Match the complete marking
Include EA1*A and every revision or approval marking visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and interface photos. Have your maintenance team compare the offered EA1*A reference with the installed equipment and applicable Yokogawa documentation.
Technical specifications for EA1*A
-
Manufacturer:Yokogawa
-
Product Category:DCS Systems
-
Spare Part Number:EA1*A
-
Weight:0.01 kg
-
Tariff Code:8537101190
-
Card function:Two-wire transmitter input
-
Style code:*A as supplied
-
Input signal:4 to 20 mA DC
-
Input resistance:250 Ω
-
Allowable input current:40 mA DC
-
Transmitter supply:25 to 28 V DC
-
Transmitter current limit:25 to 35 mA
-
Output signal:1 to 5 V DC, two outputs
-
Output resistance:1 Ω maximum
-
Minimum output load:2 kΩ
-
Power supply:24 V DC ±10 %
-
Maximum current consumption:80 mA
-
Accuracy:Within ±0.1 % of span
-
Isolation resistance:100 MΩ at 500 V DC
-
Withstand voltage:1500 V AC input-to-output/power for 1 minute
-
Ambient range:0 to 50 °C; 5 to 90 % RH non-condensing
Information
- The complete EA1*A identity establishes the offered hardware. Confirm the installed system, revision and field interfaces before approving the replacement.
Isolation role: Separates input, outputs and power according to the card specification.
Calibration focus: Verify loop voltage margin, zero, span and both output paths.
Loop design must include the transmitter minimum operating voltage, cable drop and the card input resistance. The two output paths should be treated as separate acceptance points even though they originate from one input.
Replacement requires the exact style marking, special-nest position, M4 terminal wiring and cable connector to be preserved. Commissioning should record input current, transmitter voltage and both output voltages at low, mid and high points.
-
Yokogawa EA1*A technical reference
Apter Power reference with verified manufacturer data and exact-model applicability. -
Yokogawa EA1*A engineering guide
Apter Power installation, configuration, diagnostic and acceptance guidance.
Platform applications: The uses below depend on the installed controller configuration and approved system design.
-
Two-wire transmitter interface
Power and acquire a 4 to 20 mA field transmitter. -
Signal duplication
Provide two 1 to 5 V outputs from one isolated transmitter input. -
Legacy signal conditioning
Maintain an approved CENTUM signal-conditioner nest arrangement. -
Loop diagnostics
Separate transmitter, cable, card supply and output-channel faults with measured values.
Include transmitter minimum voltage, cable drop and the 250 Ω card input.
Confirm the A/B/C terminal arrangement from the applicable Yokogawa drawing.
Measure card supply inside the ±10 % range before calibrating the loop.
Measure both 1 to 5 V outputs at several input currents.
Check backboard and special-cable contacts for damage or contamination.
Document low, mid and high input/output results before release.
Alternative Names
Technical notes
Installation relationship: Use the exact model marking and manufacturer wiring or installation information for the delivered hardware.
System boundary: Verify host equipment, companion interfaces, field wiring and configuration before energizing.
Technical reference: Yokogawa GS 33J60H80-01EN Signal Conditioners.
FAQ View All FAQ
-
How is transmitter voltage margin calculated for EA1*A?Subtract cable drop and the 5 V drop across the 250 Ω input at 20 mA from the available transmitter supply, then compare the remainder with the transmitter minimum voltage.
-
How should both outputs of EA1*A be calibrated?Inject traceable 4, 12 and 20 mA values and measure both 1 to 5 V outputs independently, recording any deviation.
-
What indicates a field-loop open circuit on EA1*A?Check transmitter supply, input current, terminal voltage and both outputs; separate an open field circuit from a card or backboard supply problem.
-
How should polarity be verified on EA1*A?Use the Yokogawa terminal drawing for the exact nest and trace field positive/negative conductors before energizing the transmitter.
-
What insulation test is appropriate for EA1*A?Remove or isolate connected electronics and use only the manufacturer- and site-approved test voltage; do not megger through live cards or transmitters.
-
How can output disagreement on EA1*A be diagnosed?Apply one stable input current and compare both outputs at the card and receiving devices to distinguish card error from downstream load or wiring.
-
What should be recorded before replacing EA1*A?Capture style marking, nest position, field terminals, special-cable identity, 24 V supply and low/mid/high loop values.
-
What acceptance result closes work on EA1*A?Both outputs must track the verified input within the approved accuracy, the transmitter must retain voltage margin and the control indications must return to the recorded state.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.