ABB 1SAP140500R0271 PM585-ETH is an AC500 V2 processor module for modular industrial automation. It executes the PLC application and coordinates compatible local or remote I/O.
- 1024 kB Flash EPROM and RAM program memory
- Ethernet plus two configurable RS-232/RS-485 interfaces
- One FieldBusPlug interface and up to four communication modules
- Up to 10 central S500 or S500-eCo expansion modules
The PM585-ETH executes cyclic, time-controlled or multitasking PLC logic and exchanges digital and analog process data with connected I/O. It has no onboard DI, DO, AI or AO channels. COM1 and COM2 support programming, Modbus master/slave and serial ASCII; COM1 also supports CS31 master. The R0271 CPU uses an R0270 TB511-ETH, TB521-ETH or TB541-ETH terminal base, which provides the Ethernet RJ45 connection.
Important Notice: Terminal base, memory card, communication modules, I/O modules, manuals, software and other accessories are not included unless specifically stated in the quotation or stock description.
Apter Power 1SAP140500R0271 PM585-ETH Manuals and Guides
Important Notice: These are two separate Apter Power documents independently prepared from manufacturer-published ABB information. Confirm the physical nameplate, current ABB documents, and host-system requirements before configuration or installation. They do not replace official ABB manuals.
Machine & Material Handling
Coordinates modular I/O and Ethernet or serial communications in machinery and material-handling automation.
Water & Wastewater
Executes PLC logic for distributed pumps, valves and instrumentation connected through compatible I/O.
Building & HVAC
Supports modular control panels using S500/S500-eCo I/O and configured Ethernet or serial data exchange.
Food, Beverage & Marine
Applies AC500 V2 control and diagnostics in ABB-listed food, beverage and marine industrial applications.
Use the complete ABB identity and the current host-system documentation before installation, replacement or commissioning.
1Match the complete 1SAP140500R0271 code; 1SAP140500R0379 is a different PM585-MC-KIT.
2Use an R0270 TB511-ETH, TB521-ETH or TB541-ETH terminal base.
3Do not describe architecture limits as onboard channel counts; the CPU has no onboard process I/O.
4Verify firmware, communication modules and I/O compatibility in ABB Automation Builder and current manuals.
5Back up the application and parameters before replacement, firmware work or commissioning.