IC670ALG230

GE Fanuc eight-channel common-supply analog current input module
In Stock
Ships by Thursday, November 12
Fast Shipping Available
Product image is representative; revision or series may vary. Contact us to request a specific version.

Product Describe:

GE IC670ALG230 is ge fanuc eight-channel common-supply analog current input module. It converts eight common-supply current-loop signals into scaled process values for the Field Control host.
Get a quick price for IC670ALG230
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for IC670ALG230

  • Manufacturer:
    General Electric
  • Product Category:
    PLC Systems
  • Spare Part Number:
    IC670ALG230
  • Estimated shipping dimensions:
    5.3x8.5x8.1cm
  • Weight:
    0.24 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Input channels:
    8
  • Input ranges:
    0 to 20 mA; 4 to 20 mA
  • Typical digital resolution:
    12 bits; 5 microA
  • Input span:
    0.1 to 20 mA
  • Maximum input:
    30 mA
  • Input resistance:
    249.75 to 250.25 ohm
  • Conversion time:
    60 microseconds per channel at 1 MHz
  • Filter cutoff:
    160 Hz typical
  • Error at 25 degC:
    +/-0.05% full scale
  • Nonlinearity:
    +/-0.025% full scale
  • External supply:
    18 to 30 V DC; 24 V typical
  • Module current including loops:
    210 mA maximum
  • BIU current:
    51 mA maximum

Information

Overview Manuals Common Applications Product Precautions
GE IC670ALG230 is ge fanuc eight-channel common-supply analog current input module. It converts eight common-supply current-loop signals into scaled process values for the Field Control host.
  • Accepts eight 0-20 mA or 4-20 mA inputs
  • Uses a precision 250-ohm input path
  • Converts each channel in 60 microseconds at 1 MHz
  • Provides configurable scaling and open-wire supervision

IC670ALG230 operates with Two-wire or externally powered transmitters, 18 to 30 V DC loop supply, Field Control BIU revision supported by the station, Shielded analog field wiring.

Engineered applications include eight-channel analog current acquisition field station, Remote I/O cabinet integration, Installed-base module renewal, Controlled commissioning and diagnostics.

Important Notice: Confirm the common return, 250-ohm input path, selected 0-20/4-20 mA range and external loop supply before forcing calibrated current points.

Apter Power IC670ALG230 Manuals and Guides

Apter Power IC670ALG230 Technical Data and System Reference PDFIC670ALG230 Field Installation and Commissioning Workbook PDF

The first document presents model-specific technical data and system identity. The second provides a separate installation, wiring and commissioning workflow.

eight-channel analog current acquisition field station

Performs the documented eight-channel analog current acquisition function at a distributed Field Control station.

Remote I/O cabinet integration

Exchanges configured process data with the host through the installed bus interface.

Installed-base module renewal

Restores an exact catalog-number position while preserving terminal and data identity.

Controlled commissioning and diagnostics

Supports staged wiring, configuration, diagnostic and functional verification.

Read the applicable GE Fanuc Field Control instructions before work. Verify IC670ALG230, its terminal assignment and the installed station configuration.
1

Verify the complete IC670ALG230 catalog marking and assigned Field Control position before work.

2

Place the connected eight-channel analog current acquisition process in its approved maintenance state before disturbing the station.

3

Isolate BIU and field power, then confirm a safe condition at the IC670ALG230 terminal block.

4

Label and record channel conductors, returns, shields and external supply wiring before disconnecting any conductor from IC670ALG230.

5

Use ESD controls and protect the module connector, terminal block keying and exposed electronics.

6

Restore only the documented channel range, scaling, alarms and default behavior; do not copy settings from an adjacent module.

7

Energize in a controlled sequence and review PWR, channel, module and network diagnostics.

8

Complete low, midpoint and high signal checks plus alarm and diagnostic verification and retain the final result before returning the process to service.

Technical notes

Confirm the common return, 250-ohm input path, selected 0-20/4-20 mA range and external loop supply before forcing calibrated current points.

FAQ View All FAQ

  • What Field Control function is assigned to IC670ALG230?
    IC670ALG230 is ge fanuc eight-channel common-supply analog current input module. It converts eight common-supply current-loop signals into scaled process values for the Field Control host.
  • Which station hardware must be paired with IC670ALG230?
    Use IC670ALG230 with the documented Field Control terminal block, compatible BIU or MFP, and the installed two-wire or externally powered transmitters.
  • Which IC670ALG230 identity should be checked before installation?
    Confirm the full IC670ALG230 catalog marking and the catalog number value IC670ALG230 against the installed station record.
  • How should field wiring be transferred when replacing IC670ALG230?
    Label and record channel conductors, returns, shields and external supply wiring before disconnecting any conductor from IC670ALG230.
  • Which configuration item is critical when commissioning IC670ALG230?
    Restore only the documented channel range, scaling, alarms and default behavior; do not copy settings from an adjacent module.
  • What diagnostic checks apply to IC670ALG230?
    Energize in a controlled sequence and review PWR, channel, module and network diagnostics.
  • How should the IC670ALG230 signal path be functionally tested?
    Complete low, midpoint and high signal checks plus alarm and diagnostic verification and retain the final result before returning the process to service.
  • Can IC670ALG230 be replaced by a visually similar Field Control module?
    No direct substitution should be assumed. Match IC670ALG230, its terminal assignment, data allocation, signal type, power arrangement, and the documented biu current value 51 mA maximum before migration.
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.