Match the complete marking
Include F3238 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered F3238 with the installed equipment and applicable HIMA documentation.
Technical specifications for F3238
-
Manufacturer:HIMA
-
Product Category:PLC Systems
-
Spare Part Number:F3238
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Platform:HIQuad
-
Input channels:8
-
Input sources:NAMUR proximity switches; contacts with resistor network
-
Line diagnostics:Short-circuit and open-circuit monitoring
-
Safety capability:SIL 3 in the applicable approved system
-
UB1 supply:24 V DC, −15%/+20%
-
UB2 supply:5 V DC, ±10%
-
Certified ambient range:0–60 °C
-
Intrinsic-safety Uo:9.9 V
-
Intrinsic-safety Io:15 mA
-
Intrinsic-safety Po:38 mW
Information
- HIMA F3238 evaluates field switching signals in intrinsically safe circuit arrangements. The module and the connected field devices must be selected as a complete approved loop.
Signal sources: NAMUR proximity switches or resistor-network contacts
Circuit function: Intrinsically safe input evaluation with SC/OC diagnostics
The IECEx circuit specification gives a 24 V DC supply circuit UB1 with −15%/+20% tolerance and a separate 5 V DC UB2 supply with ±10% tolerance. The certified ambient range is 0–60 °C. These supply values belong to the module circuits and must not be confused with the intrinsically safe field-loop output limits.
The intrinsically safe control circuits have Uo 9.9 V, Io 15 mA and Po 38 mW. Permitted external capacitance and inductance depend on the gas or dust group and whether both are considered together; the higher separate maxima cannot simply be combined. Certified switches or contacts may be located in hazardous areas from Zone 0 when the complete installation meets the applicable approval conditions.
-
HIMA F3238 technical reference
Prepared by Apter Power - PDF, 5 pages, 95.2 KB. F3238 is an eight-channel initiator input module. Intrinsic-safety values apply to the certified circuit arrangement and its external capacitance/inductance conditions; module identification alone does not establish a complete safety-loop approval. -
HIMA F3238 installation planning guide
Prepared by Apter Power - PDF, 5 pages, 96.5 KB. Identity, configuration, connection and controlled acceptance planning.
Platform applications: The following applications describe HIMA HIQuad functions. Match the complete F3238 identity to the installed system before selecting a replacement.
-
NAMUR switching signals
Evaluate suitable proximity-switch states through the approved initiator-input circuit. -
Resistor-network contacts
Use contacts with the required network so that signal states and line faults can be distinguished. -
Hazardous-area field loops
Connect certified field devices using entity parameters and wiring conditions appropriate to the location. -
Safety-system maintenance
Retain the module revision, channel assignments and validated safety application during replacement.
Match module revision and the complete system approval before installation.
Use the correct NAMUR sensor or contact resistor network for the intended loop.
Check Uo, Io, Po and the applicable external capacitance and inductance limits together.
Distinguish the 24 V and 5 V supply circuits from the intrinsically safe field connections.
Maintain the certified 0–60 °C module ambient range and approved enclosure conditions.
Perform the authorized channel and fault-response validation before returning the safety function to service.
Alternative Names
Technical notes
Installation relationship: The IECEx circuit specification gives a 24 V DC supply circuit UB1 with −15%/+20% tolerance and a separate 5 V DC UB2 supply with ±10% tolerance. The certified ambient range is 0–60 °C. These supply values belong to the module circuits and must not be confused with the intrinsically safe field-loop output limits.
Configuration: F3238 is an eight-channel initiator input module. Intrinsic-safety values apply to the certified circuit arrangement and its external capacitance/inductance conditions; module identification alone does not establish a complete safety-loop approval.
Technical reference: HIMA HIQuad technical product overview; IECEx TUR 18.0006 Issue 2, attachment Revision 02.
FAQ View All FAQ
-
Which field devices can connect to F3238?The module evaluates NAMUR proximity switches and contacts with a resistor network in the approved intrinsically safe circuit arrangement.
-
How many input channels does F3238 have?F3238 has eight initiator input channels.
-
What line diagnostics are identified for F3238?The module design provides short-circuit and open-circuit monitoring; use the appropriate field-device and resistor-network arrangement.
-
What supply circuits are specified for F3238?UB1 is 24 V DC with −15%/+20% tolerance, and UB2 is 5 V DC with ±10% tolerance.
-
What certified ambient range applies to F3238?The IECEx attachment specifies an ambient range of 0–60 °C for the module.
-
What intrinsic-safety output limits apply to F3238?The certified control-circuit limits are Uo 9.9 V, Io 15 mA and Po 38 mW; the full entity and wiring conditions must also be satisfied.
-
Can separate capacitance and inductance maxima be combined for F3238?No. The certificate specifies separate and mixed-consideration limits. Select the correct group and combined condition for the complete loop.
-
Does F3238 by itself establish a SIL 3 safety function?No. Module capability is part of an approved system. The configured logic, revision, field devices and application validation determine the complete safety function.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.