Technical specifications for ET5*B

  • Manufacturer:
    Yokogawa
  • Product Category:
    General Automation
  • Spare Part Number:
    ET5*B
  • Estimated shipping dimensions:
    8x11.4x2.3cm
  • Weight:
    0.22 lbs (0.06 kg)
  • Tariff Code:
    8537101101
  • Counliy of origin:
    Japan
  • Product Type:
    Universal thermocouple input signal conditioner card
  • Supported Thermocouples:
    K, T, J, E, B, R, S and N
  • Input Standard:
    JIS C 1602 / IEC 60584-1 (ITS-90)
  • Measuring Span:
    10 to 63 mV thermoelectric conversion
  • Input Resistance:
    1 MΩ; 10 kΩ when power off
  • External Input Resistance:
    500 Ω maximum
  • Allowable Input Voltage:
    -0.5 to 4 V DC
  • Input Linearization:
    Provided
  • Output Signal:
    1 to 5 V DC, two outputs; output resistance 1 Ω max; load resistance 2 kΩ min
  • Burnout:
    Selectable upscale, downscale or off; scaleout <60 s
  • Signal Isolation:
    Input-to-output, input-to-power, and output-to-power isolation
  • Mounting Method:
    Mounted in special signal-conditioner nest
  • External Wiring:
    M4 screw terminals; special connector cable to I/O card
  • Dimensions:
    73 × 24 × 115 mm including knob
  • Accuracy:
    Larger of ±0.1% of span and ±20 µV input conversion
  • RJC Error:
    Type R/S: ±2°C; other types: ±1°C; no RJC for Type B
  • Isolation Resistance:
    100 MΩ at 500 V DC between specified isolated circuits
  • Withstanding Voltage:
    1500 V AC for 1 min input-to-output/input-to-power; 500 V AC output-to-power
  • Power Supply:
    24 V DC ±10%
  • Maximum Current Consumption:
    60 mA at 24 V DC
  • Ambient Conditions:
    0 to 50°C; 5 to 90% RH, non-condensing
  • Temperature Effect:
    Maximum ±0.2% of span per 10°C change
  • Supply Voltage Effect:
    Maximum ±0.1% of span over 24 V DC ±10%

Information

Overview Common Applications Product Precautions
The Yokogawa ET5*B is a microprocessor-based universal thermocouple input signal conditioner card used with YS1000 Series instruments. It accepts thermocouple types B, E, J, K, T, R, S and N and provides configurable engineering units, zero, span and upscale/downscale/off burnout behavior.
 
The card provides two isolated 1–5 V DC outputs and operates from 24 V DC ±10%. It mounts in the specified signal-conditioner nest, connects to field wiring through M4 screw terminals and uses the dedicated connector/backboard arrangement.
 
Product status: the official Yokogawa sources reviewed do not publish a formal discontinuation notice, discontinuation date or one-for-one successor for ET5*B. Confirm current supply and lifecycle status with Yokogawa for the exact suffix.
Direct thermocouple input for Yokogawa YS1000 Series single-loop control and monitoring instruments.
 
Temperature measurement using B, E, J, K, T, R, S or N thermocouples with selectable °C, °F or K engineering units.
 
Process applications requiring isolated signal conditioning, two 1–5 V DC outputs, configurable zero and span, and selectable upscale or downscale burnout behavior.
 
Typical use includes temperature monitoring and control in industrial process, utility and equipment-control panels where the installed YS instrument and signal-conditioner nest support ET5*B.
Connect the reference-junction-compensation sensor to the specified CN6 mating connector; an omitted connection can cause ambient-temperature offset and incorrect readings. Confirm thermocouple type, polarity, extension wire, range, engineering units and burnout direction. Use only the compatible signal-conditioner nest, special cable and M4 terminals. Operate at 0 to 50°C, 5 to 90% RH non-condensing and 24 V DC ±10%. Do not treat another card as a complete replacement until output, supply, nest interface, RJC wiring, isolation and configuration compatibility are verified.

Alternative Names

ET5B ET5-B ET5*B/YS Yokogawa ET5 thermocouple input card

Technical notes

Yokogawa identifies ET5*B as a microprocessor-based universal thermocouple input card used with YS1000 Series instruments. Official documents and the current Yokogawa application note do not publish a formal discontinuation notice, discontinuation date, or one-for-one successor, so no replacement should be described as a complete drop-in substitute. Before replacement, confirm thermocouple type and range, °C/°F/K engineering units, zero and span, burnout direction, dual 1–5 V DC outputs, 24 V DC supply, special-nest/backboard connector and M4 terminal wiring, reference-junction-compensation sensor connection, ambient limits, isolation, and the instrument configuration procedure. The RJC sensor connector must be fitted to CN6 where required; omission can create an ambient-temperature offset and incorrect reading.

FAQ View All FAQ

  • What is the Yokogawa ET5*B?
    ET5*B is a microprocessor-based universal thermocouple input signal conditioner card used with Yokogawa YS1000 Series instruments and configured through the instrument maintenance menu.
  • Which thermocouple types does ET5*B accept?
    It supports thermocouple types B, E, J, K, T, R, S and N. Engineering units can be configured as °C, °F or K together with zero, span and burnout behavior.
  • What output and power supply does ET5*B use?
    The card provides two 1–5 V DC outputs and operates from 24 V DC ±10%, with maximum current consumption of 60 mA according to the official specifications.
  • Where is ET5*B used?
    It is used for direct thermocouple temperature input in YS1000 Series control and monitoring applications where isolated signal conditioning and configurable ranges are required.
  • Why is the reference-junction sensor connection important?
    The card assembly reference-junction-compensation sensor must be connected as specified. Yokogawa warns that omitting the connector can create an ambient-temperature offset and an incorrect temperature reading.
  • Is Yokogawa ET5*B discontinued?
    The official Yokogawa sources reviewed do not publish a formal discontinuation notice, a discontinuation date or an official successor for ET5*B. Status should be confirmed with Yokogawa for the exact suffix.
  • Can another thermocouple card completely replace ET5*B?
    No complete replacement should be assumed without engineering review. A candidate must match the thermocouple types and range, dual outputs, supply, nest/backboard connection, RJC wiring, isolation, ambient limits and configuration method.
  • What information should be provided when requesting ET5*B?
    Provide a clear nameplate photo, complete model and suffix, thermocouple type, configured range and units, burnout setting, YS instrument model, nest/connector details, quantity and required documentation.
Manufacturers

You May Also Like

Explore related automation components available through Apter Power.
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.