140DDO36400

Discrete Output Module
In Stock
Ships by Sunday, October 18
Fast Shipping Available

Product Describe:

Schneider Electric 140DDO36400 is a high-density Modicon Quantum 96-point 24 V DC sink output module organized as six groups of sixteen channels.

Ask our team:

Get a quick price for: 140DDO36400
Quantity*
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Apterpower please read our privacy policy.

Technical specifications for 140DDO36400

Technical specifications for 140DDO36400

  • Manufacturer:
    Schneider Electric
  • Product Category:
    PLC Systems
  • Spare Part Number:
    140DDO36400
  • Estimated shipping dimensions:
    4.1×10.2×25cm
  • Weight:
    0.44 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    France
  • Output count:
    96
  • Signal:
    24 V DC
  • Logic:
    Negative / sink
  • Grouping:
    6 groups of 16
  • I/O mapping:
    6 output words
  • Supply range:
    19.2 to 30 V DC
  • Point current:
    0.5 A maximum
  • Group current:
    3.2 A maximum
  • Module current:
    19.2 A maximum
  • Surge:
    2 A
  • Response:
    0.1 ms maximum
  • Protection:
    Short-circuit and overload

Information

Information

Overview Manuals Common Applications Product Precautions
Schneider Electric 140DDO36400 is a high-density Modicon Quantum 96-point 24 V DC sink output module organized as six groups of sixteen channels.
  • Output count: 96
  • Signal: 24 V DC
  • Logic: Negative / sink
  • Grouping: 6 groups of 16

140DDO36400 operates only with the documented system configuration and connected hardware.

Important Notice: Keep the six group commons, sinking polarity and cumulative current calculation with the service record.

Schneider Electric 140DDO36400 Manuals & Downloads
140DDO36400 Technical Reference (PDF)140DDO36400 Manufacturer Datasheet (PDF)

The first document presents model-specific technical and service content. The second preserves the unchanged manufacturer product data.

Dense DC output banks
Controls up to ninety-six documented 24 V DC sink loads.
Six-group distribution
Separates channels into six sixteen-point current domains.
Protected switching
Uses the module short-circuit and overload protection within stated limits.
Exact high-density renewal
Preserves the six-word output map and negative-logic identity.
Read the applicable Schneider Electric instructions before work. Verify 140DDO36400, the installed system and every configured interface before isolation, wiring or commissioning.
1
Confirm the complete Schneider Electric 140DDO36400 identity and installed position before work.
2
Place the connected machine or process in the approved maintenance state.
3
Isolate every documented supply and field circuit before disconnection.
4
Record terminal, cable, shield, network and companion-hardware identities.
5
Retain output count and signal requirements from the installed design.
6
Protect connectors, electronics and keyed interfaces from contamination or damage.
7
Restore power in the approved sequence and review diagnostics.
8
Prove the intended 96-channel 24 v dc negative-logic discrete output module response and retain the acceptance record.

Technical notes

Technical notes

Keep the six group commons, sinking polarity and cumulative current calculation with the service record.

FAQS

  • How many outputs are available on 140DDO36400?
    The module provides ninety-six solid-state 24 V DC outputs.
  • What logic orientation applies?
    It is a negative-logic sinking output module; field polarity cannot be reversed by assumption.
  • How is current limited?
    Observe 0.5 A per point, 3.2 A per group and 19.2 A total, plus the surge condition.
  • How many controller words are used?
    The 96 channels occupy six output words.
  • What does built-in protection not replace?
    It does not replace the documented external field-circuit protection and conductor sizing.
  • What should commissioning include?
    Test each permitted output group, review diagnostics and verify no overload or short-circuit indication remains.
Trusted by 5,000+ plants worldwide | Backed by our vast inventory of top-tier control parts, modules and cards, fast shipments are dispatched to cover your urgent needs. ABOUT US >>
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer`s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Product Browsing History

We’re Here When You Need Us

From product insights to customer service needs, our experienced service team will focus on getting you what you need quickly

Enquire

Complete our online form.

Call Us

Speak to one of our team.

Live Chat

Send us a message.