The smaller tip does not reduce the side-view or tip-spacing requirements of the 8 mm system. Leave the electrical clearance dictated by the transducer arrangement rather than choosing a closer spacing solely from the probe body diameter.
Important Notice: Keep the selected sensor and extension cable associated with their electrical system length; do not transfer the performance limits of an all-XL 8 mm system to this 5 mm probe channel.
The technical excerpt covers transducer construction and performance. The installation guide develops mounting, connection and signal-verification procedures for the selected assembly.