Match the complete marking
Compare the complete Bently Nevada 330851-02-000-060-10-00-00 marking, hardware configuration and connections with the installed item before approving a replacement.
-
Check the offered item before ordering
Request clear label and connector photographs of Bently Nevada 330851-02-000-060-10-00-00. Ask your maintenance team to compare the offered item with the installed equipment and the applicable Bently Nevada 3300 XL 25 mm Proximity Transducer System, 163236 Rev. M before ordering.
Technical specifications for 330851-02-000-060-10-00-00
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:330851-02-000-060-10-00-00
-
Weight:0.4 kg
-
Tariff Code:8537101190
-
Transducer family:3300 XL 25 mm
-
Mounting thread:M30×2
-
Overall case length:60 mm
-
Unthreaded-length selection:0 mm
-
Total probe lead:1.0 m
-
Lead armor:None
-
Probe resistance, center to outer:6.2 ± 0.5 Ω
-
Probe tip / case material:PEEK / AISI 304 stainless steel
-
Cable construction:75 Ω triaxial, PFA-insulated FluidLoc
-
Matched-system scale factor:0.787 V/mm nominal
-
Matched-system linear range:12.7 mm under specified calibration conditions
-
Probe continuous temperature:-35 to +200 °C
Information
- Bently Nevada 330851-02-000-060-10-00-00 supports non-contact observation of rotor growth relative to the turbine casing. The longer threaded body supports installations that need additional mechanical reach while retaining a short electrical lead and a separately selected extension cable.
Integral lead: 1.0 m unarmored FluidLoc cable
Matched-system output: 0.787 V/mm nominal
The 1 m probe lead combines with the appropriate 4 m or 8 m extension cable to form a 5 m or 9 m system using the matching 3300 XL 25 mm Proximitor Sensor. Disconnected probe resistance from center to outer conductor is 6.2 ± 0.5 Ω. Cable and conditioner selection must preserve the complete electrical length.
For the complete matched system, nominal sensitivity is 0.787 V/mm and the linear range is 12.7 mm. The reference conditions include a -24 Vdc supply, a 10 kΩ load, a Bently Nevada AISI 4140 steel target at least 61 mm in diameter, a 7 mm gap and component temperatures from 0 to +45 °C. Probe survivability to +200 °C does not make these reference accuracy conditions universal.
330851-02-000-060-10-00-00 Original Technical Excerpt
Original Bently Nevada pages explain the 25 mm sensing system, calibrated response, materials and applicable cable options. PDF · 6 pages.330851-02-000-060-10-00-00 Installation & Verification Guide
Apter Power field guide covering mechanical and thermal placement, connector protection and displacement verification. PDF · 5 pages.
Application scope: Differential-expansion performance depends on the collar or ramp geometry, target material and configured channel arrangement. Mechanical fit alone does not establish electrical or calibration compatibility.
Mechanical and thermal placement
Confirm the longer threaded reach and keep the Proximitor Sensor within its own lower temperature limit.Turbine collar observation
Measure differential rotor-to-casing growth with a correctly aligned and gapped matched transducer chain.Complementary DE channels
Use opposing collar faces only with the intended two-channel arrangement and corresponding monitor configuration.Controlled displacement verification
Move the probe mounting relative to the target and compare the electrical indication with a mechanical movement reference.
The 1 m probe lead combines with the appropriate 4 m or 8 m extension cable to form a 5 m or 9 m system using the matching 3300 XL 25 mm Proximitor Sensor.
Keep the high-temperature ClickLoc connector clean, finger tight and inside its connector protector.
Use the intended collar or ramp surface and verify the target material against the calibration.
Do not apply probe-body tightening torque to the electrical connector; connector maximum is 0.565 N·m.
Apply probe, cable and Proximitor Sensor temperature limits separately; avoid treating short-term exposure as continuous service.
Test the complete channel through controlled relative movement before restoring the machine protection function.
Alternative Names
Technical notes
Electrical relationship: The 1 m probe lead combines with the appropriate 4 m or 8 m extension cable to form a 5 m or 9 m system using the matching 3300 XL 25 mm Proximitor Sensor. Disconnected probe resistance from center to outer conductor is 6.2 ± 0.5 Ω. Cable and conditioner selection must preserve the complete electrical length.
Measurement boundary: For the complete matched system, nominal sensitivity is 0.787 V/mm and the linear range is 12.7 mm. The reference conditions include a -24 Vdc supply, a 10 kΩ load, a Bently Nevada AISI 4140 steel target at least 61 mm in diameter, a 7 mm gap and component temperatures from 0 to +45 °C. Probe survivability to +200 °C does not make these reference accuracy conditions universal.
Technical reference: Bently Nevada 3300 XL 25 mm Proximity Transducer System, 163236 Rev. M.
FAQ View All FAQ
-
What does the 60 mm case selection change on 330851-02-000-060-10-00-00?It changes the mechanical reach of the M30×2 probe case, with a zero unthreaded-length option. It does not change the selected 1.0 m electrical lead or the nominal matched-system scale factor.
-
How should the threaded body of 330851-02-000-060-10-00-00 be secured?Use the correct M30×2 mounting interface and the supplied locknut arrangement. The threaded-case recommended torque is 68 N·m, with a maximum rating of 163 N·m; keep these values separate from connector torque.
-
What is the normal thermal operating limit of 330851-02-000-060-10-00-00?The probe operating and storage range is -35 to +200 °C. Short-term exposure up to +250 °C is limited to less than 24 hours and is not a continuous service rating.
-
Why must the sensor temperature be checked separately from 330851-02-000-060-10-00-00?The Proximitor Sensor has a different operating range, -51 to +100 °C. A probe capable of high-temperature service does not make the remotely mounted conditioner suitable for the same ambient temperature.
-
When does a ramp target require a second transducer with 330851-02-000-060-10-00-00?A ramp measurement arrangement uses a second transducer viewing another ramp or a different rotor location to compensate for radial movement. The geometry introduces additional error but can extend the differential-expansion distance.
-
Can field wiring length limit dynamic response in a system using 330851-02-000-060-10-00-00?Yes. The typical system response is 0–2.7 kHz at +0/-3 dB with up to 305 m of field wiring. Follow the response-versus-cable-length information when selecting the sensor-to-monitor wiring.
-
What distinguishes the 00 approval selection of 330851-02-000-060-10-00-00 from an approved-area configuration?The 00 option is the no-approvals selection. Do not assume hazardous-area certification from the common family name or from approval markings on a different ordered version.
-
What must remain unchanged when 330851-02-000-060-10-00-00 is used in a redundant same-side collar arrangement?Preserve the two probes viewing the same collar side, their alignment, individual gaps and independent channel configuration. Verify both responses mechanically; physical redundancy alone does not prove correct measurement.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.