Technical specifications for 3502E
-
Manufacturer:Invensys
-
Product Category:DCS Systems
-
Spare Part Number:3502E
-
Estimated shipping dimensions:20.3x12.7x5.1cm
-
Weight:0.5 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Module type:TMR digital input with circuit stuck-On self-test
-
Nominal input:48 VAC/VDC
-
Input points:32, commoned in groups of 8
-
Input frequency:DC or 47-63 Hz
-
Recommended input range:35-95 VAC/VDC
-
Maximum voltage:95 VAC/VDC
-
Off-to-On level:27 VAC/VDC typical; 32 VAC/VDC worst-case
-
On-to-Off level:14 VAC/VDC typical; 11 VAC/VDC worst-case
-
Nominal turn-on current:6-9 mA
-
Input impedance:> 2.9 kOhm nominal
-
Input delay:Off-to-On < 8 ms; On-to-Off < 15 ms
-
Point isolation:1,000 VAC minimum; 1,500 VDC minimum
-
Logic power:< 10 W
-
Status indication:One indicator per point; PASS, FAULT and ACTIVE module indicators
-
Slot keys:Top 004; bottom 005
-
Maintenance toggle:Normally Off points: every 24 months, under approved procedure
Information
- 32 points commoned in groups of eight
- 48 VAC/VDC nominal TMR input architecture
- Continuous circuit stuck-On self-test
- PASS, FAULT, ACTIVE and per-point indicators
Each channel independently conditions and scans every 3502E input point, then sends its table to the corresponding Main Processor. The Main Processors vote the input data before the application uses it.
The module requires a matched external termination panel and interface cabling. Mechanical slot keying uses top key 004 and bottom key 005, and the official guide lists field-point toggling for normally Off points at the documented maintenance interval.
Important Notice: Confirm the complete 3502E identity, slot keys, ETP, interface cables, field-voltage range and approved maintenance record before installation or replacement.
These two documents are different: the first consolidates exact-model electrical, diagnostic and slot-key data; the second provides controlled installation, commissioning, testing and acceptance checks.
Technical notes
FAQ View All FAQ
-
What is Invensys Triconex 3502E?It is a 32-point, 48 VAC/VDC TMR digital-input module with a circuit stuck-On self-test.
-
How are Invensys Triconex 3502E points grouped?The 32 input points are commoned in four groups of eight.
-
What input range is recommended for Invensys Triconex 3502E?The manufacturer table lists 35-95 VAC/VDC with a 95 VAC/VDC maximum.
-
How does Invensys Triconex 3502E process input data?Three independent channels condition and scan the points, and the Main Processors vote the resulting input tables.
-
Which indicators are present on Invensys Triconex 3502E?Each point has an On/Off indicator and the module has PASS, FAULT and ACTIVE indicators.
-
Can Invensys Triconex 3502E be maintained as a hot spare?The official guide states that Tricon digital-input modules include the hot-spare feature for controlled online replacement.
-
Which slot keys belong to Invensys Triconex 3502E?The official slot-key table lists top key 004 and bottom key 005.
-
Which Invensys Triconex 3502E points require periodic toggling?The guide lists normally Off points for field-point toggling every 24 months under the approved maintenance procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-