Match the complete marking
Include 330195-02-12-50-00 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connection photos. Have your maintenance team compare the offered 330195-02-12-50-00 with the installed equipment and applicable Bently Nevada documentation.
Technical specifications for 330195-02-12-50-00
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330195-02-12-50-00
-
Weight:0.05 kg
-
Tariff Code:8537101190
-
Probe family:3300 XL 8 mm extended-temperature range
-
Mounting arrangement:Reverse mount
-
Mounting thread:3/8-24 UNF-2A
-
Reverse-mount geometry:02-12 fixed case option
-
Integral lead length:5.0 m
-
Approval option:00; agency approval not required
-
Probe-tip temperature:-52 to +218 deg C, ETR design
-
Cable and connector temperature:-51 to +260 deg C, ETR design
-
Matched Proximitor length:5 m
-
Matched-system linear range:2.0 mm (80 mils), reference setup
Information
- Bently Nevada 330195-02-12-50-00 is a 3/8-24 UNF reverse-mount 3300 XL 8 mm ETR proximity probe with a 5.0 m integral lead and the 00 no-approval ordering option.
Chain dependency: Keep the integral lead matched to the Proximitor electrical length.
Acceptance record: Set gap on the installed target before re-enabling the channel.
The probe is the sensing end of a calibrated 3300 XL 8 mm chain. Its 5 m lead is intended for a 5 m Proximitor. The published linear range and scale factor describe the complete matched transducer under reference calibration conditions.
The extended-temperature tip and cable/connector have different environmental limits. Preserve cable clearance at the back of the mounting location and set the gap on the installed target before restoring the monitor channel.
-
Bently Nevada 330195-02-12-50-00 technical reference
Original manufacturer Bently Nevada 3300 XL 8 mm Proximity Transducer System, 141194 Rev. AN. Family specifications and ordering information. -
Bently Nevada 330195-02-12-50-00 engineering guide
Apter Power installation, interface and fault-isolation guide for the offered complete model.
Platform applications: The applications below describe the complete measuring-channel functions. Verify the target, mounting position and approved channel design before selecting a replacement.
-
Reverse-side access
Fit the probe where the machine design requires insertion from the rear or a dedicated support bracket. -
Radial vibration
Measure shaft motion at the bearing plane after checking radial clearance and target material. -
Axial position
Use a matched 8 mm channel where the thrust target and travel remain within the accepted measuring span. -
Temperature-separated routing
Assess tip and cable temperatures independently and route the 5 m lead away from mechanical damage.
Confirm the 3/8-24 bore, back-side access and fixed 02-12 geometry.
Pair the 5 m lead with the corresponding 5 m Proximitor; do not add extension length.
Protect the rear cable exit against tight bends and contact with moving hardware.
Recheck response if target alloy or surrounding metal differs from the calibration setup.
Keep the coaxial joint clean and strain relieved.
Record gap, supply and operating trend before releasing the channel.
Alternative Names
Technical notes
Installation relationship: Confirm the 3/8-24 bore, back-side access and fixed 02-12 geometry.
Measurement boundary: Recheck response if target alloy or surrounding metal differs from the calibration setup.
Technical reference: Bently Nevada 3300 XL 8 mm Proximity Transducer System, 141194 Rev. AN.
FAQ View All FAQ
-
Why is the 5 m Proximitor pairing important for 330195-02-12-50-00?A different sensor length changes the electrical calibration. Verify the 5 m sensor marking and do not add an extension cable to this 5 m lead.
-
How can reverse-mount access affect replacement of 330195-02-12-50-00?The probe must pass through the documented rear clearance and support arrangement without cable strain. Compare case geometry and bracket position before setting gap.
-
What may shift the gap response of 330195-02-12-50-00 after a target change?Eddy-current coupling changes with target alloy and geometry. Recheck the matched channel against the actual machine target.
-
How should the ETR temperature limit of 330195-02-12-50-00 be applied?Check the tip and cable/connector locations separately; the published limits differ for those parts and do not describe the Proximitor environment.
-
How can an intermittent signal from 330195-02-12-50-00 be isolated?With the channel safely isolated, inspect the coaxial joint and rear cable exit, then compare probe-only resistance with the applicable reference.
-
What can reduce dynamic response while 330195-02-12-50-00 still shows a DC gap?Field-wire length, barriers, monitor loading or poor termination can attenuate higher frequencies. Inspect the complete chain and response curve.
-
When should the mechanical gap of 330195-02-12-50-00 be checked again?Repeat the gap check after moving the reverse-mount bracket, changing the probe or disturbing the target clearance.
-
What belongs in the as-left record for 330195-02-12-50-00?Retain complete probe and sensor markings, target material, resistance, gap voltage and measured running signal.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.