Technical specifications for CC-PAIH01
-
Manufacturer:Honeywell
-
Product Category:DCS Systems
-
Spare Part Number:CC-PAIH01
-
Estimated shipping dimensions:15.8x5.7x14.6cm
-
Weight:0.4 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Input type:Voltage or current; 2-wire or self-powered transmitters
-
Channels:16; 12 single-ended / 4 differential
-
Voltage-input channels:13 to 16
-
A/D resolution:16 bit
-
Ranges:0-5 V; 1-5 V; 0.4-2 V; 4-20 mA through 250 Ohm
-
CMRR:70 dB, dc to 60 Hz
-
Common-mode voltage:-6 to +5 V peak
-
NMRR:19 dB at 60 Hz
-
Input filter:Single pole; -3 dB at 6.5 Hz
-
Maximum differential input:+/-30 V
-
Crosstalk:-60 dB
-
Powered input impedance:>10 MOhm
-
Scan period:50 ms
-
Accuracy at 23.5 +/-2 degC:+/-0.075% FS
-
Accuracy at 0 to 60 degC:+/-0.15% FS
-
Compatible IOTAs:CC-TAIX01; CC-TAIX11 redundant
Information
- Processes sixteen high-level analog channels
- Supports HART communication with connected field devices
- Provides four differential voltage-input positions
- Offers open-wire detection and loop diagnostics
CC-PAIH01 operates with CC-TAIX01 or redundant CC-TAIX11 IOTA, HART or conventional transmitters, Series-C carrier, Experion control and asset configuration.
Engineered applications include HART pressure-transmitter integration, Multivariable flow measurement, Process analog acquisition, Redundant analog-input renewal.
Important Notice: Confirm the CC-TAIX01/CC-TAIX11 arrangement, IOTA jumpers, voltage-channel allocation, loop power and HART device identity before scanning and diagnostics.
Apter Power CC-PAIH01 Manuals and Guides
Apter Power CC-PAIH01 Product and System Technical Reference PDFApter Power CC-PAIH01 Field Installation and Functional Acceptance Workbook PDFThe first document organizes model-specific identity, technical data and system context. The second provides a separate installation, connection, commissioning and acceptance workflow.
HART pressure-transmitter integration
Collects process variables and device-status data from HART transmitters.
Multivariable flow measurement
Brings multiple variables from supported field instruments into Experion.
Process analog acquisition
Conditions conventional voltage or current signals for control strategies.
Redundant analog-input renewal
Restores input hardware while retaining HART addressing and channel ranges.
Verify the complete CC-PAIH01 marking and its assigned HART high-level analog-input position before work.
Place the connected process and control strategy in the approved maintenance state.
Isolate the applicable cabinet supply and analog and HART field energy before disconnecting conductors.
Record terminal numbers, channel assignments, polarity, shields and configured ranges before removal.
Use ESD controls and protect the backplane connector, terminal hardware and coated electronics.
Confirm the installed CC-TAIX01 or CC-TAIX11 IOTA and carrier arrangement against the approved project.
Restore power in a controlled sequence and clear only diagnostics created by the maintenance activity.
Complete analog scaling, open-wire and HART communication checks and retain the measured result before returning the channel to automatic service.
Technical notes
FAQ View All FAQ
-
What exact Honeywell system position is intended for CC-PAIH01?CC-PAIH01 is assigned to the documented Experion Series-C I/O role as high-level analog input module with hart; confirm that role against the installed cabinet record.
-
Which field signal or controlled function is handled by CC-PAIH01?Its documented signal duty is high-level analog current/voltage inputs plus hart digital communication. The controlling source lists channels as 16; 12 single-ended / 4 differential.
-
Which companion hardware must be checked before installing CC-PAIH01?Match CC-PAIH01 with CC-TAIX01 or redundant CC-TAIX11 IOTA and HART or conventional transmitters; also retain the approved carrier, cable and project identity.
-
What electrical limit should an engineer verify before wiring CC-PAIH01?Verify the model-specific value for A/D resolution: 16 bit. Do not transfer a limit from another module revision.
-
How should the installed configuration be preserved when replacing CC-PAIH01?Record the as-found slot, connector, channel assignment and project revision, then restore only the approved Experion Series-C I/O configuration.
-
Which isolation or handling check applies to CC-PAIH01?Apply the isolation and ESD sequence stated for CC-PAIH01; the source also identifies cmrr as 70 dB, dc to 60 Hz.
-
What diagnostic or commissioning evidence is required for CC-PAIH01?Complete the model-specific functional check for hart pressure-transmitter integration, review host diagnostics and retain the final test result.
-
Can CC-PAIH01 be substituted for a visually similar Honeywell assembly?No automatic substitution is assumed. Compare the complete CC-PAIH01 marking, input type, companion hardware, signal duty and approved system revision.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.