Match the complete marking
Include FBM10/15 and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation. -
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered FBM10/15 reference with the installed equipment and applicable Invensys documentation.
Technical specifications for FBM10/15
-
Manufacturer:Invensys
-
Product Category:DCS Systems
-
Spare Part Number:FBM10/15
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Input channels per module:8
-
Output channels per module:8
-
Combined pair inputs:16
-
Combined pair outputs:16
-
Input ON-state:79 to 132 Vac
-
Input OFF-state:0 to 20 Vac
-
Input filter selections:4, 8, 16 or 32 ms
-
Output voltage:79 to 132 Vac; 120 Vac nominal, 50/60 Hz
-
Output current:2 A maximum per channel; 12 A maximum per module
-
Output inrush:24 A peak 10 ms; 12 A rms 20 ms; 3.5 A rms 1 s
-
Module-pair supply:26 to 42 Vdc redundant
-
Power, main only:7 W maximum
-
Power, main plus expansion:11 W maximum
-
Channel isolation:1,250 Vac for one minute channel-to-earth or channel-to-channel
-
Operating temperature:0 to 60 deg C
-
Operating humidity:5 to 95% noncondensing
-
Published module mass:1 kg each
Information
- The FBM10 connects directly to the redundant Fieldbus and can support one FBM15 expansion, which depends on the main module for Fieldbus access.
I/O capacity: Eight 120 Vac inputs and eight 120 Vac outputs per module; sixteen of each for the engineered pair
Output boundary: 2 A per channel and 12 A per module with defined short-duration inrush limits
Input filtering is selected per module, while output fail-safe, sustained/momentary behavior and pulse interval are configured per channel. Preserve these settings before changing either module.
An overloaded output opens for approximately 64.5 line cycles and retries; currents above 50 A can damage the module, so the connected load and external fusing must be verified.
-
Invensys FBM10/15 official technical excerpt
Foxboro pair architecture, Fieldbus dependency, I/O windows, output loading and supported operating modes. -
Invensys FBM10/15 engineering guide
Pair identification, circuit isolation, termination checks, configuration recovery and sixteen-channel I/O proof.
Platform applications: The uses below require the documented Foxboro I/A Series Fieldbus I/O station companion components and approved machine drawing.
-
120 Vac field-status monitoring
Use the documented ON/OFF windows to monitor eight mains-level contacts per module. -
120 Vac actuator switching
Switch relays or solenoids within the 2 A channel and 12 A module limits. -
Main-plus-expansion I/O
Connect one FBM15 to the supporting FBM10 for a coordinated 16-input/16-output station. -
Ladder Logic execution
Restore the approved Digital I/O or Ladder Logic program, filters, fail-safe and momentary-output settings.
Do not release an FBM15 without identifying its supporting FBM10 and expansion connection.
Use the site lockout procedure and prove each input/output circuit de-energized before handling.
Verify load inrush and external fusing; fault current above 50 A can damage the module.
Archive input filter, output fail-safe, sustained/momentary mode and pulse interval.
Confirm discrete-wire, plug-connector or direct-connection block against the enclosure design.
Test main Fieldbus communication and every input/output on both FBM10 and FBM15.
Alternative Names
Technical notes
Pair identity: Record both serial labels and the physical main-to-expansion connection.
Output test: Measure connected load current and inrush while verifying overload recovery.
Configuration test: Record input filters, fail-safe states, momentary modes and pulse intervals.
FAQ View All FAQ
-
Why must the FBM15 portion of FBM10/15 remain associated with its FBM10 main?FBM15 depends on the main module for Fieldbus access and program execution; record the physical expansion link and both identities before separating the pair.
-
Which configuration should be archived before an FBM10/15 exchange?Retain the Digital I/O or Ladder Logic revision, input filters, output fail-safe states, sustained/momentary modes and every pulse interval.
-
How should output inrush be evaluated on FBM10/15?Measure each connected load and the simultaneous module demand, compare it with the documented channel/module limits and verify external protection before energizing.
-
How does termination hardware affect compatibility of FBM10/15?The discrete-wire, plug-connector or direct-connection arrangement must match the enclosure and channel map; photograph the installed block before removal.
-
What should be checked if FBM10/15 loses Fieldbus communication after replacement?Start with the FBM10 main connection, pair interconnect, module supply and program assignment before diagnosing the FBM15 channels.
-
How should fail-safe and momentary outputs be proven on FBM10/15?Use the approved plant test to exercise each configured mode and record the commanded state, pulse duration and actual load response.
-
What does a complete commissioning test for FBM10/15 include?Verify main Fieldbus health, the expansion relationship and every input/output on both modules with the retained channel map.
-
Why should an overloaded FBM10/15 output not be accepted after an automatic retry?The retry does not prove that load current, inrush or external fusing is correct; measure the circuit and remove the cause before release.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.