ANALOG INPUT MODULE
UNIVERSAL CONFIGURABLE FOR THERMOCOUPLE
RESISTIVE CURRENT OR VOLTAGE
2CJC CHANNELS COLD JUNTION COMPENSATION

Ask our team:

Get a quick price for: IC695ALG600
Quantity*
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy.

Technical specifications for IC695ALG600

Technical specifications for IC695ALG600

  • Manufacturer:
    General Electric
  • Product Category:
    Gas turbine control
  • Spare Part Number:
    IC695ALG600
  • Estimated shipping dimensions:
    3.4x13.2x13.7cm
  • Weight:
    0.2 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Module resolution:
    11-16 Bits
  • Power Dissapation:
    5.4W max
  • No of Channels:
    Eight (8)
  • Input signals, Current:
    0-20 mA; 4-20 mA; +/-20 mA
  • Cold Junction Compensation:
    2 channels
  • RTD Inputs:
    PT 385 / 3916, N 618 / 672, NiFe 518, CU 426

Information

Information

Overview Manuals Common Applications Product Precautions
GE IC695ALG600 is a PACSystems RX3i universal analog input module for voltage, current, resistance, RTD and thermocouple measurement.
  • Eight configurable universal analog input channels
  • Accepts current ranges including 0-20 mA, 4-20 mA and ±20 mA
  • Supports multiple RTD families for resistance-temperature measurement
  • Provides two cold-junction-compensation channels for thermocouple applications

Use IC695ALG600 in an RX3i rack with each channel configured for the installed sensor type, range and wiring method.

Important Notice: Confirm the exact module revision, terminal assembly, channel configuration, sensor wiring, grounding and compensation settings before energization.

IC695ALG600 Manuals and Guides
Apter Power IC695ALG600 Product Technical Reference PDFEmerson PACSystems RX3i I/O Data Sheet PDF
The first document is an Apter Power model-specific technical reference; the second is the official Emerson RX3i I/O data sheet for broader platform context.
IC695ALG600 mixed-sensor process measurementCombines voltage, current and resistance-based field measurements in an RX3i rack.
IC695ALG600 RTD temperature acquisitionConnects supported RTD sensor families with the channel wiring and compensation defined in the project.
IC695ALG600 thermocouple monitoringUses the installed terminal arrangement and cold-junction compensation for temperature channels.
IC695ALG600 current-loop instrumentationReceives 0-20 mA, 4-20 mA or bipolar current signals from compatible transmitters.
Read the applicable Emerson RX3i installation instructions before work. Verify IC695ALG600 and the installed terminal and sensor configuration.
1Confirm the complete IC695ALG600 catalog marking and hardware revision before replacement.
2Isolate rack power and all field signal energy before removing the terminal assembly or module.
3Record channel assignments, input types, ranges, scaling and alarm behavior before service.
4Preserve shield, grounding, polarity and sensor-lead routing for every connected channel.
5Match cold-junction compensation hardware to the installed thermocouple terminal arrangement.
6For three-wire RTD channels, verify the approved lead-resistance-compensation configuration.
7Lock the terminal assembly in place and review module and terminal diagnostics after power-up.
8Validate representative channel values under controlled conditions before returning the process to service.

Revisions

Revisions

Revision Part #

Also known as

IC695ALG600-CA-DD
IC695ALG600--CA-DD, Series -CA-DD, Rev -CA-DD
IC695ALG600AA
IC695ALG600-AA, Series AA, Rev AA
IC695ALG600AB
IC695ALG600-AB, Series AB, Rev AB
IC695ALG600BC
IC695ALG600-BC, Series BC, Rev BC
IC695ALG600CC
IC695ALG600-CC, Series CC, Rev CC
IC695ALG600DD
IC695ALG600-DD, Series DD, Rev DD
IC695ALG600EE
IC695ALG600-EE, Series EE, Rev EE
IC695ALG600FE
IC695ALG600-FE, Series FE, Rev FE
IC695ALG600GF
IC695ALG600-GF, Series GF, Rev GF

Technical notes

Technical notes

Supports software-independent configuration for current, voltage, thermocouple, RTD, and resistance signals, and features 2 built-in Cold Junction Compensation channels.

FAQS

  • What signal types can IC695ALG600 measure?
    IC695ALG600 supports configurable current, voltage, resistance, RTD and thermocouple inputs for industrial measurement applications.
  • How are the input channels arranged on IC695ALG600?
    IC695ALG600 provides eight universal analog input channels arranged as two groups of four channels.
  • Which PACSystems platform is compatible with IC695ALG600?
    IC695ALG600 is designed for a PACSystems RX3i universal backplane with a compatible RX3i controller and the approved terminal assembly.
  • Which current ranges can be configured on IC695ALG600?
    IC695ALG600 supports 0-20 mA, 4-20 mA and +/-20 mA current-input configurations.
  • What should be checked when IC695ALG600 is used with thermocouples?
    For IC695ALG600 thermocouple service, confirm the configured thermocouple type, field polarity, approved terminal arrangement and the two cold-junction-compensation channels before start-up.
  • What RTD checks are important for IC695ALG600?
    For IC695ALG600 RTD service, confirm that the configured sensor family matches the installed PT, nickel, nickel-iron or copper RTD and verify the field wiring method before energization.
  • What should be documented before replacing IC695ALG600?
    Before replacing IC695ALG600, record each channel type, range, scaling, alarm behavior, wiring identification and compensation setting.
  • How should IC695ALG600 be verified during commissioning?
    Commission IC695ALG600 with controlled representative inputs, then confirm stable channel values, correct scaling and clear module or terminal diagnostics before release.
Trusted by 5,000+ plants worldwide | Backed by our vast inventory of top-tier control parts, modules and cards, fast shipments are dispatched to cover your urgent needs. ABOUT US >>
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer`s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

We’re Here When You Need Us

From product insights to customer service needs, our experienced service team will focus on getting you what you need quickly

Enquire

Complete our online form.

Call Us

Speak to one of our team.

Live Chat

Send us a message.