Match the complete marking
Retain SNAT7261QCP in full and compare the actual converter and assembly identities.
-
Check the offered item before ordering
Review label and connector photos, matching-card scope and the installed-drive configuration.
Technical specifications for SNAT7261QCP
-
Manufacturer:ABB
-
Product Category:General Automation
-
Spare Part Number:SNAT7261QCP
-
Weight:0.88 kg
-
Tariff Code:8537101190
-
Base-design designation:SNAT 7261 INT
-
Base-design platform:SAMI GS ACS 502-506
-
Base-design component position:A3 main circuit interface
-
Base-design supply function:Power-supply circuits
-
Base-design switching interface:Transistor gate-trigger circuits
-
Base-design voltage measurement:DC-link voltage measurement circuits
-
Base-design current measurement:Motor-current measurement circuits
-
Matching-card relationship:Separate A7 card; power-range programming
-
Control-interface relationship:Separate from SNAT 7600/7640 control interface
-
Revision identity:Retain the complete QCP marking
Information
- ABB SNAT7261QCP belongs to the SNAT 7261 main-circuit interface design used inside legacy SAMI GS converters. Its board revision and matching-card arrangement are part of the installed-drive identity.
Base-design position: A3 in the converter module
Revision identity: Complete SNAT7261QCP marking
The separate A7 matching card sits on the SNAT 7261 interface and stores the power-range programming information for the particular converter hardware. The SAMI GS matching-card designation identifies the applicable power and voltage class. Consequently, the main-circuit interface and matching-card configuration must remain associated with the installed converter rather than being selected from board appearance alone.
SAMI GS card identification separates the part-list revision, printed-circuit revision and schematic revision within the three-letter suffix. Retain the full SNAT7261QCP marking together with its serial and assembly information when identifying the supplied board. The base-design functions above do not assign a converter power rating, operating-voltage rating or approval to the QCP revision, and the 600 V base configuration uses a different main-circuit interface design.
-
Official SAMI GS Interface-Design Reference Excerpt
Original manufacturer excerpt - PDF, 4 pages. SNAT 7261 base-design role, converter arrangement and identification. -
ABB SNAT7261QCP installation guide
Prepared by Apter Power - PDF, 5 pages. Identity, interfaces, installation hold points, commissioning and service checks.
Platform applications: These are legacy SAMI GS converter functions. Confirm the actual drive configuration and revision arrangement before selecting a replacement card.
-
Converter interface restoration
Restore the documented A3 main-circuit interface function in the appropriate installed SAMI GS converter. Compare the full board marking and drive records before replacement. -
Gate-trigger circuit service
The SNAT 7261 base design includes transistor gate-trigger circuits. Investigate the complete inverter path under the applicable isolated service procedure. -
DC-link measurement diagnosis
Use the converter diagnostic procedure when checking the base-design DC-voltage measurement path. Do not treat the board as an independent user-calibrated voltage transmitter. -
Motor-current feedback service
The base design includes motor-current measurement circuits and works with the converter current transducers. Check the whole feedback path when investigating a measurement fault.
Compare SNAT7261QCP with the actual installed label and assembly records. Do not reduce the selection to SNAT 7261 or infer equivalence from appearance.
Identify the separate A7 power-range programming card and preserve its relationship to the installed converter hardware.
Use the ABB converter safety procedure and verify the DC-link condition before touching boards. Account for external control supplies and unintended motor motion.
Do not interchange the A3 main-circuit interface with the separate control-interface, motor-control or input-protection card.
Confirm the converter type and nameplate. The SAMI GS manual identifies a different main-interface type for 600 V units; do not assign that rating to QCP by inference.
Recheck connections, gate-trigger and measurement behavior through the installed-drive commissioning procedure before releasing the machine.
Alternative Names
Technical notes
Base-design relationship: SNAT 7261 INT provides the converter main-circuit interface functions. Keep the complete SNAT7261QCP identity and the separate A7 matching-card arrangement with the drive record.
Service boundary: Electrical ratings and interchangeability follow the actual converter and approved assembly. Isolate and verify stored energy before board handling.
Technical reference: ABB SAMI GS Frequency Converters ACS 502-506 User's Manual, EN 58424714 Rev. B; ACS 502 Installation and Start-up Manual.
FAQ View All FAQ
-
What role does the SNAT 7261 base design give SNAT7261QCP?The documented SNAT 7261 INT is the A3 main-circuit interface card in a SAMI GS converter. The complete QCP marking remains part of the offered board identity and must be compared with the installed assembly.
-
Which circuits are described for the base design of SNAT7261QCP?ABB describes power-supply, transistor gate-trigger, DC-voltage measurement and motor-current measurement circuits on SNAT 7261 INT. These are base-design functions, rather than independently established QCP electrical ratings.
-
Is SNAT7261QCP the same function as the SNAT 7600/7640 control interface?No. The main-circuit interface is a converter-module function. The SNAT 7600/7640 control interface is a separate card associated with the display, keypad and control connections.
-
Why should the A7 matching card be checked when replacing SNAT7261QCP?The separate A7 matching card carries power-range programming information for the converter hardware. Retain the installed matching-card arrangement and confirm its identity during main-board service.
-
Can a 600 V rating be assumed from the appearance of SNAT7261QCP?No. The SAMI GS manual distinguishes SNAT 7261 INT from SNAT 7266 INT used for 600 V units. Confirm the actual drive voltage and approved board arrangement; appearance and the QCP suffix do not establish a voltage rating.
-
Does SNAT7261QCP alone perform motor-current sensing?The SNAT 7261 design includes motor-current measurement circuits, while the converter also uses separate current transducers. Fault diagnosis must include the transducers, wiring and receiving circuits.
-
How should the marking on SNAT7261QCP be retained for service?Record the complete board type, revision marking, serial or assembly information and matching-card identity with the converter record. Keep the QCP suffix intact when comparing a replacement.
-
What must be verified before touching SNAT7261QCP inside a converter?Follow the applicable ABB isolation procedure, verify the DC-link energy condition and account for external control supplies. Board removal is a converter service operation and should be performed by qualified personnel under the site procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
You May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.