Technical specifications for IC698PSA100

  • Manufacturer:
    General Electric
  • Product Category:
    PLC Systems
  • Estimated shipping dimensions:
    6.4x19x29.2cm
  • Weight:
    1.92 kg
  • Tariff Code:
    8537101190
  • Counliy of origin:
    USA
  • Product family:
    PACSystems RX7i
  • Module function:
    Rack power supply
  • Total output:
    100 W
  • AC input:
    85 to 264 VAC, 47 to 63 Hz
  • DC input:
    100 to 150 VDC
  • +5 V output:
    20 A maximum
  • +12 V output:
    2 A maximum
  • -12 V output:
    1 A maximum

Information

Overview Manuals Common Applications Product Precautions
GE IC698PSA100 is the convection-cooled supply used when an RX7i main rack requires up to 100 W without a forced-air fan tray. The module plugs into the leftmost rack position and reports loss of acceptable input or output through the VME AC_FAIL# interface.
  • 100 W total output from 0 to 60 °C
  • 85–264 VAC or 100–150 VDC input
  • +5 V, +12 V and -12 V backplane outputs
  • Overcurrent, overvoltage and overtemperature protection

The engineered signal path is AC or DC field source → IC698PSA100 in RX7i slot 0 → Protected three-rail DC output → PACSystems RX7i backplane modules. Commission each boundary against the controlled project record.

Important Notice: Isolate the incoming source; the front ON/OFF switch disables outputs but does not remove hazardous input voltage.

GE IC698PSA100 Manuals & Downloads
GE IC698PSA100 Technical Reference (PDF)GE IC698PSA100 Installation & Commissioning Guide (PDF)

The Technical Reference is a model-specific official GE manual excerpt. The separate Installation & Commissioning Guide organizes field preparation, verification and acceptance for GE IC698PSA100.

RX7i main-rack power
Feeds PACSystems RX7i CPUs and option modules within the 100 W budget.
Wide-range AC cabinets
Accepts common 120/240 VAC industrial feeds without input-range selection.
DC-fed control systems
Operates from the documented 100–150 VDC source range.
Convection-cooled racks
Delivers full rated output through 60 °C without a fan tray.
Apply these controls specifically to GE IC698PSA100 before isolation, replacement, reconnection, energization and final release.
1
Isolate the incoming source; the front ON/OFF switch disables outputs but does not remove hazardous input voltage.
2
Install IC698PSA100 only in slot 0 of an RX7i main rack and secure the mounting screws.
3
Calculate the combined +5 V, +12 V and -12 V demand before energizing the rack.
4
Use copper conductors with the documented temperature rating and tighten terminals to the specified torque.
5
Bond the supply ground terminal to the rack ground and protective earth with the recommended conductor.
6
Do not insert or remove the supply or adjacent modules while field or rack power is present.
7
Investigate OUTPUT OK loss before cycling power; an overload on one rail can collapse other rails.
8
After installation, verify FIELD OK, OUTPUT OK and the controller response to the AC_FAIL# warning path.

Technical notes

GE IC698PSA100 supplies the PACSystems RX7i backplane with regulated +5 V, +12 V and -12 V outputs from a wide-range AC or DC source.

FAQ View All FAQ

  • What input sources can GE IC698PSA100 accept?
    It accepts 85–264 VAC at 47–63 Hz or 100–150 VDC through the front input terminals.
  • What is the total output rating of GE IC698PSA100?
    The supply delivers up to 100 W from 0 to 60 °C without forced-air cooling.
  • Which DC rails are provided by GE IC698PSA100?
    The RX7i backplane receives +5 V at up to 20 A, +12 V at up to 2 A and -12 V at up to 1 A.
  • Which rack position is required for GE IC698PSA100?
    Install it in slot 0, the leftmost power-supply position of the RX7i main rack.
  • Does the GE IC698PSA100 front switch isolate the input?
    No. It enables or disables the output channels; hazardous input voltage can remain inside the module.
  • How does GE IC698PSA100 signal an imminent loss of power?
    It asserts the VME AC_FAIL# signal at least 5 ms before the outputs fall below their specified limits.
  • How does GE IC698PSA100 recover from an output short circuit?
    Electronic current limiting collapses the affected rail and normal operation resumes after the overload is removed.
  • What should be checked after installing GE IC698PSA100?
    Confirm grounding, conductor termination, output-load calculation, FIELD OK, OUTPUT OK and stable controller operation.
Related reading

Related cases and sourcing guidance

View all case studies
Manufacturers

Product Browsing History

Revisit the products you recently viewed on Apter Power.
SPEAK TO OUR TEAM
Let’s find the right solution for you.
Send us the part number, quantity and delivery destination. Our team will help confirm availability and lead time.
  • Whatsapp: +86 18030235313

    Send us a message.
  • sales13@apterpower.com

    Complete our online form.
  • +86 18030235313

    Speak to our team in your native language.