frequency:100 Hz
-
Simultaneous factor:100%
Information
- Siemens 6ES5430-4UA12 conditions field signals for the S5 input image. Thresholds, response time and the common enable circuit determine whether a transition becomes valid controller data.
Qualification: Voltage thresholds and delay
Common control: Enable circuit and jumper arrangement
Logical zero is −3 to 7 V and logical one 13 to 33 V. The intermediate region is not a guaranteed state. Include input delay and response time when selecting sensors or attempting to capture brief pulses.
F+/F− enable has its own thresholds and wiring requirements. Preserve the approved enable jumper and test it with the inputs. Two-wire BERO connections also have a specific supply requirement beyond a generic nominal-24 V description.
6ES5430-4UA12 Original Technical Excerpt
Siemens SIMATIC S5 U-Periphery, 6ES5 430-4UA12 Technical Data. Selected original pages retain the relevant technical context. PDF · 2 pages.6ES5430-4UA12 Installation & Verification Guide
Apter Power installation workbook covering map group and enable wiring, measure loaded sensor states, restore connectors and reference, validation and handover. PDF · 5 pages.
Application scope: These applications describe the intended system function. Select the actual configuration for that function; accessories are included only when itemized.
Record rack address, terminals, reference and jumper arrangement. Identify separate sensor supplies and isolate the circuits under the approved procedure.
Check representative sensors at module terminals in both states. Include cable drop and residual sensor current when comparing guaranteed thresholds.
Inspect the front connector, common supply/reference and F+/F− arrangement. Avoid assumptions from differently grouped input modules.
Operate known inputs and observe the controller image. Use actual pulse duration and repetition for time-sensitive signals and check adjacent channels.
Test required supply/enable-loss response safely, restore connections and retain measured values and the final map.
Retain the final tested settings, physical connections and accepted operating response for 6ES5430-4UA12.
Alternative Names
Technical notes
Voltage margin: Measure at loaded input terminals; intermediate voltage is not guaranteed logic.
Timing assessment: Combine conditioning delay and controller scan before relying on short events.
Common enable: Check F+/F− and jumpers when group-wide behavior changes.
FAQ View All FAQ
-
Why is a mid-range sensor voltage unreliable at 6ES5430-4UA12?Between 7 and 13 V is outside guaranteed logic regions. Measure under load and correct the circuit so both states meet thresholds.
-
Can isolation between all individual channels be assumed on 6ES5430-4UA12?No. They form one group. Check shared references before connecting signals from different potential systems.
-
Why might a short pulse be missed by 6ES5430-4UA12?Conditioning and response time can prevent it reaching the input image. Test actual pulse width and controller scan behavior.
-
What should be checked if every channel on 6ES5430-4UA12 stops responding?Inspect the shared supply, reference and F+/F− enable before diagnosing independent sensor failures.
-
How does a two-wire BERO sensor affect 6ES5430-4UA12's wiring assessment?Check its 22–33 V supply requirement and residual off-state behavior, then measure loaded input states.
-
Does the 100 Hz limit prove 6ES5430-4UA12 captures every edge?No. Pulse width, input response and program timing also matter. Test the actual waveform and scan path.
-
How should 6ES5430-4UA12 be tested after connector replacement?Check terminal assignments, references and enable, then exercise representative inputs in both states against their controller addresses.
-
Why record the enable jumper before removing 6ES5430-4UA12?It defines the intended common control. Restore and test the approved arrangement rather than assuming identical factory configuration.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.