Product Describe:

BASLER ELECTRIC ICRM-7 is an inrush-current reduction module, part number 9387900103, for compatible DECS-100 and DECS-150 excitation systems. It is rated for 9 Aac and accepts 90–277 Vac or 90–300 Vdc operating power.
Get a quick price for ICRM-7
E-mail *
Mobile *
Company
Content *
Quantity *
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy

What happens after you enquire

  • 1

    Requirement review

    We review the part number, quantity and delivery requirements and ask for any missing details.
  • 2

    Quotation and availability

    We confirm the proposed item, condition, availability, price and estimated lead time in the quotation.
  • 3

    Order confirmation and dispatch

    Once the quotation and purchasing details are agreed, your contact will coordinate the order and available dispatch information.

Technical specifications for ICRM-7

  • Manufacturer:
    BASLER ELECTRIC
  • Product Category:
    General Automation
  • Spare Part Number:
    ICRM-7
  • Estimated shipping dimensions:
    10.16×5.08×6.35 cm
  • Weight:
    0.23 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Product function:
    Inrush-current reduction module
  • Compatible regulators:
    DECS-100 and DECS-150
  • AC input range:
    90–277 Vac
  • DC input range:
    90–300 Vdc
  • Frequency range:
    DC or 50–420 Hz
  • Current rating:
    9 Aac
  • Power dissipation:
    25 W
  • Operating temperature:
    -25 to 70 °C
  • Storage temperature:
    -40 to 70 °C
  • Mounting:
    Vertical; ventilation holes at top and bottom
  • Cooldown:
    Wait at least 5 minutes after operating power is removed
  • Troubleshooting resistance:
    Approximately 2 ohms across each IN/OUT pair

Information

Overview Manuals Common Applications Product Precautions
The ICRM-7 limits input inrush presented to compatible DECS digital excitation-control hardware when the source impedance is low or switched.
  • Compatible with DECS-100 and DECS-150
  • 90–277 Vac or 90–300 Vdc input
  • 9 Aac current rating
  • Vertical mounting with ventilation openings clear

The ICRM-7 is inserted between the operating-power source and the compatible DECS voltage regulator to reduce startup inrush. Its three IN/OUT paths are connected to the regulator output terminals identified in the Basler manual, and the enclosure must remain vertically mounted for airflow. The module contains no user-serviceable parts and is replaced if troubleshooting confirms failure.

Important Notice: Confirm part number 9387900103, source voltage, DECS model, wiring and vertical mounting orientation before installation.

BASLER ELECTRIC ICRM-7 Manuals & Downloads
BASLER ELECTRIC ICRM-7 Official Manufacturer Manual (PDF)BASLER ELECTRIC ICRM-7 Installation & Commissioning Guide (PDF)

The first document reproduces applicable official manufacturer pages unchanged; the second provides a separate evidence-led installation and commissioning workflow.

DECS-100 excitation
Inrush-current reduction ahead of a compatible DECS-100 operating-power input.
DECS-150 excitation
Controlled startup of a compatible DECS-150 supplied from a low-impedance or switched source.
Generator retrofits
Documented upgrades where the approved excitation design specifies an ICRM-7 between source and regulator.
Maintenance replacement
Like-for-like replacement after resistance checks identify a failed non-serviceable ICRM module.
Read the applicable BASLER ELECTRIC instructions before work. Verify ICRM-7 and the installed system configuration before isolation or replacement.
1
Record the ICRM-7 marking and Basler part number 9387900103 before work.
2
De-energize every connected source and wait at least five minutes before handling.
3
Verify that the operating-power source is within the published AC or DC range.
4
Map every IN and OUT conductor to the approved DECS wiring diagram before removal.
5
Mount the ICRM-7 vertically with its upper and lower ventilation openings clear.
6
Treat the enclosure as hot during operation and provide the required clearance.
7
Check each IN/OUT path and replace the module if fault testing confirms failure.
8
Energize under control and record stable regulator startup and acceptance results.

Technical notes

The ICRM-7 is inserted between the operating-power source and the compatible DECS voltage regulator to reduce startup inrush. Its three IN/OUT paths are connected to the regulator output terminals identified in the Basler manual, and the enclosure must remain vertically mounted for airflow. The module contains no user-serviceable parts and is replaced if troubleshooting confirms failure.

FAQ View All FAQ

  • What does the BASLER ELECTRIC ICRM-7 do?
    The BASLER ELECTRIC ICRM-7 reduces the startup inrush current presented to a compatible DECS voltage regulator.
  • Which excitation controllers are compatible with ICRM-7?
    The ICRM-7 is compatible with the DECS-100 and DECS-150 digital excitation control systems.
  • What input ranges can part 9387900103 accept?
    Part 9387900103 accepts 90–277 Vac or 90–300 Vdc at DC or 50–420 Hz.
  • How much current can the ICRM-7 carry?
    The ICRM-7 has a published current rating of 9 Aac.
  • Why must ICRM-7 be mounted vertically?
    The ICRM-7 must be mounted vertically so air can pass through the ventilation openings at the top and bottom of its enclosure.
  • How long should technicians wait after removing ICRM-7 operating power?
    Technicians must wait at least five minutes after operating power is removed before handling or testing the ICRM-7.
  • What resistance indicates a normal ICRM-7 current path?
    A normal ICRM-7 current path measures approximately 2 ohms across each corresponding IN and OUT terminal pair.
  • Can the ICRM-7 be repaired in the field?
    The ICRM-7 contains no user-serviceable parts, so a module that fails the approved checks must be replaced.
Related reading

Related cases and sourcing guidance

View all case studies
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.