Match the complete marking
Include 136711-02 and any visible revision or approval marking in your enquiry. Compare the rear I/O label with the installed 3500/61 monitor and rack drawing.
-
Check the offered item before ordering
Request clear photographs of the actual 136711-02 label, terminals and barrier assembly. Have your maintenance team compare the offered part with the installed equipment, the approved IS drawing and the applicable Bently Nevada documentation.
Technical specifications for 136711-02
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:136711-02
-
Estimated shipping dimensions:2.3x18.5x24.1cm
-
Weight:0.94 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Spare-part identity:136711-02; 3500/61-specific I/O assembly
-
I/O execution:RTD/TC non-isolated
-
Barrier arrangement:Internal barriers
-
Field termination:Internal terminations
-
Matching monitor:3500/61 temperature monitor with recorder outputs
-
Host signal capacity:1 to 6 RTD or thermocouple channels; host system
-
Required IS earth module:3500/04-01 in a rack containing internal barriers
-
Rack configuration software:Revision 2.3 or later for internal-barrier support
-
3500/61 host firmware:Revision 1.06 E or later for internal-barrier support
-
External termination option:Unavailable with internal-barrier I/O
-
TMR rack option:Not compatible with internal-barrier I/O
-
Safe/hazardous wiring separation:50 mm (2 in) in the documented rack layout
-
Rack position:General-purpose position; plan added depth and access
Information
- The 136711-02 spare is the field-interface half of a 3500/61 temperature channel; its internal barrier arrangement changes the rack earthing and field-wiring requirements.
Rack readiness: Check the dedicated IS earth position and the internal-barrier software and firmware revisions before exchange.
Field interface: Keep the intrinsic-safety wiring route and internal termination arrangement aligned with the approved installation.
Internal barriers form the intrinsically safe interface to approved field transducers. Their rack installation needs a dedicated 3500/04-01 IS Earthing Module and a wiring layout that maintains the prescribed separation between hazardous-area and safe-area circuits. This execution cannot be changed to an external termination or a TMR arrangement by moving connectors.
Before exchange, record the installed spare marking, rack position, monitor firmware, rack-configuration software and each connected sensor circuit. After installation, verify the earthing path, termination identity and channel behavior under the approved site procedure. Treat any change to the sensor or barrier scheme as an engineering review of the complete system.
-
Bently Nevada 3500/04 Internal Barriers excerpt
Original 141495 Rev. R pages identifying 136711-02 and the rack installation boundaries. -
Bently Nevada 136711-02 engineering guide
Apter Power installation, configuration, diagnostic and acceptance guidance.
Platform applications: The uses below depend on the installed controller configuration and approved system design.
-
3500/61 temperature rack
Provide the internal-barrier field interface for a matching six-channel temperature monitor. -
Hazardous-area sensor circuits
Connect approved RTD or thermocouple paths through the specified IS barrier architecture. -
Existing-rack upgrade
Replace a standard I/O assembly only after checking rack earth, depth, firmware and approved field wiring. -
Service replacement
Restore the same I/O execution while retaining the existing monitor and validated channel configuration.
Compare the 136711-02 rear I/O label with the adjacent 3500/61 monitor and rack drawing.
Verify the dedicated 3500/04-01 earthing module before energizing barrier-connected circuits.
Check 3500/61 firmware 1.06 E or later and rack configuration software 2.3 or later.
Trace hazardous and safe wiring and preserve 50 mm physical separation in the documented rack layout.
Do not use external terminations or a TMR rack arrangement with this internal-barrier execution.
Inject or simulate an approved RTD/TC input and verify monitor indication, alarms and recorder path separately.
Alternative Names
Technical notes
Assembly identity: 136711-02 is the non-isolated internal-barrier I/O spare with internal terminations for the 3500/61 monitor.
Installation boundary: Verify the dedicated 3500/04-01 IS Earthing Module, approved field wiring, rack software and monitor firmware before exchange.
Technical reference: Bently Nevada 3500/04 Internal Barriers, 141495 Rev. R; 3500/60 and 3500/61 Temperature Modules, 141540 Rev. L.
FAQ View All FAQ
-
Why does 136711-02 require an IS earthing module in the rack?Its internal barriers use the rack backplane IS earth connection. Verify a dedicated 3500/04-01 earthing module and the approved earth path before connecting hazardous-area field circuits.
-
Can 136711-02 use an external termination block instead of its internal terminations?No. The internal-barrier execution is specified with internal terminations; the manufacturer excludes the external-termination option for this barrier architecture. Reconcile field wiring to the installed connector layout.
-
What rack configuration software is needed before fitting 136711-02?The internal-barrier guidance calls for revision 2.3 or later of the 3500 Rack Configuration Software for a 3500/61 installation. Check the archived rack project and its software revision before service.
-
Which 3500/61 firmware boundary matters for 136711-02?The internal-barrier datasheet lists 3500/61 firmware 1.06 E or later. Record the installed monitor firmware and confirm support before replacing its I/O assembly.
-
Can 136711-02 be used in a 3500 TMR temperature-monitor arrangement?No. The manufacturer excludes internal-barrier I/O from TMR rack options because connecting one transducer to multiple I/O inputs would compromise the intrinsically safe system. Verify the rack topology before ordering.
-
How should 136711-02 be positioned beside standard I/O modules?An internal-barrier I/O assembly may occupy a general-purpose rack position and sit next to standard I/O. Its greater depth needs maintenance clearance, and the installed layout must retain 50 mm separation of safe and hazardous field wiring.
-
What must be checked when upgrading a standard rack to 136711-02?Confirm the matching 3500/61 monitor, dedicated IS earth, configuration-software and firmware revisions, cabinet clearance and approved sensor circuits. Replace the I/O assembly only within the documented internal-barrier design.
-
How can 136711-02 be accepted after replacement without confusing it with the front monitor?Verify the rear I/O marking and terminations, inspect the IS earth and field segregation, then prove each affected RTD/TC input through the front 3500/61 indication and alarm path. Check recorder outputs as a separate host-monitor function.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-