Preserve the installed HMI project
Archive the approved project, engineering-software version, CompactFlash content, PLC interface selection and node settings before removing the panel. -
Prove the restored operator station
After installation, verify 24 V DC supply, touch calibration, screen navigation, PLC data exchange, alarms and every used operator command.
Technical specifications for 6AV6545-0CC10-0AX0
-
Manufacturer:Siemens
-
Product Category:HMI Panels
-
Spare Part Number:6AV6545-0CC10-0AX0
-
Weight:3.72 kg
-
Tariff Code:8537101190
-
Product family:SIMATIC HMI TP 270
-
Display technology:STN color display
-
Screen diagonal:10.4 in
-
Color depth:256 colors
-
Display resolution:640 x 480 pixels
-
Operator input:Resistive touchscreen
-
Processor:32-bit RISC CPU
-
Operating system:Microsoft Windows CE
-
Configuration memory:2 MB
-
Rated supply:24 V DC
-
Supply range:20.4 to 28.8 V DC
-
Rated current:0.9 A
-
Typical power input:15 W
-
Engineering software:ProTool V6 SP3 or later; WinCC flexible Standard 2004 or later
-
Serial interfaces:2 x RS232; 1 x RS422; 1 x RS485
-
PLC interface selection:IF1A RS232 or IF1B RS422/485; not simultaneous
-
Removable storage:1 x CompactFlash card slot
-
USB interface:1 x USB; connected load max. 500 mA
-
Backlight MTBF:60,000 h at 25 deg C
-
Backup battery:Optional 3.6 V; minimum backup duration 3 years
-
Real-time clock:Hardware clock; battery-backed and synchronizable
-
Mounting panel thickness:2.5 to 6 mm
-
Permitted inclination:Up to +/-35 deg from vertical
Information
- Siemens 6AV6545-0CC10-0AX0 combines a 640 x 480 touch display, 2 MB configuration memory and serial PLC interfaces in the SIMATIC TP270 operator-panel architecture.
Interface allocation: IF1A and IF1B are alternative serial paths; use only the documented selection.
Service continuity: Preserve the panel project, communication settings and CF-card data before replacement.
The panel uses a 24 V DC supply and provides two RS232 paths together with RS422 and RS485 capability. IF1A and IF1B are alternative communication interfaces rather than simultaneous ports; the selected PLC, MPI or PROFIBUS connection must match the saved project and installed wiring.
Two megabytes of configuration memory and a CompactFlash slot support the installed project and service data. Before replacement, retain the ProTool or WinCC flexible project, communication settings, CF-card content and clock information, then prove screen navigation, alarms, PLC data exchange and touch response after restoration.
-
Siemens 6AV6545-0CC10-0AX0 technical reference
Verified product data, interface limits, lifecycle context and technical interpretation. -
Siemens 6AV6545-0CC10-0AX0 engineering field guide
Installation, project-restoration, communication, diagnostic and acceptance guidance.
Platform applications: The uses below depend on the installed project and documented machine design.
-
Machine visualization and alarm operation
Display process values, alarm messages and operator screens defined by the installed HMI project. -
Serial PLC operator station
Exchange project tags through the documented RS232, RS422, RS485, MPI or PROFIBUS path supported by the installed configuration. -
Recipe and service-data handling
Use the CompactFlash slot for supported project, backup or recipe workflows defined by the engineering environment. -
Installed-base TP270 maintenance
Restore an existing TP270 station only after matching the panel cutout, 24 V DC supply, interface allocation and saved project.
Save the installed ProTool or WinCC flexible project, communication settings and CF-card content before removal.
Measure the panel supply under load and keep it within the documented 20.4 to 28.8 V DC range.
Use either IF1A RS232 or IF1B RS422/485 as documented; do not operate both alternatives simultaneously.
Confirm the panel cutout, sealing surface, 2.5 to 6 mm panel thickness, ventilation clearance and permitted inclination.
Operate with a finger or approved touchscreen pen and keep sharp or hard tools away from the touch surface.
After restoration, prove startup, project loading, touch calibration, PLC communication, alarms and every used operator function.
Alternative Names
Technical notes
Power and startup: Apply 24 V DC within 20.4 to 28.8 V DC, observe the startup dialog and confirm the saved project opens without a configuration or communication fault.
Serial communication: Verify the documented IF1A or IF1B selection, cable pinout, PLC address and project communication driver before energizing the connected station.
Project restoration: Use the approved ProTool or WinCC flexible project and retain the CF-card data, recipes, alarm text and communication parameters required by the machine.
Touch and display proof: Check the full active touch area, screen navigation, alarm acknowledgement, color display, backlight condition and every used operator control.
FAQ View All FAQ
-
What should be backed up before removing Siemens 6AV6545-0CC10-0AX0?Retain the ProTool or WinCC flexible project, CF-card content, recipe data, alarm configuration, PLC interface selection, node settings and a photographic record of the installed wiring.
-
How should an IF1A or IF1B communication fault be isolated on Siemens 6AV6545-0CC10-0AX0?Confirm which interface the project assigns, verify its switch setting and cable pinout, then check the PLC address, baud rate and driver without using IF1A and IF1B simultaneously.
-
What checks apply when Siemens 6AV6545-0CC10-0AX0 has a blank screen?Measure the 24 V DC supply under load, observe startup indications, check backlight condition and determine whether the panel reaches the loader, transfer dialog or configured project.
-
How is touch operation accepted after replacing Siemens 6AV6545-0CC10-0AX0?Run the approved touch calibration, test the full active area, navigate every used screen and prove alarms and commands with the machine in an approved test state.
-
How is PLC communication proved after installing Siemens 6AV6545-0CC10-0AX0?Verify the project driver, node address, interface selection and field wiring, then compare live tags, alarm updates and command acknowledgements with the PLC state.
-
What is the effect of the optional backup battery in Siemens 6AV6545-0CC10-0AX0?The 3.6 V battery supports the hardware clock during loss of panel power; record the clock behavior and replace the battery only under the approved service procedure.
-
Which mounting checks are required for Siemens 6AV6545-0CC10-0AX0?Confirm the panel cutout and sealing surface, keep the mounting sheet within 2.5 to 6 mm, preserve ventilation clearance and keep the installed inclination within +/-35 degrees.
-
Which engineering-software checks apply to Siemens 6AV6545-0CC10-0AX0?Confirm the archived project version and required ProTool or WinCC flexible environment before transfer, then document the restored project, communication result and functional acceptance.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
6AV6545-0CC10-0AX0Product Details -
330103-00-04-05-02-CNProduct Details -
330104-00-05-50-02-00Product Details -
330103-00-04-50-11-00Product Details -
330103-00-06-05-02-CNProduct Details -
330104-02-19-10-01-00Product Details -
21504-00-40-10-02Product Details -
330192-00-25-50-00Product Details -
330232-05-10-12-05Product Details -
6ES7321-1BH10-0AA0Product Details
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.