Technical specifications for P0922YU FPS400-24
-
Manufacturer:Invensys
-
Product Category:DCS Systems
-
Spare Part Number:FPS400-24
-
Weight:2.8 kg
-
Tariff Code:8537101190
-
AC input range:85–265 V AC
-
AC input frequency:47–63 Hz
-
DC input range:108–145 V DC; 125 V nominal
-
Input current at 85 V AC:5.6 A RMS maximum
-
Input current at 230 V AC:2.5 A RMS maximum
-
Cold-start inrush:20 A peak at 110 V AC; 40 A peak at 220 V AC
-
Output factory setting:24.0 V DC ±0.2 V
-
Maximum nominal output:400 W; input and temperature derating applies
-
Rated output at 120–240 V AC:24 V DC, 16.7 A before applicable derating
-
Rated output at 100–120 V AC:24 V DC, 14.4 A before applicable derating
-
Line regulation:2.0% of output voltage
-
Load regulation:2.0% of output voltage
-
Ripple/noise bandwidth:20 MHz
-
Output ripple/noise:100 mV peak-to-peak; 10 mV RMS maximum
-
Temperature coefficient:0.025% per °C
-
Soft-start time:3 s typical at 110 V AC; 5 s maximum
-
50–100% load-step recovery:Within regulation limits in 50 ms; excursion <5%
-
Overvoltage shutdown setting:28.0 V DC for FBM/FCM/FCP applications
-
Current-limit level:110% of maximum at the rated 25 °C load
-
Alarm contact arrangement:SPDT / form C: NC, NO and COM
-
Alarm-state threshold:<22 V DC: relay de-energized
-
Power-OK threshold:>23.5 V DC: relay energized
-
DC alarm contact rating:2 A at 30 V DC maximum
-
AC alarm contact rating:2 A at 42.5 V AC maximum
-
Operating temperature:−30 to +71 °C; load derating applies
-
Storage temperature:−55 to +85 °C
-
Relative humidity:5–95%, noncondensing
-
Cooling method:Natural convection; no fan
-
Output-to-chassis isolation test:500 V AC
-
Input-to-chassis isolation test:1500 V AC
-
Calibration:No routine voltage adjustment or calibration required
Information
- Foxboro P0922YU FPS400-24 forms the supply boundary between the incoming distribution circuit and the configured DCS baseplates. Load allocation and the temperature around the supply determine usable capacity, while a separate alarm circuit reports loss of its output.
Fault response: Current limiting and latched overvoltage shutdown require different recovery checks.
Supervision path: Local indicators and a form C contact support independent observation of output health.
The power budget combines installed FBMs, communication or control modules, termination assemblies and any internally powered field circuits. Nameplate power is not a constant rating across the complete thermal and input-voltage envelope. Preserve the applicable static-air derating and installation limits when expanding the subsystem; extra cable outlets do not create additional output capacity.
Output undervoltage and normal-voltage indications support local diagnosis, while the form C relay can operate an externally powered alarm. A healthy indication at the supply does not replace voltage measurement at a distant baseplate. Keep the sealed housing intact, retain free convection and compare source, output and load behavior before deciding which component caused a loss of power.
P0922YU FPS400-24 Official Power Supply Technical Excerpt
Original English input/output ratings, thermal derating, overload behavior and status-relay data for the P0922YU execution. PDF · 10 pages.P0922YU FPS400-24 Installation & Verification Guide
Apter Power acceptance workbook for source identification, load allocation, distribution cables, alarm circuits and recovery checks. PDF · 5 pages.
Application scope: Use it for a defined baseplate load or a separate external field-device load. Thermal capacity, input execution, cable distribution and the actual hazardous-area installation requirements remain part of the system design.
