Match the complete marking
Include 369-HI-R-0-0-0-0-E and every visible revision or serial identity in your enquiry. Keep the same complete reference on the quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 369-HI-R-0-0-0-0-E with the installed equipment and applicable GE documentation.
Technical specifications for 369-HI-R-0-0-0-0-E
-
Manufacturer:General Electric
-
Product Category:General Automation
-
Spare Part Number:369-HI-R-0-0-0-0-E
-
Weight:3.5 kg
-
Tariff Code:8537101190
-
Relay family:369 Motor Management Relay
-
Control supply:HI: 50–300 V DC or 60–265 V AC
-
Built-in RTD inputs:R: 12
-
Harsh-environment option:0: not selected
-
Faceplate/diagnostics:E: enhanced
-
Base analog output:One; additional outputs require M or B option
-
Mechanical execution:Non-drawout
-
Setup utility:EnerVista 369 Setup, with firmware-matched settings
Information
- GE Multilin 369-HI-R-0-0-0-0-E supervises a motor through the 369 protection platform, with the ordered RTD channels and enhanced diagnostic interface available for the installed motor scheme.
Thermal review: Map each installed RTD to the protected winding or bearing
Acceptance path: Test alarms and trips against the starter's operating state
The zero-option positions omit the optional metering or backspin package, fiber-optic port, extra protocol interface and harsh-environment execution. One analog output remains available on the base relay; the additional three analog outputs belong to the metering or backspin option and should not be attributed to this code.
Enhanced execution provides motor-status indicators, a Motor Health Report, learned motor data, a start data logger, an expanded event recorder and security-audit events. Protection performance still depends on the installed CT circuits, motor model, RTD wiring, programmed setpoints and relay firmware.
-
General Electric 369-HI-R-0-0-0-0-E technical reference
Original manufacturer excerpt - PDF, 5 pages. Motor Management Relay identity, interfaces and engineering scope. -
General Electric 369-HI-R-0-0-0-0-E installation guide
Prepared by Apter Power - PDF, 5 pages. Preparation, installation, testing and handover for 369-HI-R-0-0-0-0-E.
Application boundary: The HI/R/E options provide control power, temperature inputs and enhanced diagnostics; optional metering, backspin, fiber and network packages are absent from this order code.
-
Motor thermal protection
Combine the configured motor thermal model with winding, bearing or auxiliary RTD measurements to supervise temperature-related limits. -
Starter trip coordination
Connect the programmed alarm and trip outputs to the installed starter logic, proving each action under the site's protection test plan. -
Condition event review
Use enhanced learned data, motor health information and event records to investigate starts, thermal loading and abnormal trips. -
Local maintenance access
Review motor status and alarm conditions at the enhanced faceplate while preserving the as-left firmware and setting record.
Use the approved CT shorting/isolation procedure before disturbing current wiring, and verify ratio and polarity after work.
Check the actual panel supply is inside 50–300 V DC or 60–265 V AC before energizing; do not use a LO relay's supply assumption.
Map each connected sensor to its motor location and chosen RTD type. Check lead continuity, sensor response and alarm assignment channel by channel.
Export settings and record firmware, thermal model, CT ratios, RTD types, trip delays and output logic before replacement.
Do not plan optional metering/backspin, fiber, protocol or harsh-environment functions for the zero-coded positions.
Test the intended trip/alarm outputs and breaker or contactor response in a controlled condition; restore the site-approved protection state.
Alternative Names
Technical notes
Motor protection relationship: Configure current-transformer ratios, motor thermal model, trip contacts and RTD inputs for the actual starter and motor. The R option supplies twelve built-in RTD channels; sensor type is selected in software.
Option boundary: The four zero positions omit the optional metering/backspin package, fiber port, protocol interface and harsh-environment package. The E suffix adds enhanced diagnostics and faceplate functions.
Technical reference: GE Multilin 369 Motor Management Relay Instruction Manual, 369man-bx. The full order code is explicitly listed as a HI/R/E example; actual firmware and protection setpoints are retained from the installed relay.
FAQ View All FAQ
-
What supply checks are needed before energizing 369-HI-R-0-0-0-0-E?Measure the auxiliary source at the relay terminals and compare it with the HI option's 50–300 V DC or 60–265 V AC range. Check protective wiring and the motor-starter interface before power-up; the HI code does not describe the site's actual connected voltage.
-
How should the RTD inputs of 369-HI-R-0-0-0-0-E be assigned to the motor?The R option provides twelve built-in RTD channels. Identify each connected sensor by winding or bearing location, verify its selected sensor type and loop continuity, and compare readings with the motor's known condition; unused channels should not be interpreted as measured temperatures.
-
Which optional functions must be excluded from a protection plan for 369-HI-R-0-0-0-0-E?The zero option in the metering/backspin position does not select those packages or their additional analog outputs. Preserve the base relay functions, including one analog output, but do not assign optional features or three extra outputs to this ordered unit without separate fitted-hardware evidence.
-
How should communications be planned for 369-HI-R-0-0-0-0-E without assuming a fiber port?The fiber-option position is zero. Identify the actual fitted communication hardware and terminal wiring, then confirm the protocol and configuration used by the site; the broader 369 family may support options that are not installed on this order code.
-
How can the enhanced diagnostics of 369-HI-R-0-0-0-0-E support fault review?The E execution adds an enhanced faceplate and diagnostic functions such as motor-health information, learned data, start logging and expanded event records, subject to installed firmware. Record the firmware revision and correlate events with motor operation before changing protection settings.
-
How should RTD faults be checked on 369-HI-R-0-0-0-0-E?Verify sensor type, loop wiring and channel assignment first. Compare temperature readings against the motor's known operating condition and investigate open, shorted or misassigned loops before changing trip thresholds.
-
Can 369-HI-R-0-0-0-0-E be swapped without restoring settings?No. Preserve the original firmware and settings, including CT ratios, thermal model, RTD types and trip-output mapping; compare the restored configuration with the motor protection study and test the starter interface.
-
What should be proven before 369-HI-R-0-0-0-0-E returns to service?Verify HI supply, CT inputs, each used RTD, alarm/trip logic, enhanced indications and the starter response under a controlled commissioning procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.