Match the complete marking
Compare the full Emerson IC695ALG728 marking, hardware execution and mating interfaces with the installed position before approving a replacement.
-
Check the offered item before ordering
Request clear photographs of the offered IC695ALG728 marking and connections. Ask the maintenance team to compare them with the applicable Emerson instructions and the installed circuit or system design.
Technical specifications for IC695ALG728
-
Manufacturer:Emerson
-
Product Category:PLC Systems
-
Spare Part Number:IC695ALG728
-
Weight:0.26 kg
-
Tariff Code:8537101190
-
Output channels:8, non-isolated
-
Current output:0–20 mA or 4–20 mA
-
Voltage output:±10 V or 0–10 V
-
External supply:19.2–30 V DC; 250 mA maximum
-
HART protocol:Version 5.0
-
Analog update:About 16 ms with HART; 8 ms without HART, all channels
-
Current load:850 Ω maximum at 20 V supply
-
Voltage load:2 kΩ minimum
-
Settling to 95%:70 ms current with HART; 23 ms without HART; 2 ms voltage
Information
- Each channel uses its selected voltage or current range; HART data transfer is an additional communication function rather than a replacement for the analog command path.
Device communication: HART information alongside the current loop
Timing model: distinguish output refresh, settling and device polling
Analog output refresh, output settling and HART variable acquisition have different timing. HART traffic is grouped and asynchronous to the analog scan. The application should distinguish a fresh analog command from a newly acquired digital device variable when supervising a final element.
Use the selected voltage range with a receiver whose load meets the output requirements. Validate the CPU and I/O path for supported HART pass-through to a monitoring station. Inspect field power, terminal-block seating and enabled-channel faults. Module readiness does not establish that every output circuit is healthy.
IC695ALG728 Apter Power Technical Reference
Apter Power technical reference for IC695ALG728, covering the verified interface and operating limits. PDF · 5 pages.IC695ALG728 Installation & Verification Guide
Apter Power service guide covering record final-element behavior; verify direct field power; check loop compliance and controlled acceptance. PDF · 5 pages.
Application scope: Applications must satisfy the module or transducer boundary and the actual controller, receiver or target conditions.
Smart final elements
Combine a supported analog command with HART access to compatible field-device information.Voltage command circuits
Use the selected voltage range with a receiver whose load meets the output requirements.Asset-management integration
Validate the CPU and I/O path for supported HART pass-through to a monitoring station.Defined loss-of-control behavior
Use the configured output fallback or hold strategy as part of an engineered final-element response.
Capture channel ranges, scaling and hold/default settings. Put actuators in their approved maintenance condition before disturbing output wiring.
Measure the external supply at the module terminal block and identify its return. Confirm that the source is not mistakenly routed only to backplane TB1.
Review the complete current-loop resistance and the expected minimum supply. Include any HART connection equipment and receiving-device requirements.
Test low, middle and high analog commands after allowing the applicable settling time. Separately check HART device identity and variable updates.
Test the approved controller-stop or communication-loss response with the process protected. Restore channel diagnostics and confirm the final element returns to commanded operation.
Keep the affected process in its approved maintenance state until field indications and the intended control or monitoring response have both been checked.
Alternative Names
Technical notes
Configuration scope: Technical values apply to IC695ALG728 with the stated operating conditions. Check supplied revision and the configured installation.
Engineering acceptance: The intended hart analog output module function must be accepted with its actual mating interfaces and configured system. Review the complete current-loop resistance and the expected minimum supply. Include any HART connection equipment and receiving-device requirements.
FAQ View All FAQ
-
Why can an IC695ALG728 HART variable update more slowly than its analog output?HART acquisition is asynchronous and depends on device grouping, retries and requested variables. Do not use analog scan time as the digital-device update interval.
-
Can the RX3i backplane TB1 supply replace the direct field-power connection on IC695ALG728?No. The external supply must connect directly to this module terminal block. A powered backplane alone does not energize the analog output circuits.
-
How should loop resistance be assessed for IC695ALG728?Include the receiving device, wiring and any series equipment in the load total. Check compliance at the lowest field supply rather than only at nominal voltage.
-
Why does IC695ALG728 require a slower acceptance test when HART is enabled?Current-output settling is longer with HART enabled. Allow the specified settling interval before comparing a new command with a measured current.
-
Does IC695ALG728 need thermal review when several current outputs are loaded?Yes. Current-mode derating depends on supply voltage, load and active channels. Evaluate the actual combination rather than assuming eight channels always support the same ambient limit.
-
What should be checked if IC695ALG728 Field Status is amber but Module OK is green?Inspect field power, terminal-block seating and enabled-channel faults. Module readiness does not establish that every output circuit is healthy.
-
How can IC695ALG728 default-output settings affect a stopped controller?The configured hold/default behavior determines the command retained or applied during the relevant loss-of-control condition. Test that response against the final element’s safe process state.
-
Why should IC695ALG728 HART pass-through be validated at system level?It relies on a compatible CPU, I/O location and software communication path. A HART-capable output module alone does not establish end-to-end access from an asset-management station.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.