Match the complete marking
Include 16710-27 and any revision or approval marking visible on the item. Keep the exact complete reference on your enquiry and quotation.
-
Check the offered item before ordering
Request clear photos of the three-socket plug, armor and terminal lugs for 16710-27. Have your maintenance team compare the offered reference with the installed equipment and applicable Bently Nevada 16710 interconnect documentation.
Technical specifications for 16710-27
-
Manufacturer:Bently Nevada
-
Product Category:Machinery Monitoring Systems
-
Spare Part Number:16710-27
-
Weight:1.25 kg
-
Tariff Code:8537101190
-
Cable family:16710-AA armored interconnect
-
Ordered length:27 ft (approx. 8.23 m)
-
Length-code unit:Feet; 27 selects 27 ft
-
Conductor count:3 conductors
-
Conductor size:22 AWG (0.5 mm²)
-
Signal shielding:Shielded cable
-
Mechanical protection:Armored construction
-
Equipment-end termination:Three-socket plug
-
Other-end termination:Terminal lugs
-
Published length range:3–99 ft for 16710-AA family
-
Documented system context:177230 Seismic Transmitter and 330450 HTAS references
-
Connection boundary:Verify exact installed pinout and mating device
Information
- Bently Nevada 16710-27 provides an armored signal path between a compatible vibration transducer connection and an instrument terminal arrangement.
Cable: three shielded 22 AWG conductors with armor
Terminations: three-socket plug and terminal lugs
The published 16710 family construction gives separate conductors, shielding and mechanical armor. Preserve the intended signal and shield terminations rather than treating armor as a signal conductor.
Before service, isolate both ends and test continuity and unintended shorts. After reconnection, compare the received vibration signal with the approved baseline for the particular transmitter or acceleration system; the cable itself has no standalone channel scale.
-
Bently Nevada 177230 Seismic Transmitter Datasheet, 177232 Rev. U
Original manufacturer technical data; use the ordering and system limits applicable to the complete offered code. -
Apter Power 16710-27 field workflow
Three-page installation, interface, fault-isolation and acceptance guide for the offered model.
Compatibility boundary: The device wiring drawing controls plug contact and terminal-lug assignments; the cable does not set measurement scale.
-
Seismic transmitter link
The 177230 literature lists 16710-AA armored cable; check the installed transmitter connector and terminal map. -
Acceleration-system link
The 330450 system literature also identifies the 16710-AA cable family; follow that system drawing for the exact installation. -
Armored field route
Protect the three shielded conductors along machinery while supporting the keyed plug and terminal lugs. -
Maintenance replacement
Check continuity, shield termination and terminal labels before comparing the restored instrument signal with the baseline.
Disconnect the host equipment under the site procedure before working on plug contacts or terminal lugs.
Use the installed wiring drawing to verify each socket-to-lug path; never assign pins from cable appearance alone.
Terminate shielding according to the instrument design and avoid using the armor as a signal return.
Protect the 27 ft armored three-conductor assembly from crushing, hot surfaces and unsupported pull at the plug.
Before energizing, test every conductor for end-to-end continuity and unwanted contact with other conductors or armor.
After replacement, compare the instrument signal and diagnostic status against the machine baseline.
Alternative Names
Technical notes
Installation relationship: The 16710-AA family uses a three-socket plug at one end and terminal lugs at the other. Match the 27 ft cable run, connector and terminal assignment to the installed system drawing.
System boundary: Cable construction is documented for selected Bently Nevada vibration systems; a matching plug alone does not establish electrical compatibility with every sensor or monitor.
Technical reference: Bently Nevada 177230 Seismic Transmitter Datasheet, 177232 Rev. U, and 330450 High Temperature Acceleration System Datasheet, 169885 Rev. H.
FAQ View All FAQ
-
How should the three-socket end of 16710-27 be matched to the installed instrument?Compare the exact keyed plug and its three contacts with the equipment drawing before connection. Verify each conductor path to the corresponding lug; plug fit alone does not establish correct signal assignment.
-
How should the shield of 16710-27 be terminated?Follow the installed system wiring diagram for the shield and signal return. Check for unintended multiple ground points or an open shield after fitting the lugs; do not assume the armor is the signal return.
-
What continuity tests are useful before installing 16710-27?With both ends disconnected, test each conductor end to end and check for unintended conductor-to-conductor or conductor-to-armor shorts. Record the measured results with the installed terminal designations.
-
How should the armor of 16710-27 be routed around machinery?Protect the armored run from abrasion, crushing, unsupported bends and hot surfaces. Follow the equipment drawing for minimum clearance and secure the cable without loading the three-socket plug.
-
Can 16710-27 be shortened in the field without changing the installation review?Changing length or terminating a cut cable alters the ordered 27 ft assembly. Check the approved system drawing and connector-to-lug wiring before any alteration, then repeat continuity and insulation checks.
-
How can a fault in 16710-27 be distinguished from a connected sensor fault?Disconnect the cable under the site procedure, isolate the conductor and shield paths, and test the cable separately. Reconnect a verified path before condemning the sensor or receiving electronics.
-
Does 16710-27 establish the electrical rating of a complete vibration channel?No. It is an interconnect cable. Check the specific transmitter or acceleration-system document and installed device markings for supply, output, temperature and approval conditions.
-
What records should accompany replacement of 16710-27?Record the complete cable code, route, plug and lug mapping, shielding termination and continuity results. Compare the restored signal with the approved baseline for the specific monitoring system.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.