Record the full IC693PTM101A marking, the revision on each matched hardware element and the installed rack position. Keep that set identity on the enquiry and quotation.
-
Check the offered item before ordering
Request available labels for the rack module, matching interface board and connecting cable. Have your maintenance team compare the offered IC693PTM101A set with the installed equipment and applicable GE documentation.
Technical specifications for IC693PTM101A
-
Manufacturer:General Electric
-
Product Category:PLC Systems
-
Spare Part Number:IC693PTM101A
-
Weight:0.2 kg
-
Tariff Code:8537101190
-
Power-system modes:Single phase; three-phase wye or delta
-
Backplane demand:5 VDC at 400 mA maximum
-
Module dissipation:4 W maximum
-
Backplane isolation:1500 V
-
PT voltage range:10–150 VAC RMS; 120 VAC nominal
-
CT current range:0–7.5 A RMS; 5 A nominal
-
Input frequency:35–70 Hz
-
A/D resolution:14 bits
-
PLC discrete exchange:16 %I bits and 16 %Q bits
-
PLC analog exchange:25 %AI words and 2 %AQ words
-
Interface connection:Shielded DB-25 cable
-
Input terminal ratings:15 A current and 150 V voltage maximum
Information
- The rack module exchanges commands, measured values and fault status with the PLC. External current and potential transformers, the matched interface board and the site wiring complete the measurement chain.
System boundary: Keep the matched interface board and cable with the processing module
Measurement path: External CT and PT circuits supply the field signals
Acceptance focus: Prove scaling, phase wiring and PLC data exchange against the installed design
In synchronism-monitor mode, the system compares generator and grid voltage, frequency and relative phase. GE describes a 20 ms calculation interval at 50 Hz and 16.67 ms at 60 Hz. The PTM is a measurement input to the control application; a separate protective scheme is required for protection.
GE GFK-1734A lists IC693PTM101 with its matched interface board and a 39-inch cable. The interface board converts CT and PT signals for the rack module; it has no CT shorting bars. The final terminal map, transformer ratios, grounding and PLC word allocation must be established from the installed electrical design.
-
GE Fanuc Series 90-30 PTM User's Manual (GFK-1734A)
GE Fanuc original manual - PDF, 61 pages. Base IC693PTM101 set, electrical limits, PLC exchange and installation. -
General Electric IC693PTM101A installation guide
Prepared by Apter Power - PDF, 2 pages. Identification, installation checks, commissioning and fault isolation.
Application scope: Use its power-monitor or synchronism-monitor data only where the Series 90-30 program and external transformers are engineered for the selected network.
-
Energy and demand monitoring
Bring calculated power, energy, power factor and sliding demand values into a Series 90-30 program for site reporting or load management. -
Generator-grid comparison
Use generator and grid measurements for a programmed synchronization decision with independent switchgear interlocks. -
Three-phase circuit observation
Select the documented wye or delta mode and validate PT/CT polarity and ratios against the actual power circuit. -
Matched-set replacement
Exchange the processor and matching interface board as a pair and confirm the supplied 39-inch cable reaches the installed cabinet layout.
Disconnect all connected power-distribution circuits before servicing the interface board or sensing transformers.
Install the interface-board frame ground first, before any other connection, as required by GE.
The interface board has no built-in CT shorting bars. Provide the specified external shorting arrangement and follow the site CT isolation procedure.
Compare transformer secondary values with the voltage, current, frequency and terminal ratings before energizing.
Do not interchange the paired processor and interface boards without checking the complete set and revision.
Recheck %I, %Q, %AI and %AQ allocation, PT/CT ratios, measurement mode and alarm logic after replacement.
Alternative Names
Technical notes
System relationship: The rack processor requires its matched interface board, shielded DB-25 cable and correctly scaled CT/PT field circuits.
Protection boundary: The PTM is a measurement device; provide external CT shorting and independent electrical protection.
Technical reference: GE Fanuc Power Transducer for the Series 90-30 PLC User’s Manual, GFK-1734A, January 2000. Base IC693PTM101 values require A-suffix verification.
FAQ View All FAQ
-
Why must IC693PTM101A be checked as a matched hardware set?GE describes the IC693PTM101 base configuration as a rack processing module paired with a specific interface board and cable. The boards are treated as one set, so confirm both labels, the DB-25 lead and the installed revision before replacement.
-
How does IC693PTM101A distinguish power monitoring from synchronization monitoring?The Series 90-30 program selects the operating mode through the PTM command bits. Power-monitor mode calculates electrical quantities; synchronism mode compares generator and grid voltage, frequency and phase. Confirm the application logic and transformer wiring for the intended mode.
-
Why are external CT shorting provisions needed with IC693PTM101A?The GE interface board does not include CT shorting bars. Use a suitable external arrangement and the plant isolation procedure before opening any CT secondary circuit.
-
What should be verified before IC693PTM101A is connected to a three-phase circuit?Confirm wye or delta configuration, transformer secondary ratings and ratios, polarity, grounding and terminal assignments. Then compare live phase measurements and PLC data words with an independent meter or site baseline.
-
Can IC693PTM101A serve as the plant protective relay?The GE PTM manual describes measurement and monitoring functions and explicitly excludes protective-relay use. Keep independent protection and switchgear interlocks as designed for the installation.
-
How is the Series 90-30 I/O image allocated for IC693PTM101A?The documented PTM uses 16 %I and 16 %Q bits plus 25 %AI and 2 %AQ words. Check the actual baseplate address, available memory and project configuration before downloading the PLC program.
-
What distinguishes the documented IC693PTM101 configuration used by IC693PTM101A?GE distinguishes PTM101 from PTM100 by the supplied interface-cable length: 39 inches versus 19 inches. The A suffix is not decoded in GFK-1734A, so verify it against the offered unit instead of assuming another electrical difference.
-
What acceptance test should follow an IC693PTM101A exchange?Verify frame ground, CT/PT terminations and cable seating first. Energize under the approved plan, check status and fault bits, then compare measured RMS values, phase data and calculated quantities with expected test or operating values.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.