330877-080-37-00 is installed with one-metre 3300 XL 50 mm probe, nine-metre 3300 XL 50 mm Proximitor Sensor, gold-plated coaxial connectors, compatible long-range displacement monitor.
Engineered applications include Steam-turbine differential expansion, Large-shaft axial movement, Valve-position measurement, Generator rotor-to-stator clearance monitoring.
Important Notice: Match 330877-080-37-00 only with the nine-metre 50 mm Proximitor Sensor and one-metre probe, support the armored PFA cable above its bend radius, and verify connector cleanliness before long-range displacement calibration.
The first document presents model-specific technical identity and engineering data. The second provides a separate installation, connection and commissioning workflow.
330877-080-37-00 supports this documented 3300 XL 50 mm Proximity Transducer System engineering task.
330877-080-37-00 supports this documented 3300 XL 50 mm Proximity Transducer System engineering task.
330877-080-37-00 supports this documented 3300 XL 50 mm Proximity Transducer System engineering task.
330877-080-37-00 supports this documented 3300 XL 50 mm Proximity Transducer System engineering task.
Verify the complete 330877-080-37-00 marking and its documented 3300 XL 50 mm Proximity Transducer System position before field work.
Place the monitored machine and associated protection channel in the approved maintenance state before disconnecting 3300 XL 50 mm armored FluidLoc extension cable.
Protect every exposed connector and cable end from oil, moisture, dirt and impact while 330877-080-37-00 is open.
Record probe, extension-cable and Proximitor Sensor identities so the calibrated system length is preserved.
Route 330877-080-37-00 without sharp bends, crushing, abrasion or tensile loading at either coaxial termination.
Clean and finger-tighten each ClickLoc connection; never transfer connector torque or wiring practice from a different transducer family.
Set the static gap only after mechanical mounting and the complete matched loop have been confirmed.
Verify polarity, dynamic response and alarm action before returning the machinery-protection channel to service.