Match the complete marking
Match the complete Siemens 6ES7131-4BF00-0AA0 marking and installed configuration. Confirm the full module reference, terminal base and interleaved channel assignments.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 6ES7131-4BF00-0AA0 with the installed equipment and applicable Siemens documents.
Technical specifications for 6ES7131-4BF00-0AA0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES7131-4BF00-0AA0
-
Weight:0.04 kg
-
Tariff Code:8537101190
-
Digital inputs:8
-
Rated supply:24 V DC
-
Input address space:1 byte
-
Parameter length:3 bytes
-
Logic 1 range:15–30 V
-
Logic 0 range:-30 to +5 V
-
Input current at logic 1:5 mA typical
-
Input delay:3 ms typical; 2–4.5 ms
-
Two-wire sensor leakage:1.5 mA maximum
-
Cable length, unshielded:600 m maximum
-
Cable length, shielded:1000 m maximum
-
Isochronous operation:Supported
Information
- Siemens 6ES7131-4BF00-0AA0 provides compact binary acquisition with per-channel indication. Correct terminal order, sensor leakage and input filtering matter when the module is used for machine-state or interlock feedback.
Sensor integration: Contacts and compatible two-wire sensors
Local inspection: Individual green state indications
Two-wire sensors need a suitable supply distribution arrangement and acceptable off-state leakage. Additional terminals may be needed at the selected base. Review both the active signal voltage and the inactive state before accepting a sensor circuit.
Input delay filters short disturbances and affects detection of fast events. Use the module within its intended digital-state application, and verify the complete input-to-program response. Individual LEDs support troubleshooting but this execution does not provide module diagnostic functions.
6ES7131-4BF00-0AA0 Original Technical Excerpt
Siemens 8DI DC24V Manual, A5E01077339-02. Selected original pages retain the relevant technical context. PDF · 6 pages.6ES7131-4BF00-0AA0 Installation & Verification Guide
Apter Power installation workbook covering map the eight field signals, restore the terminal assignment, measure active and inactive states, testing and handover. PDF · 5 pages.
Application scope: The applications describe the complete signal or control path. Confirm the intended function and interface; accessories are supplied only when itemized.
Machine-state feedback
Acquire contact or compatible sensor states for a PLC program.Distributed interlocks
Transfer configured binary conditions through an ET 200S station.Two-wire sensor groups
Connect sensors with suitable leakage and supply distribution.Timed digital acquisition
Use in a compatible configured isochronous station when required.
Label each sensor or contact with its assigned DI number and controller bit. Record sensor supply distribution and any application substitution before isolating the field circuits.
Wire according to the interleaved DI terminal arrangement. Inspect the selected terminal base and provide the necessary sensor-supply distribution without confusing AUX and input terminals.
Check both voltage states with the actual sensor connected. For two-wire sensors, review leakage and confirm a reliable inactive state. Inspect shared reference and shielding where disturbances are present.
Operate each signal under controlled conditions and compare LED, raw input byte and application response. Include timing checks when pulse duration or synchronous acquisition matters.
Remove temporary forces or substitutions and test the required process permissives. Retain final channel mapping and any timing or leakage findings.
Retain the final tested settings, physical connection and accepted process response for 6ES7131-4BF00-0AA0.
Alternative Names
Technical notes
Interleaved terminal order: Verify DI0–DI7 against the actual terminal numbering and controller byte mapping.
Off-state acceptance: Two-wire leakage and the resulting input voltage must permit a reliable zero state.
Diagnostics boundary: Channel LEDs are state indicators; this module does not provide wire-break diagnostic functions.
FAQ View All FAQ
-
Why can sequential terminal wiring produce wrong bits with 6ES7131-4BF00-0AA0?Its terminal assignment interleaves channel numbers across the two terminal columns. Verify each conductor against the intended DI number and PLC bit.
-
How can two-wire sensor leakage affect 6ES7131-4BF00-0AA0?Excessive off-state leakage can prevent a reliable zero. Check both the sensor leakage specification and the measured inactive input voltage.
-
Can 6ES7131-4BF00-0AA0 reliably capture every very short pulse?Input filtering introduces delay. Compare the pulse duration and application sampling with the complete input path rather than treating it as a high-speed counter.
-
Why may additional supply terminals be required with 6ES7131-4BF00-0AA0?Eight two-wire sensors need suitable supply distribution as well as input terminals. The chosen terminal module may need an add-on or potential-distribution arrangement.
-
What does an illuminated channel LED on 6ES7131-4BF00-0AA0 fail to prove?It does not prove that the intended PLC bit, interlock or field device has been assigned correctly. Trace the signal through the application.
-
Can channel diagnostics on 6ES7131-4BF00-0AA0 identify an open wire?This execution has no diagnostic functions. Use the application or external monitoring required to detect a missing field signal.
-
What should be checked before enabling isochronous acquisition with 6ES7131-4BF00-0AA0?Confirm compatible station interface and firmware, hardware configuration and the controller timing design. Module support alone does not configure the station.
-
How should a noisy input connected to 6ES7131-4BF00-0AA0 be investigated?Inspect supply reference, routing, shielding, terminal contact and signal levels. Compare the disturbance duration with input filtering before changing the control logic.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.