STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000

SmartLine Gauge Pressure Transmitter
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (1)
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (2)
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (3)
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (1)
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (2)
Honeywell STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 (3)
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

Honeywell STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 is an STG740 SmartLine gauge pressure transmitter configuration. The STG740 sensor family measures process pressure through a piezoresistive element with temperature compensation.
  • Manufacturer part number
    STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000
  • Shipping
    Swift global dispatch
  • Condition
    New, original product
  • Shipping size (est.)
    31cm × 26cm × 21cm
  • Country of Origin
    USA
Get a quick price for STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000
E-mail *
Mobile
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 0

    Review your reference

    Send the complete STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 marking, quantity and current label photos. We will review the exact transmitter execution and installed process connection.

  • 1

    Confirm the offer

    Check the quoted reference, condition, included items and expected dispatch date before approving your order.

  • 2

    Arrange dispatch

    Confirm the delivery address and receive the tracking reference when the shipment is arranged.

  • Match the complete marking

    Include STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 and every visible option and revision marking on the item. Keep the exact reference on the enquiry and quotation.

  • Check the offered item before ordering

    Request current label, connection and housing photos. Compare the offered transmitter with the installed process connection and approved loop design.

Technical specifications for STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000

  • Manufacturer:
    Honeywell
  • Product Category:
    General Automation
  • Spare Part Number:
    STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000
  • Weight:
    4.82 kg
  • Tariff Code:
    8537101190
  • Sensor principle:
    Piezoresistive with temperature compensation
  • Upper range limit:
    500 psi / 35 bar
  • Lower range limit:
    -14.7 psi / -1 bar
  • Minimum span:
    5 psi / 0.35 bar
  • Maximum turndown:
    100:1
  • Standard reference accuracy:
    ±0.055% of span under stated conditions
  • Optional reference accuracy:
    ±0.040% of span; option dependent
  • Long-term stability:
    0.02% URL per year for 10 years, family rating

Information

Overview Downloads Applications / Compatibility Product Precautions
  • The STG740 range extends from a lower range limit of -14.7 psi to an upper range limit of 500 psi. Its minimum calibrated span is 5 psi, so the selected lower and upper range values must be reviewed against the process envelope and protective overpressure design.
Sensing: Temperature-compensated piezoresistive element
Range planning: STG740 limits and configured span
Integration: Protocol and mechanical options verified on unit
The STG740 range extends from a lower range limit of -14.7 psi to an upper range limit of 500 psi. Its minimum calibrated span is 5 psi, so the selected lower and upper range values must be reviewed against the process envelope and protective overpressure design.

SmartLine STG700 devices can be ordered with different communication, display, process-connection and approval selections. The long order code alone is not decoded here; the fitted protocol and wetted-material configuration must be read from the actual nameplate and Honeywell order record.

A replacement must preserve the original pressure range, calibrated units, damping, output behavior and mounting arrangement. After installation, verify the impulse line, zero reference and control-system reading under the approved loop procedure.
Controller platform reference: Honeywell SmartLine STG700 gauge-pressure family. Match the installed configuration and interfaces.
Technical downloads for Honeywell STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000: an Apter Power technical reference and an installation and commissioning guide.
These Apter Power documents support product identification and service planning. Apply the approved system and site procedures during installation.
Process applications: STG740 gauge-pressure measurement can provide feedback for pressure control, operator indication and configured alarm or trend monitoring in an engineered process loop.

System compatibility: Match STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 to the installed host input, communication execution, process connection and approved instrument configuration; the long option code must be checked against the offered unit.
Installation and commissioning checks for Honeywell STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000.
Confirm the process connection

Compare the fitted meter body and connection orientation with the piping design.

Record calibration

Preserve lower and upper range values, units and damping.

Check protocol

Read the actual transmitter label before assigning HART or DE wiring.

Inspect impulse line

Apply isolation, draining and pressure restoration procedures.

Verify loop power

Use the protocol-specific supply and load requirements.

Perform loop test

Compare local pressure indication and host input at controlled points.

Alternative Names

STG740 STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000

Technical notes

Range selection: Select calibration limits within the STG740 rated range and at or above the minimum span.

Output interface: Confirm the actual HART or DE execution before assigning power and communication.

Loop verification: Document the process connection and multi-point loop acceptance test.

FAQ View All FAQ

  • How should the calibrated range of STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 be preserved?
    Record the installed LRV, URV, engineering unit and damping before exchange; verify them against the approved loop sheet.
  • Can the HART supply range be assumed for STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000?
    Only after the delivered communication option is confirmed from the nameplate and order record.
  • What pressure connection details matter for STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000?
    Match meter-body orientation, process thread or flange, seal material and isolation arrangement to the installed instrument.
  • How is a zero shift on STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 investigated?
    Check static pressure, impulse-line condition, mounting effects and configured zero before adjusting calibration.
  • What should be checked if the host reading from STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 is unstable?
    Inspect loop power and load, cable shielding, damping and process pulsation.
  • When can another STG700 device replace STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000?
    Only after the pressure range, wetted materials, protocol, approvals and full option code are approved.
  • How should STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000 be accepted after installation?
    Complete a controlled pressure or loop simulation and record readings at multiple points.
  • What evidence identifies the exact execution of STG740-STG740-E1GC4A-1-C-AHB-11S-A-50A0-0000?
    Use the complete nameplate and original order record to decode every installed option and certification.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.