Match the complete marking
Include DS2020DACAG2 and any series, revision or assembly markings. Keep the complete reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label, connector and mounting photos. Have your maintenance team compare the offered DS2020DACAG2 with the installed equipment and applicable GE documentation.
Technical specifications for DS2020DACAG2
-
Manufacturer:General Electric
-
Product Category:Gas Turbine Control
-
Spare Part Number:DS2020DACAG2
-
Weight:19.8 kg
-
Tariff Code:8537101190
-
Product series:Mark VIe
-
Product function:AC-DC power conversion
-
Nominal input:115/230 V AC, selectable
-
AC input range:105–132 / 210–265 V AC
-
Input frequency:47–63 Hz
-
Nominal DC output:125 V DC; approximately 1000 W
-
Output voltage range:90–145 V DC at 1–9.5 A over input range
-
Continuous output current:9.5 A DC at -30 to 45 °C
-
High-temperature derating:Linear to 7.5 A DC at 60 °C
-
Two-module parallel limit:16.5 A DC total; same AC source
-
Output ripple:4 V peak-to-peak
-
Power connector:12-position JZ; PDM JZ2 or JZ3
-
Input selection:JTX1: 115 V AC; JTX2: 230 V AC
-
Ambient temperature:-30 to 60 °C; free convection
-
Relative humidity:5–95%, non-condensing
Information
- GE DS2020DACAG2 supplies the DC power-distribution path in applicable Mark VIe control systems and connects to the PDM through a common input/output harness.
System family: Mark VIe control-power distribution
Nominal input: 115/230 V AC, internally selected
Nominal output: 125 V DC, approximately 1000 W
The nominal input is selected inside the module by placing the captive cable in JTX1 for 115 V AC or JTX2 for 230 V AC. The permitted ranges are 105 to 132 V AC or 210 to 265 V AC at 47 to 63 Hz. A single 12-position JZ connector carries the AC input and DC output through the harness to PDM connector JZ2 or JZ3, and four base mounting holes secure the module. The selector must match the actual source before energization. Where incoming-line harmonic attenuation is required, the installation needs a suitable input filter.
A single DS2020DACAG2 is rated for 9.5 A DC from -30 to 45 °C, with linear derating to 7.5 A DC at 60 °C under free-convection conditions. Two G2 modules may operate in parallel for a maximum recommended total panel current of 16.5 A DC, provided they share the same AC source and the specified current-sharing conditions. This limit is lower than twice the individual rating because of output-voltage and impedance variation. The G2 design replaces DS2020DACAG1 in systems using that earlier version, but G1 paralleling is not recommended. The module has no built-in diagnostic features; installation checks must establish the supply selection, output loading and connection condition.
-
GE DS2020DACAG2 original technical excerpt
GEH-6721G - PDF, 5 pages. Original AC-DC conversion, input selection, loading and environmental data. -
GE DS2020DACAG2 installation guide
Prepared by Apter Power - PDF, 5 pages. Supply selection, JZ connections, thermal limits and parallel-operation checks.
Operating configuration: Single-module and two-module parallel arrangements have different current limits. The application must preserve the specified ambient-temperature derating and equal-source conditions.
-
AC-fed control-power conversion
Convert a selected 115 or 230 V AC source into DC control power. Use the applicable PDM harness and verify the actual output under the intended load. -
Control-power ride-through
Local capacitor energy supports the DC bus during a loss of control power. Available hold-up time depends on initial input voltage and the connected constant-power load. -
Parallel G2 power arrangements
Use two G2 modules on one AC source where the panel design requires greater current. Respect the 16.5 A DC total limit and confirm current sharing. -
Earlier DACA replacement
DS2020DACAG2 is a replacement for DS2020DACAG1 in systems using the earlier version. Preserve the selected input voltage, harness arrangement and cabinet mounting.
Isolate the incoming supply before service. Allow the specified one-minute discharge interval, then verify residual voltage under the approved site procedure before handling connections.
Use JTX1 for nominal 115 V AC or JTX2 for nominal 230 V AC. Confirm the source voltage and selector before energizing DS2020DACAG2.
Identify the single 12-position JZ power harness and its PDM JZ2 or JZ3 destination. Secure the four base mounting points and restore the correct connector arrangement.
Keep the installation within -30 to 60 °C with free convection. Above 45 °C, reduce the output rating linearly from 9.5 A to 7.5 A at 60 °C.
Connect both G2 modules to the same AC source. Limit total panel current to 16.5 A DC and assess individual current sharing; do not apply this arrangement to G1 modules.
Measure the DC output under the intended load and review capacitor condition and service history. The module has no built-in diagnostics, and capacitor aging depends on ambient temperature.
Alternative Names
Technical notes
System relationship: Match JTX1 to 115 V AC or JTX2 to 230 V AC. Check the 12-position JZ harness to PDM JZ2 or JZ3 before applying power.
Configuration boundary: Output ratings depend on input voltage, load and ambient temperature. Parallel operation requires two G2 modules on the same AC source and a 16.5 A DC total-current limit.
Technical reference: GEH-6721G, Mark VIe Control System Guide, Volume II — DS2020DACAG2 AC-DC power conversion excerpt.
FAQ View All FAQ
-
What does GE DS2020DACAG2 do?It converts a selected 115/230 V AC supply into nominal 125 V DC control power for applicable Mark VIe systems. Local capacitor energy supports ride-through during loss of control power.
-
How is the input voltage selected on DS2020DACAG2?The internal captive cable connects to JTX1 for 115 V AC or JTX2 for 230 V AC. Confirm the selection before applying power; the allowed input ranges are 105–132 or 210–265 V AC at 47–63 Hz.
-
Is the output of DS2020DACAG2 fixed at 125 V DC?125 V DC is the nominal value. Across the full input range, output is specified as 90–145 V DC with a 1–9.5 A load. The operating point depends on input voltage and load.
-
What current can one DS2020DACAG2 supply?One module is rated for 9.5 A DC from -30 to 45 °C. Above 45 °C, linearly derate the rating to 7.5 A DC at 60 °C under free-convection conditions.
-
Can two DS2020DACAG2 modules operate in parallel?Yes, with both G2 modules connected to the same AC source and the specified current-sharing conditions. The maximum recommended total panel current is 16.5 A DC, not 19 A.
-
Which connector carries power on DS2020DACAG2?A single 12-position JZ connector carries AC input and DC output through the harness to PDM connector JZ2 or JZ3. JTX1 and JTX2 are the separate internal input-selection positions.
-
Can DS2020DACAG2 replace DS2020DACAG1?The G2 design is a drop-in replacement for G1 in systems using the earlier version. Preserve the installed input selection, harness and mounting arrangement. G1 paralleling is not recommended.
-
Does DS2020DACAG2 provide built-in diagnostics?No built-in diagnostic features are provided. Check the actual AC selection, DC output, load and connection condition using the applicable commissioning or maintenance procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.