Technical specifications for 6ES7405-0KA02-0AA0
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES7405-0KA02-0AA0
-
Weight:1.4 kg
-
Tariff Code:8537101190
-
Rated DC input:24 / 48 / 60 V DC
-
Static input range:19.2–72 V DC
-
Dynamic input range:18.5–75.5 V DC
-
Rated input current:4.0 / 2.0 / 1.6 A at 24 / 48 / 60 V
-
Inrush peak:18 A
-
Inrush half-value width:20 ms
-
Logic-rail rated voltage:5.1 V DC
-
Logic-rail capacity:10 A
-
Auxiliary-rail rated voltage:24 V DC
-
Auxiliary-rail capacity:1 A
-
Input power:95 W
-
Power loss:20 W
-
Mains interruption buffering:More than 20 ms, repetition interval 1 s
-
Power-off backup current:100 µA maximum
-
Optional backup batteries:2 × lithium AA, 3.6 V; use approved battery specification
-
Battery-monitor selection:OFF / 1 BATT / 2 BATT
-
Protective separation:Yes, according to IEC 61131-2
-
Protection class:Class I with protective conductor
-
Overvoltage category:II
-
Pollution degree:2
-
Secondary-to-PE test:700 V DC
-
Primary-to-secondary/PE test:2200 V DC
-
Feeder connection:3-pin; 3 × 1.5 mm² stranded with ferrules
-
Standby function:Outputs to 0 V; no feeder disconnection
Information
- Siemens 6ES7405-0KA02-0AA0 combines rack power conversion with supervision of the backup supply. The front controls allow output standby and fault acknowledgement while keeping the feeder-isolation and data-retention functions distinct.
Backup-state visibility: Battery and backplane-backup indicators help separate battery faults from converter faults.
Controlled acknowledgement: FMR clears retained fault indications after the underlying condition has been corrected.
The standby switch drives the output voltages to zero through the control loop and does not disconnect the incoming power. The three-pin feeder connector must not be inserted or removed under power. The front cover protects the battery connections and controls during operation, while the rack connector and supply position remain part of the installation check.
Two optional batteries support the backup arrangement rather than sustaining normal rack power. The BATT.INDIC selection determines which battery conditions are monitored; BAF concerns the backup voltage on the backplane, while BATT1F and BATT2F identify individual battery problems. A reset is meaningful only after the actual fault and expected monitoring mode have been reconciled.
6ES7405-0KA02-0AA0 Official S7-400 Power Supply Excerpt
Original English Siemens PS 405 10A ratings, backup controls and fault-indication guidance. PDF · 6 pages.6ES7405-0KA02-0AA0 Installation & Verification Guide
Apter Power rack-power service workbook covering feeder isolation, rail budgets, battery monitoring and restored-operation checks. PDF · 5 pages.
Application scope: Use the standard PS 405 10A within an approved rack arrangement. Plan normal rail loading, brief interruption handling and battery-backed data retention as separate design questions; the standard module is not a substitute for the redundant R version.
DC-fed S7-400 racks
Convert a supported plant DC feeder into the rack’s logic and auxiliary supply rails.Battery-supervised controller systems
Monitor the installed backup configuration and distinguish battery-specific faults from low backplane backup voltage.Rail-specific load planning
Allocate each installed module’s demand to the appropriate 5 V or 24 V rack capacity.Structured power-fault diagnosis
Use the combination of INTF, rail and battery indicators to direct checks before changing hardware.
Disconnect and secure the feeder before connector or wiring work; output standby is not isolation.
Verify the logic and auxiliary loads independently rather than using one combined current figure.
Record battery arrangement and monitoring switch position before a service action.
Investigate the indicated condition and then acknowledge retained indications.
Keep the cover closed in service and discharge static before accessing protected connections.
Compare the complete 0KA02 reference with the required rack role.
Alternative Names
Technical notes
Standby boundary: A zero output selected by standby does not prove the feeder connector is de-energized. Use the installation’s isolation procedure before handling it.
Backup indication: A delayed battery alarm after disconnection can reflect internal capacitance. Do not judge the monitoring function from an immediate observation alone.
Restart assessment: If the corrected overload does not permit restart after a few seconds, the applicable recovery guidance calls for removing input power for five minutes before retesting this module.
FAQ View All FAQ
-
Does moving 6ES7405-0KA02-0AA0 to standby make its feeder connector safe to unplug?No. Standby acts on the output control loop without disconnecting incoming power. Isolate and secure the external feeder and verify the electrical state before handling the three-pin connector.
-
Why can 6ES7405-0KA02-0AA0 report BAF even when both batteries look correctly installed?BAF monitors the backup voltage on the backplane, so other causes include an external backup-path problem, overload or short circuit. Compare individual battery indications with the complete backup circuit rather than replacing batteries solely from BAF.
-
What is the effect of selecting 1 BATT instead of 2 BATT on 6ES7405-0KA02-0AA0?The first setting monitors battery 1, while the second enables monitoring of both batteries. Match the selection to the actual backup arrangement and verify the intended alarms; the switch does not create a missing backup battery.
-
Can spare current capacity on the logic rail of 6ES7405-0KA02-0AA0 cover excess 24 V demand?No. The rails have separate ratings and load paths. Recalculate the installed modules’ demand for each rail and correct the overloaded allocation rather than relying on a combined wattage or total-current estimate.
-
What distinguishes a retained fault indication from an active overload on 6ES7405-0KA02-0AA0?After an overload is removed, the rail indication may flash until FMR is pressed. Check actual load and rail state before acknowledgement; a continuing overload requires corrective action, not repeated resetting.
-
How should 6ES7405-0KA02-0AA0 be assessed if it still fails to restart after a corrected short circuit?For this module, the recovery guidance calls for removing input power for five minutes when restart does not occur after a few seconds. Retest only after the fault and load are checked; continued failure requires further hardware assessment.
-
Can the backup batteries in 6ES7405-0KA02-0AA0 keep the entire rack running through a long feeder outage?No. Battery-backed retention and normal rack power are different functions. Evaluate process continuity separately from the backup arrangement and the brief input-interruption buffering capability.
-
Would exchanging 6ES7405-0KA02-0AA0 for a PS 405 10A R preserve the same system configuration automatically?No. Standard and redundant variants have different intended roles. Verify the complete article number, rack arrangement and redundancy design before accepting a substitution.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.