Technical specifications for 8310
-
Manufacturer:Invensys
-
Product Category:DCS Systems
-
Spare Part Number:8310
-
Estimated shipping dimensions:6.1x41x17.7cm
-
Weight:2.8 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Product role:175 W high-density power module
-
Nominal input:120 VAC/VDC
-
Recommended range:120 VAC/VDC (-15% to +10%)
-
AC input range:85-140 VAC at 47-63 Hz
-
DC input range:95-180 VDC
-
Input power:240 W minimum per source
-
Fuse:5 A time-delay
-
Isolation:1,000 VAC or 1,500 VDC input-to-output
-
Power factor:0.70 typical
-
Chassis support:Main, expansion and RXM chassis
-
Redundancy:Two module positions per chassis
-
Status supervision:Power, alarm, temperature and battery indications
Information
Overview
Manuals
Common Applications
Product Precautions
Inside the chassis, TRICONEX 8310 isolates and conditions the incoming supply while monitoring power, temperature, alarm and battery status.
- Delivers 175 W in the high-density Tricon power-module format
- Accepts 85–140 VAC at 47–63 Hz or 95–180 VDC
- Provides 1,000 VAC or 1,500 VDC input-to-output isolation
- Supports paired module positions for redundant chassis power
Two 8310 modules can share normal chassis load while maintaining the documented redundant supply arrangement. The module also supervises power, alarm, temperature and battery conditions, so replacement checks should include the source fuse, input range, chassis position and front-panel status indications.
Important Notice: Confirm the complete 8310 identity, installed system record and approved companion hardware before replacement or commissioning.
TRICONEX 8310 Manuals & Downloads
TRICONEX 8310 Technical Reference (PDF)TRICONEX 8310 Installation & Commissioning Guide (PDF)
The first document presents exact-model technical evidence, while the second organizes a separate controlled installation and commissioning workflow.
Installed Tricon systems
Controlled service where the approved system records explicitly identify 8310.
Planned maintenance
Like-for-like inspection or replacement work that preserves the documented power module arrangement.
Lifecycle-managed spares
Exact-identity spare control for operating installations that retain the TRICONEX 8310 designation.
Commissioning verification
Functional checks that confirm the recorded interface, configuration and diagnostics after 8310 is installed.
Read the applicable TRICONEX instructions before work. Verify 8310 and the installed system configuration before isolation or replacement.
1
Record the complete TRICONEX 8310 marking and installed position before work.
2
Place the controller and affected process function in the approved safe maintenance state.
3
Verify the documented system version, companion hardware and interface assigned to 8310.
4
Isolate the applicable controller and field energy in accordance with the approved procedure.
5
Inspect connectors, keys, cable assemblies and mechanical retention before installation.
6
Install 8310 only in the recorded location without changing the approved architecture.
7
Restore power under control and confirm the specified indicators, communications and diagnostics.
8
Document the final identity, configuration and functional acceptance results before release.
Technical notes
For 8310, the verified dataset records nominal input as 120 VAC/VDC and recommended range as 120 VAC/VDC (-15% to +10%). These values must be applied only after the complete installed marking, cabinet record and approved system architecture have been reconciled.
FAQ View All FAQ
-
What function does TRICONEX 8310 perform?TRICONEX 8310 performs the documented role of a power module within the applicable installed-system architecture.
-
Which nominal input is specified for 8310?The manufacturer specifies the nominal input for 8310 as 120 VAC/VDC.
-
How does the manufacturer define the recommended range of 8310?The manufacturer specifies the recommended range for 8310 as 120 VAC/VDC (-15% to +10%).
-
What ac input range applies to the TRICONEX 8310?The manufacturer specifies the ac input range for 8310 as 85-140 VAC at 47-63 Hz.
-
Where does 8310 fit with respect to dc input range?The manufacturer specifies the dc input range for 8310 as 95-180 VDC.
-
Why must the input power be checked on 8310?The manufacturer specifies the input power for 8310 as 240 W minimum per source.
-
When replacing 8310, which fuse must match the record?The manufacturer specifies the fuse for 8310 as 5 A time-delay.
-
What does the manual state about the isolation for 8310?The manufacturer specifies the isolation for 8310 as 1,000 VAC or 1,500 VDC input-to-output.
Manufacturers
Supporting new and legacy automation
Whether you're maintaining existing equipment or sourcing parts for current systems, we provide fast, dependable supply you can rely on.
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
PRODUCTS IN SEARCH PAGE ()
50+ account managers available now
Related reading
Related cases and sourcing guidance
View all case studies
Manufacturers
You May Also Like
Explore related automation components available through Apter Power.
Manufacturers
Product Browsing History
Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.