Standard 200 Series baseplates
Supply the installed FBM, FCM or FCP arrangement after summing the individual module and termination-related power requirements.Separate field-device power
Provide an independently allocated supply for external instruments; do not combine them with DIN-rail baseplates on the same FPS400-24.Cabinet power supervision
Connect the form C output to an independently powered alarm circuit so loss of supply output remains observable.Existing supply replacement
Retain P0922YU input selection and match the installed baseplate, input and alarm cables rather than substituting solely by output voltage.
Verify the P0922YU marking and AC/high-voltage DC source before connection; isolate according to the approved cabinet procedure.
Calculate capacity from input voltage, static-air temperature and installation rating before adding loads.
Retain the intended mounting orientation and clearances. Use the specified lower clamp for a vertical DIN rail.
Keep the baseplate supply allocation distinct from any FPS400-24 used for external field devices.
Check relay state and externally powered annunciation, including the expected indication when supply output is lost.
Resolve overload or overvoltage before controlled recovery. Do not open the sealed housing to access its internal fuse.
Alternative Names
Technical notes
Low-line derating: Below 100 V AC, reduce the applicable capacity by 3 W for each volt below 100 V. Apply temperature and installation conditions as well.
Overvoltage reset: After eliminating the cause, interrupt input power under the approved procedure. The overvoltage shutdown resets in less than 30 seconds after input power is removed.
Alarm-contact loading: The relay contact ratings are 2 A at 30 V DC and 2 A at 42.5 V AC. Match the actual alarm circuit voltage and load to the appropriate rating; a current rating alone does not define a suitable alarm circuit.
Cabling and mounting: The supply supports horizontal or vertical DIN-rail installation, with X0175TQ below the unit on a vertical rail. Added cable connections remain subject to the total power budget.
FAQ View All FAQ
-
Can a 300 W load remain connected to P0922YU FPS400-24 at 120 V AC and 60 °C static air?The applicable thermal table limits that condition to 275 W, so 300 W exceeds the stated thermal capacity. Reallocate the load or change the approved installation conditions, and also check the applicable installation rating before acceptance.
-
How does a 90 V AC source change the load budget of P0922YU FPS400-24 at 25 °C?Starting from the 345 W value at 100 V AC, the 3 W/V reduction gives 315 W at 90 V AC. A 320 W load would exceed that derived limit even though 90 V lies inside the input operating range. Check source behavior under load rather than only its open-circuit voltage.
-
Why should the alarm driven by P0922YU FPS400-24 use an external power source?If the alarm is powered only by the output being monitored, loss of that output may silence the annunciator. Test the form C contact with the approved independent alarm supply and verify that loss of output produces the intended indication.
-
How can a normal load transition be distinguished from sustained poor regulation on P0922YU FPS400-24?Observe the output during and after the specified 50–100% load step. The transient may approach the stated less-than-5% excursion, but must recover inside regulation limits within 50 ms. A continuing error after recovery requires investigation of the source, distribution and load.
-
Why can removing an overload restore P0922YU FPS400-24 while clearing an overvoltage cause does not immediately restore output?Current limiting returns to normal when the overload is removed. Overvoltage shutdown requires interruption of input power after its cause has been corrected. Keep these recovery mechanisms distinct and use the approved isolation and restart procedure.
-
Does adding a Y-cable to P0922YU FPS400-24 increase available output power?No. It adds physical connection points, not conversion capacity. Recalculate aggregate module and termination loads against the input- and temperature-dependent power limit before accepting the extra baseplate connections.
-
Why can a baseplate have low voltage while the green indication on P0922YU FPS400-24 remains normal?The indicator observes supply output, whereas cable and connector resistance can cause a drop downstream. Compare supply and baseplate voltages under the actual load, then inspect the approved distribution path before replacing the supply.
-
Can the isolation test voltages of P0922YU FPS400-24 be used as continuous operating ratings?No. Dielectric test values describe insulation verification, not permissible continuous voltage on the output or chassis. Use the specified input/output operating ranges and the approved grounding arrangement; any insulation testing must follow the equipment procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.