Match the complete marking
Include MU-TAMR03 51309218-125 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered MU-TAMR03 51309218-125 with the installed equipment and applicable Honeywell documentation.
Technical specifications for MU-TAMR03 51309218-125
-
Manufacturer:Honeywell
-
Product Category:DCS Systems
-
Spare Part Number:MU-TAMR03 51309218-125
-
Weight:0.78 kg
-
Tariff Code:8537101190
-
RTD input channels:16
-
Assembly planning supply basis:24 V DC
-
Assembly planning current:185 mA
-
FTAs per documented adapter:2
-
Combined LLMux group:32 channels
-
Maximum FTA-to-adapter run:305 m
-
Terminal type:Compression
-
Documented RTD connection:3 wire, with the applicable LLMux processor
-
Pt100 DIN conversion range:-200 to +850 °C, matched RTD chain
-
Pt100 JIS conversion range:-200 to +650 °C, matched RTD chain
-
Ni120 conversion range:-45 to +315 °C, matched RTD chain
-
Cu10 conversion range:-20 to +250 °C, matched RTD chain
-
Maximum RTD lead resistance:15 ohm, documented matched chain
Information
- This assembly terminates RTDs in the LLMux chain; thermocouple FTAs and their cold-junction-reference arrangements serve a different sensor function.
Mixed-group integration: RTD and thermocouple groups can share the documented adapter architecture.
Orientation-controlled service: Relay position and grounded mounting are retained during replacement.
Each RTD FTA communicates through the LLMux power adapter. Two FTAs can be the same or different sensor types, so an RTD group can share an adapter with an approved thermocouple group while retaining separate assignments.
Mount the relay assembly with its power-connector side up in the approved shielded and grounded enclosure. The 185 mA value is an assembly entry in the 24 V DC cabinet-planning table and must not be interpreted as RTD excitation current.
Honeywell MU-TAMR03 51309218-125 Technical Planning Excerpt
Original manufacturer assembly-identification and applicable planning pages.MU-TAMR03 51309218-125 Engineering Field Guide
Identify the RTD daughterboard, Capture sensor lead assignments, Maintain upright orientation.
Application scope: Keep the power-connector side up for the mercury-wetted relay arrangement.
RTD field groups
Terminate resistance-temperature sensor circuits in the documented LLMux system.Mixed temperature cabinets
Preserve independent RTD and thermocouple group assignments on a shared adapter.Remote RTD enclosure
Use the approved cable route, grounded mounting channel and shielded enclosure.Temperature maintenance
Validate representative RTD readings after reconstructing the terminal map.
Match the actual sensor function before approving an FTA.
Record the installed RTD conductor arrangement from the wiring drawing.
Retain the power-connector-side-up mounting position.
Check the mounting channel and enclosure safety-ground connections.
Use assembly planning current only for its stated budget purpose.
Verify representative RTD channels against accepted plant references.
Alternative Names
Technical notes
Sensor function: The RTD daughterboard is distinct from the thermocouple local or remote CJR versions.
Planning-current boundary: 185 mA is the FTA assembly planning allowance, with no RTD excitation claim implied.
Installed orientation: Keep the power-connector side up for the mercury-wetted relay arrangement.
FAQ View All FAQ
-
Can a thermocouple FTA serve as a direct replacement for MU-TAMR03 51309218-125?The motherboard and daughterboard combination determines sensor function. Verify the RTD assembly identity because thermocouple versions use different input and reference arrangements.
-
Does the 185 mA figure describe RTD excitation in MU-TAMR03 51309218-125?It is the assembly-current entry in the 24 V DC planning table. Retain the installed sensor specification for any excitation or resistance-measurement assessment.
-
What mounting position must be preserved for MU-TAMR03 51309218-125?The power-connector side faces upward for the mercury-wetted relays. Record the mounting direction and inspect it after assembly replacement.
-
How should the RTD conductor map be captured before removing MU-TAMR03 51309218-125?Label each sensor conductor and terminal according to the approved drawing. Preserve the original sensor lead configuration rather than assuming another RTD wiring arrangement.
-
Can MU-TAMR03 51309218-125 share the adapter with a thermocouple group?The documented two-FTA arrangement permits mixed types. Verify the group assignments independently and compare readings on each sensor group.
-
What should be inspected when several channels of MU-TAMR03 51309218-125 drift together?Review shared FTA connections, adapter cable and enclosure grounding with the approved diagnostic procedure. Compare multiple known sensor references before replacing individual RTDs.
-
Why does the remote enclosure matter for MU-TAMR03 51309218-125?The FTA requires electromagnetic shielding, a grounded mounting channel and appropriate environment. Check those conditions at the actual remote location.
-
How should the coated alternative be distinguished from MU-TAMR03 51309218-125?MC-TAMR03 51309218-175 is the coated execution. Match the complete part marking and environmental basis before considering it.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.