Match the complete marking
Include the complete Bently Nevada 330704-000-050-10-02-05 marking and any hardware revision on the item. Compare the complete order code, mating interfaces and installed measurement chain.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 330704-000-050-10-02-05 with the installed equipment and applicable Bently Nevada documents.
Technical specifications for 330704-000-050-10-02-05
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330704-000-050-10-02-05
-
Weight:0.15 kg
-
Tariff Code:8537101190
-
Tip diameter:11 mm
-
Mounting thread:M14 x 1.5
-
Unthreaded section:0 mm
-
Case length:50 mm
-
Probe length:1.0 m
-
Lead protection:Armor
-
Connector:Miniature coaxial ClickLoc, standard cable
-
System linear range:4 mm
-
System scale factor:3.94 V/mm
-
Recommended gap:2.5 mm
Information
- Bently Nevada 330704-000-050-10-02-05 places an 11 mm sensing tip at a metric mounting point while using an armored lead for the machine-side cable route.
Lead configuration: 1.0 m; armored standard cable
Matched-system scale: 3.94 V/mm
The 50 mm metric case has no unthreaded section, and the 330704 construction protects the lead with armor. The miniature ClickLoc connector couples to the corresponding extension cable without changing the selected 1.0 m probe length.
The nominal 3.94 V/mm scale is a system calibration. Target material, probe mounting and total electrical length must remain consistent when replacing the probe; a mechanically fitting XL 8 mm or NSv component is not an equivalent electrical substitution.
330704-000-050-10-02-05 Official Technical Excerpt
The original technical excerpt applicable to Bently Nevada 330704-000-050-10-02-05 covers system performance, probe connections and applicable order selections. PDF · 6 pages.330704-000-050-10-02-05 Installation & Verification Guide
Apter Power installation and verification guide covering mounting, cable matching, target clearance, gap and signal checks. PDF · 5 pages.
Application scope: Apply the M14 x 1.5 installation to its intended target and keep the selected 1.0 m probe length in the electrical-length calculation.
Axial position
Use the matched 4 mm-range system where the required target travel fits its calibrated range.Radial vibration
Measure shaft movement through a correctly gapped XL 11 mm chain.Protected lead routing
Armor supports the machine-side installation where cable protection is required.Metric probe replacement
Retain the 50 mm case and M14 x 1.5 interface at the existing mount.
Match the M14 x 1.5 installation and selected case geometry.
Retain the armored standard cable construction and avoid connector strain.
Match the probe and extension cable to the Proximitor calibration.
Assess target material and clearance before applying nominal sensitivity.
Establish the gap using the complete energized measurement chain.
Check static response, dynamic indication and configured alarms.
Alternative Names
Technical notes
Signal and interface: The 4 mm linear range and 3.94 V/mm scale factor belong to the complete matched system; the probe alone does not establish these ratings.
Installation boundary: The reference gap is 2.5 mm. Confirm target material, available travel and correct total electrical length before using the nominal calibration.
Technical basis: Bently Nevada 3300 XL 11 mm Proximity Transducer System, 146256 Rev. T. Ordering selections apply to this complete probe code. Range, scale factor and gap are matched-system values under the specified calibration conditions.
FAQ View All FAQ
-
What mounting geometry does 330704-000-050-10-02-05 use?It has an M14 x 1.5 threaded case, 50 mm overall case length and no unthreaded section.
-
Is the lead of 330704-000-050-10-02-05 armored?Yes. The 330704 construction includes armor around the standard probe cable.
-
Can 330704-000-050-10-02-05 use an 8 mm Proximitor calibration?Use the matched XL 11 mm system. Its nominal 3.94 V/mm scale differs from the 7.87 V/mm scale of an XL 8 mm system.
-
Which cable completes a 5 m system with 330704-000-050-10-02-05?The 1.0 m probe requires a compatible 4.0 m XL 11 mm extension cable for a 5.0 m calibrated chain.
-
What is the matched-system linear range for 330704-000-050-10-02-05?The XL 11 mm system provides a 4 mm linear range under the stated calibration conditions.
-
Does 330704-000-050-10-02-05 have a FluidLoc lead?No. Connector option 02 selects the miniature ClickLoc connection with standard cable.
-
Why must the target be checked before setting 330704-000-050-10-02-05?Target material and geometry influence the calibration, so a nominal gap does not by itself establish the correct measurement scale.
-
What distinguishes the output check for 330704-000-050-10-02-05 from an XL 8 mm probe?Use the 3.94 V/mm nominal XL 11 mm scale and its applicable range, rather than testing against the XL 8 mm sensitivity.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.