Technical specifications for AAI143-H00 S1
-
Manufacturer:Yokogawa
-
Product Category:DCS Systems
-
Spare Part Number:AAI143-H00 S1
-
Weight:0.24 kg
-
Tariff Code:8537101190
-
Product series:CENTUM FIO
-
Reference design:AAI143-H
-
Base input channels:16
-
Base input signal:4 to 20 mA
-
Base allowable input current:24 mA
-
Base analog accuracy:±16 µA
-
Base analog update period:10 ms
-
Isolation boundary:Input to system
-
Transmitter selection:2-wire / 4-wire, setting pin per channel
-
Digital communication:HART
-
HART design capacity:Up to 16 devices; 32 variables/module
-
Field connections:Pressure-clamp terminal / MIL / KS1 cable
Information
- Yokogawa AAI143-H00 S1 brings transmitter loop signals and supported HART variables into the FCS input/output image for use by the control application.
Base input channels: 16, 4–20 mA
Digital communication: HART on the AAI143-H design
Transmitter selection: Two-wire or four-wire setting by channel
For each channel, a setting pin selects a two-wire or four-wire transmitter arrangement. In two-wire service the module provides transmitter power, with at least 19.0 V at 20 mA and no more than 25.5 V at zero current, subject to the base-design 25 mA output-current limit. External wiring voltage drop must be included in the loop calculation. A Zener barrier cannot be connected to this module; an isolation barrier is required for the applicable intrinsically safe arrangement.
The AAI143-H design communicates with HART field devices and places analog data and HART variables in the I/O image. The FCS accesses that image for regulatory or sequence functions. The referenced HART implementation supports up to 16 devices and 32 HART variables per module; multidrop use is limited to input devices and does not support the analog value or burst function. Analog scan timing and HART-variable refresh are different, so control design must use the relevant update behavior.
-
Yokogawa AAI143-H00 S1 technical reference
Original manufacturer excerpt. Base-design specifications and configuration requirements; match the complete offered marking. PDF, 6 pages, 288.7 KB. -
Yokogawa AAI143-H00 S1 installation guide
Prepared by Apter Power. Product-specific preparation, interface checks, commissioning and functional acceptance. PDF, 5 pages, 26.6 KB.
Application scope: The following uses describe the supported base-design role. Confirm AAI143-H00 S1 against the installed host and configuration before replacement.
-
Process transmitter acquisition
Bring 4–20 mA measurements into the FCS for regulatory and sequence functions, using the correct transmitter wiring and channel configuration. -
HART variable integration
Use supported field-device variables through the I/O image. Account for HART refresh behavior separately from the analog scan. -
Two-wire loop integration
Supply and read compatible two-wire transmitters through the configured channels, allowing sufficient voltage margin for wiring and field devices. -
Redundant analog input stations
Use a supported matched pair and adjacent odd/even slots where the configured FIO system requires redundant HART-capable analog modules.
Confirm the per-channel two-wire or four-wire setting before connection. Do not assume the old and replacement module settings match.
Include field-wire voltage drop when evaluating transmitter supply. Preserve polarity and the correct source of loop power.
Do not connect a Zener barrier to the AAI143 design. Review an isolation barrier and the full intrinsic-safety configuration where applicable.
The analog update period and HART-variable refresh serve different functions. Verify each against the control application.
Use the approved matching modules and adjacent-slot arrangement when the system is configured for redundant HART analog I/O.
Check low, mid and high test points, channel scaling and the assigned HART variables before releasing the loop to service.
Alternative Names
Technical notes
System relationship: Verify 4–20 mA signal type, two-wire/four-wire pin settings, polarity, transmitter supply and isolation-barrier arrangement.
Configuration boundary: The technical data describes the AAI143 base design. Match the complete AAI143-H00 S1 marking, style and installed configuration; do not transfer later suffix approvals or ratings automatically.
Technical reference: Yokogawa Analog I/O Modules (for FIO), GS 33J60F60-01EN, 6th edition.
FAQ View All FAQ
-
What analog signals does AAI143-H00 S1 process?The AAI143-H base design provides sixteen 4–20 mA input channels with isolation between input and system.
-
What analog update period applies to the base design of AAI143-H00 S1?The analog data update period is 10 ms. HART-variable refresh is a separate communication process and must not be treated as the analog scan period.
-
How are two-wire and four-wire transmitters selected on AAI143-H00 S1?The AAI143 base design uses a setting pin for each channel to select the two-wire or four-wire transmitter arrangement.
-
Does AAI143-H00 S1 support HART communication?The AAI143-H design supports HART communication and makes supported field-device variables available through the FCS I/O image.
-
Can a Zener barrier be connected to AAI143-H00 S1?The AAI143 reference prohibits a Zener barrier. Use the appropriate isolation barrier for an intrinsically safe application and verify the complete installation.
-
What analog accuracy applies to the base design of AAI143-H00 S1?The reference accuracy is ±16 µA with an allowable input current of 24 mA. Apply the actual installed revision and operating conditions.
-
How should transmitter power be evaluated for AAI143-H00 S1?For the base two-wire circuit, transmitter power is at least 19.0 V at 20 mA and no more than 25.5 V at zero current. Allow for voltage drop in the external loop wiring.
-
What HART multidrop limitation matters for AAI143-H00 S1?The referenced HART implementation permits input-device multidrop connections only; analog-value transfer and burst function are not supported in that arrangement.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.