The monitor brings turbine drivetrain measurements into a dedicated condition-monitoring system for fault detection, trending and maintenance planning.
Collects turbine drivetrain condition signals.
Supports vibration trending across critical rotating components.
Provides a dedicated platform for wind-turbine monitoring.
Integrates measured data with diagnostic and maintenance workflows.
Use 3701/60A only in the specified monitoring chain and verify the complete signal path after controlled replacement.
Important Notice: Capture the installed 3701/60A interfaces and configuration before removal, then prove the monitored value, status and alarm path after installation.
The first PDF covers the product function, system role and technical selection. The installation guide covers identification, connection checks, commissioning and the acceptance test results.
Gearbox condition monitoring
Tracks bearing and gear vibration patterns.
Generator monitoring
Supervises generator-bearing condition.
Main-bearing trending
Tracks long-term vibration changes.
Wind-farm maintenance
Supports condition-based maintenance decisions.
Before installing Bently Nevada 3701/60A, confirm the specified system, interfaces and controlled configuration.
1
Confirm the complete 3701/60A marking and the specified wind turbine condition monitor position.
2
Place the affected machine protection channel in the approved maintenance state.
3
Capture the installed system family, primary asset and monitoring role before removal.
4
De-energize the associated monitor, sensor supply or field circuit as the procedure requires.
5
Label every connector, conductor and shield before separation.
6
Inspect mating contacts, mounting hardware and cable condition before installation.
7
Restore the retained configuration and verify signal polarity and proportional response.
8
Function-test the complete alarm, indication and shutdown path before returning the machine to service.
Technical notes
Capture the installed 3701/60A interfaces and configuration before removal, then prove the monitored value, status and alarm path after installation.