Match the complete marking
Match the complete Siemens 6ES5460-4UA11 marking and actual installed configuration. Check both range submodules, both mode-switch blocks and the sensor-front-connector arrangement.
-
Check the offered item before ordering
Compare offered-unit photographs, interfaces and included items with the installed 6ES5460-4UA11 and its applicable installation requirements.
Technical specifications for 6ES5460-4UA11
-
Manufacturer:Siemens
-
Product Category:PLC Systems
-
Spare Part Number:6ES5460-4UA11
-
Weight:0.54 kg
-
Tariff Code:8537101190
-
Analog inputs:8
-
Range-module grouping:4 channels per submodule
-
Digital representation:13-bit two’s complement or 12 bits plus sign
-
Conversion method:Integrating dual slope
-
Integration at 50 / 60 Hz:20 ms / 16⅔ ms
-
Coding time at 50 / 60 Hz:60 ms / 50 ms per value
-
Eight-channel cycle at 50 Hz:Approximately 0.48 s
-
Permissible common-mode potential:60 V AC / 75 V DC maximum
-
Low-level range:±50 mV
Information
- Siemens 6ES5460-4UA11 provides a configurable interface between field transducers and the S5 program, with independent attention required for range selection, digital representation and sensor reference potentials.
Signal processing: Selectable mains-frequency integration
Data interpretation: Preserve sign format and sensor scaling
Input channels are isolated from the reference potential and from one another, except in the Pt100 arrangement. Two-wire transducer connections also require attention to their common reference and can remove the isolation otherwise available between channels.
The integration setting must suit the mains frequency, and the program must decode the chosen signed-number representation. Validate the complete sensor-to-program path using an appropriate signal source, including the configured overflow and open-circuit response.
6ES5460-4UA11 Original Technical Excerpt
SIMATIC S5 Analog Modules, C79000-B8576-C300-06. Selected original pages retain the relevant technical tables and interface context. PDF · 9 pages.6ES5460-4UA11 Installation & Verification Guide
Apter Power field guide covering capture range and mode settings, check sensor references, reinstate the measurement hardware, validation and handover. PDF · 5 pages.
Application scope: The applications below describe the installed measurement or control path. Select compatible companion equipment; accessories are included only when expressly itemized.
Process-transducer acquisition
Convert the supported current or voltage range to the S5 input word.Resistance temperature measurement
Use the specified Pt100 excitation and reference wiring.Low-level voltage sensing
Match gain, compensation and input submodule to the sensor signal.Analog-loop restoration
Retain hardware range and numerical representation during replacement.
Record the two range-submodule identities, both mode-switch blocks, address and sensor wiring. Identify current-loop, voltage and resistance circuits separately, including any compensation arrangement.
Trace the sensor return and excitation paths. Review the Pt100 or two-wire-transmitter common-reference arrangement and confirm that the actual potential differences remain within the module limits.
Isolate the field circuit as required, then restore the module, submodules and front connector according to the installation procedure. Select the recorded integration frequency and digital representation; retain the original range mode.
Apply traceable reference signals at zero and suitable nonzero points. Allow the integrating conversion and channel scan to settle; compare each input word with the configured sign and scale.
Test the supported overflow and open-circuit response with the process secured. Remove temporary signal sources, restore each sensor and record the final range, switch settings and observed diagnostics.
Retain the final 6ES5460-4UA11 identity, tested settings and accepted channel or system response for subsequent maintenance.
Alternative Names
Technical notes
Range hardware: Two four-channel submodules define the electrical input circuits. Verify their part numbers and mode compatibility before connecting a current loop or voltage source.
Sensor-reference boundary: The Pt100 wiring arrangement does not retain isolation between individual inputs. Assess common references and the permitted common-mode voltage for the actual sensor circuit.
Sampling and diagnostics: The integrating converter rejects interference in relation to the selected mains frequency. Account for the full channel scan when evaluating a fast-changing process signal.
FAQ View All FAQ
-
Why can 6ES5460-4UA11 show a plausible value with the wrong range submodule installed?A wrong divider or shunt can still produce a stable digital result. Check the physical submodule and inject known signal points before accepting the program scaling.
-
How does the mains-frequency setting affect measurements with 6ES5460-4UA11?It determines the integration interval used to reject periodic interference. Select the actual supply-network frequency and investigate noise before modifying software filtering.
-
Does Pt100 wiring preserve channel-to-channel isolation on 6ES5460-4UA11?No. The Pt100 arrangement is an exception to the channel-isolation statement, so sensor references must be assessed as a connected measurement circuit.
-
Why must the S5 program data format match the switch setting on 6ES5460-4UA11?Two’s complement and absolute value plus sign encode negative values differently. A mismatch can give incorrect sign or magnitude even when the analog signal is correct.
-
How should unused voltage inputs on 6ES5460-4UA11 be terminated?Use the termination arrangement specified for the installed divider, shunt or continuity submodule and open-circuit mode. Do not apply one jumper scheme to every range type.
-
Can a 2-wire transmitter be connected to 6ES5460-4UA11 without reviewing the reference wiring?No. Its supply and return arrangement changes the reference relationships and may remove isolation between channels and the load supply.
-
Why does a fast signal step reach different channels of 6ES5460-4UA11 at different times?The channels are converted sequentially. Evaluate the complete acquisition cycle instead of treating all input words as simultaneous samples.
-
What should be tested after moving a sensor from one group of 6ES5460-4UA11 to another?Check the destination range submodule, open-circuit selection, compensation and software scaling, then verify several known input points.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.