Match the complete marking
Include DSTA170 57120001-FC and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered DSTA170 57120001-FC with the installed equipment and applicable ABB documentation.
Technical specifications for DSTA170 57120001-FC
-
Manufacturer:ABB
-
Product Category:DCS Systems
-
Spare Part Number:57120001-FC
-
Weight:0.1 kg
-
Tariff Code:8537101190
-
Connection function:Analog-output field wiring
-
Paired output board:DSAO120
-
Output channels:8
-
Voltage connections:8
-
Current connections:8
-
Signal selection:By connection to voltage or current terminals
-
Current-path configuration:Diode with solder-jumper bypass
-
Normal current configuration:Bypass jumper fitted
-
Parallel-current configuration:Relevant bypass jumper open
-
Isolation boundary:DSAO120 arrangement is non-isolated
Information
- ABB DSTA170 57120001-FC terminates the analog-output wiring between the DSAO120 board and the controlled field equipment. The signal connections determine whether each channel uses voltage or current output.
Channel arrangement: Eight DSAO120 channels
Signal selection: Separate voltage and current connections
The unit provides eight voltage-output connections and eight current-output connections, allowing the required signal function to be chosen through the field connection for each channel. The DSAO120 arrangement is not galvanically isolated. The load and return wiring therefore need to follow the circuit design for that board rather than the isolated DSAO120A arrangement.
Each current output has a diode with a solder-jumper bypass. Normal operation uses the bypass in place; the documented parallel-current-output arrangement requires the relevant bypass to be opened. This configuration applies when two current outputs feed the same control object and must be assessed as a complete circuit before any jumper change.
-
ABB DSTA170 57120001-FC technical reference
Original ABB excerpt - PDF, 1 pages, 506.1 KB. DSTA170 57120001-FC is the connection unit for the DSAO120 analog-output arrangement. Output range and conversion resolution belong to the paired output board; cables and the board are separate items. -
ABB DSTA170 57120001-FC installation planning guide
Prepared by Apter Power - PDF, 5 pages, 96.4 KB. Identity, configuration, connection and controlled acceptance planning.
Platform applications: The following applications describe Advant S100 I/O functions. Match the complete DSTA170 57120001-FC identity to the installed system before selecting a replacement.
-
Analog field termination
Connect eight DSAO120 output channels to the field equipment through the appropriate screw-terminal circuits. -
Voltage-output wiring
Select the voltage connection and matching return for channels configured to drive a voltage-controlled load. -
Current-output wiring
Use the current connection and return for the intended loop, respecting the non-isolated board arrangement. -
Parallel-current circuit service
Maintain the documented diode-bypass arrangement when two output channels serve the same control object.
Match DSTA170 to the installed DSAO120 arrangement; do not substitute DSTA171 or assume DSAO120A behavior.
Record voltage/current selection and return wiring before disconnecting the field conductors.
Treat the DSAO120 circuits as non-isolated and assess grounding and common-potential connections.
Record the current-path bypass state. Change it only under the applicable ABB circuit procedure.
Secure controlled equipment and isolate applicable supplies before wiring or connection-unit replacement.
Perform a controlled channel check against the intended voltage or current signal and confirm the field response.
Alternative Names
Technical notes
Installation relationship: The unit provides eight voltage-output connections and eight current-output connections, allowing the required signal function to be chosen through the field connection for each channel. The DSAO120 arrangement is not galvanically isolated. The load and return wiring therefore need to follow the circuit design for that board rather than the isolated DSAO120A arrangement.
Configuration: DSTA170 57120001-FC is the connection unit for the DSAO120 analog-output arrangement. Output range and conversion resolution belong to the paired output board; cables and the board are separate items.
Technical reference: ABB S100 I/O Hardware Reference Manual, 3BSE002413R501, March 2004; Advant Controller 450 Product Guide, 3BSE015953R201 Rev. B.
FAQ View All FAQ
-
Which output board is paired with DSTA170 57120001-FC?DSTA170 provides the field connection interface for DSAO120. The output board, cable and connection unit have separate identities and should be matched as an installed set.
-
How many analog channels does DSTA170 57120001-FC connect?It connects eight channels. Each channel has voltage and current connection choices; these do not represent sixteen independent converted outputs.
-
How is voltage or current selected on DSTA170 57120001-FC?The selected field-wiring connection determines the signal function for each DSAO120 channel. Use the appropriate voltage or current connection and its return circuit.
-
Does DSTA170 57120001-FC provide isolated analog outputs?The paired DSAO120 output arrangement has no galvanic isolation. The isolation characteristics of DSAO120A must not be applied to this arrangement.
-
What is the purpose of the current-output diode on DSTA170 57120001-FC?Each current-output path includes a diode that can be bypassed with a solder jumper. The bypass configuration changes between normal operation and the documented parallel-current arrangement.
-
What is the normal bypass setting for DSTA170 57120001-FC?The current-output bypass jumpers are fitted for normal operation. Preserve the channel configuration and verify the circuit before changing a solder jumper.
-
What changes when DSTA170 57120001-FC is used with parallel current outputs?When two current outputs from the same or different boards feed one control object, the applicable bypass jumpers are opened in the documented arrangement. Do not parallel outputs without a complete circuit review.
-
Does DSTA170 57120001-FC determine analog-output resolution?No. Conversion resolution belongs to DSAO120. The associated board provides 12-bit resolution including sign; DSTA170 is the field-wiring connection unit.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-