Technical specifications for CON021
-
Manufacturer:Emerson
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:CON021
-
Estimated shipping dimensions:16x15x4cm
-
Weight:0.3 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Alternative model:SNG-CON021
-
Compatible sensors:PR6422; PR6423; PR6424; PR6425; PR6426; PR6453
-
Frequency response:0 to 20 kHz (-3 dB)
-
Rise time:<15 us
-
Supply for -4 to -20 V output:-23 to -32 V DC
-
Supply for -2 to -18 V output:-21 to -32 V DC
-
Operating temperature:-30 to +100 degC
-
Shock and vibration:5 g at 60 Hz at 25 degC
-
Ingress protection:IP20
-
Sensor connector:Self-locking LEMO
-
Supply/output terminal capacity:1.5 mm2 maximum
-
Housing material:LMgSi0.5F22
Information
- Interfaces six documented PR642x/PR6453 sensor families
- Passes dynamic shaft motion through a 20 kHz bandwidth
- Uses a self-locking LEMO probe connection
- Provides a voltage output for the connected monitor channel
CON021 operates with Matched PR642x or PR6453 probe, Compatible extension cable where specified, Negative DC instrument supply, Voltage-input machinery monitor.
Engineered applications include Radial shaft-vibration loops, Axial position measurement, Machine centerline observation, Eccentricity and expansion monitoring.
Important Notice: Mount the converter with four M5 fasteners, verify the PR642x family and output range, isolate the negative DC supply, and prove gap voltage plus dynamic response before enabling alarms.
Apter Power CON021 Manuals and Guides
Apter Power CON021 Measurement-System Technical Reference PDFApter Power CON021 Installation, Loop Check and Acceptance Workbook PDFThe first document provides model-specific technical and measurement-system reference data. The second is a separate field workbook for mounting, wiring, commissioning and acceptance records.
Radial shaft-vibration loops
Conditions probe motion for vibration trending and protection.
Axial position measurement
Converts thrust-position displacement into a monitor-ready voltage.
Machine centerline observation
Maintains a stable non-contact reference for slow shaft-position changes.
Eccentricity and expansion monitoring
Supports low-frequency mechanical movement measurements with the matched probe.
Confirm the complete CON021/SNG-CON021 identification and the paired PR642x probe type before removal.
Place the monitored machine and protection channel in the approved maintenance state.
Isolate the negative DC supply and record supply polarity plus output conductors.
Protect the self-locking LEMO interface from dirt, moisture and bent contacts.
Mount the replacement with four M5 fasteners on a stable grounded panel.
Verify the selected -4 to -20 V or -2 to -18 V output arrangement against the monitor input.
Set the probe gap in the approved linear region and check the quiescent output.
Prove dynamic response, polarity and alarm action before returning the channel to service.
Alternative Names
Technical notes
FAQ View All FAQ
-
What measurement or system function does CON021 perform?CON021 is a pr642x eddy-current sensor signal converter. It supplies and conditions a compatible PR642x probe and delivers the configured proportional voltage signal to the monitoring system.
-
Which installed hardware must be paired with CON021?Use CON021 with the documented PR642x eddy-current transducer system components: Matched PR642x or PR6453 probe, Compatible extension cable where specified, Negative DC instrument supply.
-
How should the Converter model value for CON021 be verified?Confirm the complete nameplate and order code before work; the documented converter model is CON021.
-
What connection detail is critical when installing CON021?Preserve every conductor, connector and shield identity, then follow the model-specific connection arrangement described in the controlling Emerson document.
-
How is CON021 mechanically installed without changing measurement behavior?Isolate the negative DC supply and record supply polarity plus output conductors.
-
What commissioning test should be completed for CON021?Prove dynamic response, polarity and alarm action before returning the channel to service.
-
What configuration record should be retained when replacing CON021?Retain the as-found position, alternative model, cable or channel identity, gap or scaling value, diagnostics and final functional-test result.
-
Can CON021 replace a similar Emerson model without engineering review?No direct substitution should be assumed; verify the full order code, measuring function, interface, cable or channel arrangement and the approved PR642x eddy-current transducer system configuration.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.