Technical specifications for IC670ALG240
-
Manufacturer:General Electric
-
Product Category:PLC Systems
-
Spare Part Number:IC670ALG240
-
Estimated shipping dimensions:5.3x8.5x8.1cm
-
Weight:0.25 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Input channels:16
-
Input-current span:0 to 25 mA
-
Input shunt:250 ohm
-
A/D resolution:16 bits
-
Digital counts:0 to 65535 for 0 to 25 mA
-
Resolution per LSB:0.38 microA
-
All-channel conversion:Approximately 1 ms
-
Analog input data:16 words
-
Status data:88 bits optional
-
Fault-clear data:16 bits optional
-
Filter selections:10 ms or 20 ms
-
Line-frequency selections:50 Hz or 60 Hz
-
Required BIU revision:2.0 or later
Information
- Scans sixteen current-loop channels
- Uses a 16-bit converter with 0.38 microA steps
- Completes an all-channel conversion in about 1 ms
- Supports channel alarms and latched fault clearing
IC670ALG240 operates with Two-wire or three-wire transmitters, Common analog return, Field Control BIU revision 2.0 or later, Configured I and Q diagnostic data.
Engineered applications include sixteen-channel process-current acquisition field station, Remote I/O cabinet integration, Installed-base module renewal, Controlled commissioning and diagnostics.
Important Notice: Confirm the shared analog return, transmitter power arrangement, 50/60 Hz selection, software filter and status-bit allocation before loop tests.
Apter Power IC670ALG240 Manuals and Guides
Apter Power IC670ALG240 Technical Data and System Reference PDFIC670ALG240 Field Installation and Commissioning Workbook PDFThe first document presents model-specific technical data and system identity. The second provides a separate installation, wiring and commissioning workflow.
sixteen-channel process-current acquisition field station
Performs the documented sixteen-channel process-current acquisition function at a distributed Field Control station.
Remote I/O cabinet integration
Exchanges configured process data with the host through the installed bus interface.
Installed-base module renewal
Restores an exact catalog-number position while preserving terminal and data identity.
Controlled commissioning and diagnostics
Supports staged wiring, configuration, diagnostic and functional verification.
Verify the complete IC670ALG240 catalog marking and assigned Field Control position before work.
Place the connected sixteen-channel process-current acquisition process in its approved maintenance state before disturbing the station.
Isolate BIU and field power, then confirm a safe condition at the IC670ALG240 terminal block.
Label and record channel conductors, returns, shields and external supply wiring before disconnecting any conductor from IC670ALG240.
Use ESD controls and protect the module connector, terminal block keying and exposed electronics.
Restore only the documented channel range, scaling, alarms and default behavior; do not copy settings from an adjacent module.
Energize in a controlled sequence and review PWR, channel, module and network diagnostics.
Complete low, midpoint and high signal checks plus alarm and diagnostic verification and retain the final result before returning the process to service.
Technical notes
FAQ View All FAQ
-
What Field Control function is assigned to IC670ALG240?IC670ALG240 is ge fanuc sixteen-channel grouped analog current input module. It scans sixteen common-return current inputs and reports scaled values, channel alarms and open-wire status to the Field Control host.
-
Which station hardware must be paired with IC670ALG240?Use IC670ALG240 with the documented Field Control terminal block, compatible BIU or MFP, and the installed two-wire or three-wire transmitters.
-
Which IC670ALG240 identity should be checked before installation?Confirm the full IC670ALG240 catalog marking and the catalog number value IC670ALG240 against the installed station record.
-
How should field wiring be transferred when replacing IC670ALG240?Label and record channel conductors, returns, shields and external supply wiring before disconnecting any conductor from IC670ALG240.
-
Which configuration item is critical when commissioning IC670ALG240?Restore only the documented channel range, scaling, alarms and default behavior; do not copy settings from an adjacent module.
-
What diagnostic checks apply to IC670ALG240?Energize in a controlled sequence and review PWR, channel, module and network diagnostics.
-
How should the IC670ALG240 signal path be functionally tested?Complete low, midpoint and high signal checks plus alarm and diagnostic verification and retain the final result before returning the process to service.
-
Can IC670ALG240 be replaced by a visually similar Field Control module?No direct substitution should be assumed. Match IC670ALG240, its terminal assignment, data allocation, signal type, power arrangement, and the documented required biu revision value 2.0 or later before migration.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-