Match the complete marking
Include 6EP1334-1SL12 and any revision or assembly number visible on the item. Keep the exact reference on your enquiry and quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 6EP1334-1SL12 with the installed equipment and applicable Siemens documentation.
Technical specifications for 6EP1334-1SL12
-
Manufacturer:Siemens
-
Product Category:General Automation
-
Spare Part Number:6EP1334-1SL12
-
Weight:1.12 kg
-
Tariff Code:8537101190
-
Product series:SITOP
-
Product type:SITOP 24 V Power Supply
-
Nominal output:24 V DC
-
Rated output current:10 A
-
Selectable input:120/230 V AC, 50/60 Hz
-
Output tolerance:±3%
-
Output ripple:<150 mV
-
Operating temperature:0 to +60 °C
-
Protection:IP20
Information
- Siemens 6EP1334-1SL12 is a SITOP industrial power supply with a regulated 24 V DC, 10 A output.
Installation: DIN-rail mounting in a suitable control cabinet
Load planning: Review startup current and protection coordination
The supply operates at 50/60 Hz and provides a 24 V output with a stated ±3% tolerance. Siemens specifies less than 150 mV output ripple, automatic restart after a short circuit, DIN-rail mounting and IP20 protection. The 0 to +60 °C operating range and required installation clearances must be considered with the enclosure's thermal design.
Use the unit in cabinet power distribution where the total continuous load, startup current and protection coordination suit a 10 A SITOP supply. During replacement, compare the existing input selector position, output distribution, grounding, breaker and load current. Verify the actual output voltage and connected control functions after energization.
-
Siemens 6EP1334-1SL12 technical reference
Apter Power technical reference - PDF, 2 pages. Product identity, verified characteristics, system integration and selection checks. -
Siemens 6EP1334-1SL12 installation guide
Apter Power installation verification guide - PDF, 2 pages. Identity, host configuration, inspection and functional release checks.
Compatibility scope: The site input selection, output current budget, protective devices and cabinet installation must suit the connected load. Check polarity and distribution when replacing an existing supply.
-
PLC cabinet supply
Feed approved 24 V DC controller and interface equipment from the regulated rail. The total continuous load must stay within the supply rating. -
Distributed I/O power
Provide a compatible 24 V rail for remote I/O electronics and field interfaces. Distribution and protection remain part of the cabinet design. -
Machine auxiliary circuits
Supply approved sensors, relays or control auxiliaries that require 24 V DC. The connected devices determine the circuit-level protection. -
Existing SITOP replacement
Restore a matching 24 V, 10 A supply where the input selector and cabinet wiring correspond to this execution. Verify output behavior under the installed load.
Check the exact 6EP1334-1SL12 marking, input terminals and output rating. Record the existing cabinet connection plan.
Disconnect the AC feeder and confirm absence of voltage before touching terminals. Observe the site lockout procedure for connected equipment.
Set the 120/230 V AC selector for the actual supply and verify the protective device. Incorrect selection can damage the power supply.
Confirm 24 V DC polarity, terminal tightness and load distribution. Keep the total connected load within the 10 A output rating.
Maintain the installation clearances and ventilation required for the SITOP unit. Avoid obstructing the cooling path or stressing terminals.
Measure the output voltage after energizing and check stability with the normal load connected. Confirm the affected PLC and I/O equipment starts correctly.
Alternative Names
Technical notes
System relationship: The supply operates at 50/60 Hz and provides a 24 V output with a stated ±3% tolerance. Siemens specifies less than 150 mV output ripple, automatic restart after a short circuit, DIN-rail mounting and IP20 protection. The 0 to +60 °C operating range and required installation clearances must be considered with the enclosure's thermal design.
Applicability: The characteristics above describe the identified SITOP execution of 6EP1334-1SL12. Optional functions, connected devices and installed revisions must be checked against the complete marking and approved project configuration.
Technical reference: Siemens SITOP operating instructions, 6EP133x-1SL1x series, exact 6EP1334-1SL12 rating.
FAQ View All FAQ
-
What is the product type of Siemens 6EP1334-1SL12?Siemens 6EP1334-1SL12 is a SITOP primary switched-mode, rail-mounted power supply. It converts a selected 120 or 230 V single-phase AC input to an isolated 24 V DC output for control-system loads and includes short-circuit and open-circuit protection.
-
What is the nominal output of Siemens 6EP1334-1SL12?The rated output is 24 V DC at the L+ and M terminals. Siemens specifies a floating output and a voltage tolerance of ±3%; the connected load and distribution should be designed for a regulated 24 V supply.
-
What is the rated output current of Siemens 6EP1334-1SL12?The specified DC output range is 0 to 10 A, equivalent to 240 W at the nominal 24 V output. The supply uses current limitation and automatic restart after an output short circuit; check the connected load before returning the system to service.
-
What is the selectable input of Siemens 6EP1334-1SL12?It is intended for 120 or 230 V AC, 50/60 Hz single-phase input. The manual gives 85–132 V for the 120 V selector position and 170–264 V for the 230 V position; set the selector to the actual supply before energizing.
-
What is the output tolerance of Siemens 6EP1334-1SL12?Siemens specifies 24 V DC ±3% at the output. The manual also lists less than 150 mV peak-to-peak ripple and less than 240 mV peak-to-peak spikes, which are separate measures from the nominal voltage tolerance.
-
How should Siemens 6EP1334-1SL12 be mounted for cooling?Mount the unit vertically on the specified DIN EN 50022-35x15 rail with its input and output terminals at the bottom. Siemens calls for at least 40 mm of free space above and below the supply for natural-convection cooling.
-
What should be checked before replacing Siemens 6EP1334-1SL12?Record the complete order number, input selector position, upstream protective and isolating devices, and the existing L1/N/PE and L+/M wiring. Confirm that the replacement's 24 V, 10 A rating and mounting clearances suit the connected load and cabinet.
-
How is Siemens 6EP1334-1SL12 checked after installation?After confirming the AC selector setting and terminal wiring, measure the DC voltage across L+ and M with the intended load connected. Verify that the output remains within the specified 24 V ±3% range and that total load current does not exceed 10 A.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.