Speak to a sourcing specialist
sales13@apterpower.com

AAR181-S50-S2

RTD Input Module
In Stock
Ships by Sunday, November 8
Fast Shipping Available
Yokogawa AAR181-S50-S2 RTD input module, angled view with front connector and label
Yokogawa AAR181-S50-S2 RTD input module, angled view of opposite end with edge connector
Yokogawa AAR181-S50-S2 RTD input module, side label printed MODEL AAR181 SUFFIX -S50
Yokogawa AAR181-S50-S2 RTD input module, angled view with front connector and label
Yokogawa AAR181-S50-S2 RTD input module, angled view of opposite end with edge connector
Yokogawa AAR181-S50-S2 RTD input module, side label printed MODEL AAR181 SUFFIX -S50
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

Yokogawa AAR181-S50-S2 is a 12-channel isolated RTD input module for three-wire Pt100 and JPt100 field measurements. The -S50 ordering segment denotes standard construction, no explosion protection and basic type.
Get a quick price for AAR181-S50-S2
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for AAR181-S50-S2

  • Manufacturer:
    Yokogawa
  • Product Category:
    DCS Systems
  • Spare Part Number:
    AAR181-S50-S2
  • Estimated shipping dimensions:
    3.2x10.8x13cm
  • Weight:
    0.2 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    Japan
  • Product function:
    Isolated resistance-temperature-detector input module
  • Input channels:
    12 isolated channels
  • Primary sensor:
    Pt100, three-wire type
  • Additional sensor:
    JPt100
  • RTD standard:
    JIS C1604:1997 and IEC 751:1995
  • Allowable input voltage:
    +/-5 V
  • Withstand voltage:
    1500 V AC / 1 min, input-to-system
  • RTD accuracy:
    +/-120 mOhm
  • Measurement current:
    1 mA
  • Wiring resistance:
    <=40 Ohm per wire
  • Data update period:
    1 second
  • External connection:
    Pressure-clamp terminal
  • Suffix -S:
    Standard type
  • Suffix 5:
    No explosion protection
  • Suffix 0:
    Basic type

Information

Overview Manuals Common Applications Product Precautions
Yokogawa AAR181-S50-S2 serves as the temperature-measurement interface between three-wire resistance sensors and a CENTUM VP field I/O node. Channel isolation keeps each measurement path separate while the module presents processed values to the host system.
  • Twelve isolated RTD input channels
  • Three-wire Pt100 measurement with JPt100 support
  • One-second data update period
  • Pressure-clamp terminal field connection

Use Yokogawa AAR181-S50-S2 only in the documented CENTUM VP field I/O context, with the field wiring, controller configuration and acceptance checks reconciled before service.

Important Notice: Confirm the complete AAR181-S50-S2 identifier and the installed interface conditions; do not substitute a nearby model without a documented engineering review.

Yokogawa AAR181-S50-S2 Manuals & Downloads
AAR181-S50-S2 Technical Reference (PDF)AAR181-S50-S2 Installation & Commissioning Guide (PDF)

Important Notice: The Technical Reference consolidates exact-model engineering data and interfaces; the Installation & Commissioning Guide organizes preparation, wiring checks and acceptance steps.

Process temperature acquisition
Collects twelve Pt100 or JPt100 resistance-temperature measurements for the control system.
Multi-point equipment monitoring
Brings several three-wire RTD points from vessels, piping or rotating-equipment auxiliaries into one isolated module.
Control-system maintenance
Supports exact-model replacement where the installed terminal arrangement and suffix code must be retained.
Loop fault investigation
Provides a defined channel structure for checking sensor, conductor and termination faults before module replacement.
Apply these checks specifically to Yokogawa AAR181-S50-S2 before installation, wiring changes, energization or return to service.
1
De-energize the node and field circuits before inserting, removing or rewiring the module.
2
Confirm the complete AAR181-S50-S2 code on the physical unit before replacement.
3
Use only documented three-wire Pt100 or JPt100 circuits; do not apply transmitter current or voltage signals.
4
Keep each conductor within the documented wiring-resistance limit and match the paired signal-conductor resistance.
5
Use the specified pressure-clamp terminal and check every clamp for secure conductor retention.
6
Do not infer an explosion-protection approval: suffix 5 denotes no explosion protection.
7
Preserve the final -S2 identifier until an exact project or manufacturer code record confirms its meaning.
8
Commission one channel at a time and compare the indicated temperature with a known reference before release.

Technical notes

Exact-model content for Yokogawa AAR181-S50-S2 is based only on the cited manufacturer documentation. Verify the installed unit, wiring and system configuration before replacement or commissioning.

FAQ View All FAQ

  • What signal type does Yokogawa AAR181-S50-S2 accept?
    It accepts three-wire Pt100 and JPt100 RTD signals.
  • How many channels are available on Yokogawa AAR181-S50-S2?
    The module provides twelve isolated RTD input channels.
  • What update period applies to Yokogawa AAR181-S50-S2?
    The data update period is one second.
  • Which field terminal is used with Yokogawa AAR181-S50-S2?
    It uses a pressure-clamp terminal.
  • What does the S50 segment mean in Yokogawa AAR181-S50-S2?
    S denotes standard type, 5 denotes no explosion protection, and 0 denotes basic type.
  • What must match when replacing Yokogawa AAR181-S50-S2?
    Match the complete code, node slot, terminal arrangement and channel assignments before installation.
  • What wiring check is required for Yokogawa AAR181-S50-S2?
    Keep wiring resistance at 40 ohms or less per wire and keep the paired signal-conductor resistance equal.
  • How should Yokogawa AAR181-S50-S2 be accepted after installation?
    Verify the exact code, inspect every clamp, energize the node, and compare each configured channel against a known temperature or resistance reference.
Related reading

Related cases and sourcing guidance

View all case studies
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.