Technical specifications for 1784-PCMK
-
Manufacturer:Allen-Bradley
-
Product Category:PLC Systems
-
Spare Part Number:1784-PCMK
-
Estimated shipping dimensions:5.6x2.5x8.9cm
-
Weight:0.06 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Catalog number:1784-PCMK
-
Card format:PCMCIA Type II
-
Card power:160 mA at 5 V DC
-
Power dissipation:0.8 W
-
Thermal dissipation:2.73 BTU/h
-
Operating temperature:0 to 55 degC
-
Storage temperature:-20 to 65 degC
-
Vibration:15 g at 10 to 200 Hz
-
Operating shock:30 g
-
Non-operating shock:50 g
-
Maximum communication-cable length:Less than 10 m
-
PCM2/4/5/6 total cable length:3.16 m
-
Card-to-pod cable length:17.8 cm
-
Pod-to-processor cable length:2.8 m
-
Wiring category:3 on communication ports
-
Enclosure:Open style
Information
- Uses a PCMCIA Type II host interface
- Supports cable assemblies for DH+, DH-485 and Remote I/O service
- Draws 160 mA from the 5 V card supply
- Requires communication cabling shorter than 10 m
1784-PCMK is installed with Computer with supported PCMCIA services, 1784-PCM2/4/5/6 cable assembly, Compatible PLC-5, SLC or ControlLogix interface, Approved communication software and driver.
Engineered applications include PLC programming connection, DH+ network diagnostics, Remote I/O service access, Legacy controller commissioning.
Important Notice: Stop active communications before ejecting 1784-PCMK, use ESD controls, set cable termination as documented and confirm the selected data rate before going online.
Apter Power 1784-PCMK Manuals and Guides
Apter Power 1784-PCMK Product Technical Reference PDF1784-PCMK Engineering Installation and Verification WorkbookThe first document presents model-specific technical identity and engineering data. The second provides a separate installation, connection and commissioning workflow.
PLC programming connection
1784-PCMK supports this documented Allen-Bradley PCMCIA industrial communications engineering task.
DH+ network diagnostics
1784-PCMK supports this documented Allen-Bradley PCMCIA industrial communications engineering task.
Remote I/O service access
1784-PCMK supports this documented Allen-Bradley PCMCIA industrial communications engineering task.
Legacy controller commissioning
1784-PCMK supports this documented Allen-Bradley PCMCIA industrial communications engineering task.
Verify the complete 1784-PCMK marking and the assigned Allen-Bradley PCMCIA industrial communications position before work.
Place the connected machine or process in the approved maintenance state before disturbing 1784-PCMK.
Isolate the applicable power and field energy, then confirm a safe state before disconnecting 1784-PCMK.
Record connector, conductor, slot and configuration identities before removal of 1784-PCMK.
Use ESD controls and protect keyed interfaces, exposed contacts and electronic assemblies during handling.
Confirm that the installed companion hardware and approved project match the 1784-PCMK arrangement.
Restore power in a controlled sequence and review device, rack and host diagnostics.
Prove the intended function and retain the final test result before returning 1784-PCMK to service.
Technical notes
FAQ View All FAQ
-
What is 1784-PCMK?Allen-Bradley 1784-PCMK is allen-bradley pcmk communication card. It connects a compatible computer to Allen-Bradley industrial networks through the selected 1784-PCM cable assembly.
-
Which system uses 1784-PCMK?Use 1784-PCMK only in the documented Allen-Bradley PCMCIA industrial communications arrangement and the installed hardware configuration.
-
What should be checked before installing 1784-PCMK?Confirm the complete marking, assigned position, companion hardware and approved configuration before field work.
-
How should wiring be handled when replacing 1784-PCMK?Record every connector and conductor before removal, preserve polarity and shielding, and follow the applicable manufacturer connection instructions.
-
How is 1784-PCMK configured after replacement?Restore only the approved project or device settings, then verify status and diagnostics before automatic operation.
-
How should 1784-PCMK be commissioned?Energize under controlled conditions, exercise the intended system function and record the final diagnostic state.
-
What maintenance record is needed for 1784-PCMK?Retain the as-found connection record, installed position, configuration revision and functional-test result.
-
Can 1784-PCMK be substituted directly?A substitution requires complete catalog-number, hardware-revision, interface and system-compatibility checks against the controlling documentation.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studies-
28 ABB BRC410 Units: Ready to Inspect, Collected on Order DayRead case > -
24 Siemens Spare Parts Delivered to an Australian Waste Management FacilityRead case > -
Bently Nevada Cables and Proximitors Delivered to DubaiRead case > -
Siemens TP1500 Comfort: Check the Panel and Machine ProjectRead case >
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.