Technical specifications for KJ3001X1-BA1 1290549X152
-
Manufacturer:Emerson
-
Product Category:DCS Systems
-
Spare Part Number:KJ3001X1-BA1 1290549X152
-
Estimated shipping dimensions:22.5x14x5cm
-
Weight:0.38 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Card function:DI, 8-channel, 24 VDC, isolated
-
LocalBus power:12 VDC at 100 mA
-
Field circuit:24 VDC at 5 mA per channel
-
Ambient temperature:0 to +60 degrees C
-
Relative humidity:5 to 95% non-condensing; IP20 rating
-
Shock:10 g half-sine for 11 ms
-
Vibration:1 mm peak-to-peak from 5 to 16 Hz; 0.5 g from 16 to 150 Hz
-
Airborne contaminants:ISA-S71.04-1985 Class G3
-
Terminal-block key:A4
-
Maintenance:No user-serviceable parts; no calibration
Information
- Reports isolated field-contact states on eight separate channels
- Uses A4 keying to align the card with its intended terminal block
- Allows powered insertion only under the instruction sheet's stated supply conditions
- Retains the full secondary identifier as an installation-specific check
Treat 1290549X152 as part of the installed identity even though the card-level instruction establishes the KJ3001X1-BA1 electrical ratings. Record the rack position and terminal assembly before removal.
After connection, stimulate each field input individually and compare the resulting controller state with the loop drawing so channel order and isolation remain traceable.
Important Notice: Do not infer interchangeability from the KJ3001X1-BA1 family code alone; the secondary marking and A4 terminal assignment must match the field record.
The Technical Reference records the discrete-input and A4 keying boundaries for the exact marking. The Installation & Commissioning Guide covers channel mapping, field-power isolation, conditional insertion and input-state acceptance.
Technical notes
FAQ View All FAQ
-
How many isolated inputs does Emerson KJ3001X1-BA1 1290549X152 provide?The KJ3001X1-BA1 manufacturer sheet identifies eight isolated 24 VDC discrete-input channels.
-
What LocalBus demand must the cabinet support for Emerson KJ3001X1-BA1 1290549X152?The card electronics require 12 VDC at 100 mA from the LocalBus supply.
-
Which terminal-block key belongs with Emerson KJ3001X1-BA1 1290549X152?The documented rotary-key position is A4, which must match the installed terminal block before insertion.
-
What field input applies per channel on Emerson KJ3001X1-BA1 1290549X152?The exact card sheet lists a 24 VDC field circuit at 5 mA per channel.
-
When must field power be removed from Emerson KJ3001X1-BA1 1290549X152?Field power must be removed before connecting or disconnecting the device.
-
Can Emerson KJ3001X1-BA1 1290549X152 be inserted with system power present?Only the conditional one-unit insertion method and the specified dual DC/DC supply boundary in the manufacturer instruction may be used; otherwise system power must be de-energized.
-
What operating environment is documented for Emerson KJ3001X1-BA1 1290549X152?The sheet lists 0 to +60 degrees C, 5 to 95% non-condensing relative humidity and an IP20 rating.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-