Match the complete marking
Include 750-P5-G5-S5-HI-A20-R-E and every visible revision or serial identity in your enquiry. Keep the same complete reference on the quotation.
-
Check the offered item before ordering
Request available label and connector photos. Have your maintenance team compare the offered 750-P5-G5-S5-HI-A20-R-E with the installed equipment and applicable GE documentation.
Technical specifications for 750-P5-G5-S5-HI-A20-R-E
-
Manufacturer:General Electric
-
Product Category:General Automation
-
Spare Part Number:750-P5-G5-S5-HI-A20-R-E
-
Weight:4.96 kg
-
Tariff Code:8537101190
-
Relay family:750 feeder management
-
Phase CT inputs:P5: 5 A
-
Zero-sequence CT input:G5: 5 A
-
Sensitive-ground CT input:S5: 5 A
-
Control supply:HI: 88–300 V DC or 70–265 V AC, 48–62 Hz
-
Analog outputs:A20: eight 4–20 mA outputs
-
Breaker-closed indicator:R: red LED
-
Front display:E: enhanced LCD
-
Protection role:Feeder protection and monitoring
-
Setup software:EnerVista 750/760 Setup; version matched to firmware
-
Firmware check:Read actual revision before importing settings
Information
- GE Multilin 750-P5-G5-S5-HI-A20-R-E brings phase, zero-sequence and sensitive-ground measurements into a 750 feeder-protection scheme, with an enhanced front-panel interface for local review.
Output review: Prove each wired analog destination against the channel scaling
Handover record: Capture firmware, event settings and the complete relay marking
The HI supply option covers 88–300 V DC or 70–265 V AC at 48–62 Hz. The R option provides a red breaker-closed indicator, while the E execution uses the enhanced LCD and its revised navigation. Record the installed firmware before transferring settings between units.
Its A20 group provides eight 4–20 mA analog outputs. Loop scaling, receiver input and break detection must match the actual analog channel settings. Feeder trip, alarm and metering behavior follows the configured relay logic and actual wiring; exercise the protection functions under an approved test plan before returning the circuit to service.
-
General Electric 750-P5-G5-S5-HI-A20-R-E technical reference
Original manufacturer excerpt - PDF, 5 pages. Feeder Management Relay identity, interfaces and engineering scope. -
General Electric 750-P5-G5-S5-HI-A20-R-E installation guide
Prepared by Apter Power - PDF, 5 pages. Preparation, installation, testing and handover for 750-P5-G5-S5-HI-A20-R-E.
Interface boundary: This relay monitors and protects the feeder; its eight 4–20 mA analog outputs serve configured downstream instruments, while 760 autoreclose functions are outside this 750 identity.
-
Phase-current protection
Apply the three 5 A phase inputs to the feeder CT set, then commission pickup, delay and restraint settings against the protection study. -
Ground-fault supervision
Use the separate 5 A zero-sequence and sensitive-ground inputs only with the corresponding CT circuits and approved grounding scheme. -
Analog plant reporting
Map the eight 4–20 mA channels to meters, recorders or control inputs with documented engineering units and receiver ranges. Use the 4–20 mA scaling expected by the installed analog receiving system, and verify the low-current end of each loop. -
Local operating review
Use the enhanced LCD and breaker-closed indicator for on-site status review, while proving the breaker indication against the actual auxiliary contact wiring.
Follow the site CT isolation and shorting procedure before opening current circuits. Confirm phase, zero-sequence and sensitive-ground inputs are landed on the intended terminals.
Verify the available control voltage and frequency fall inside the HI option range before energizing the relay; do not infer the supply from another 750 relay in the cubicle.
Export settings and record firmware, CT ratios, breaker logic, protection elements and event settings before replacement. Review differences before importing an archived file.
Test every assigned 4–20 mA output at meaningful low, mid and high indications, checking receiver scaling, polarity and channel mapping.
Place the breaker in the approved maintenance state; test alarm and trip outputs through the site protection procedure before release.
Compare the red breaker-closed LED and enhanced-display status with actual breaker contacts and control-system indications after commissioning.
Alternative Names
Technical notes
Installation relationship: Connect the P5, G5 and S5 current inputs to their corresponding 5 A CT circuits. Match the HI control supply to the available source and validate the trip/close wiring before energizing.
Analog interface: The A20 option supplies eight 4–20 mA analog outputs. Configure each receiver for the selected channel range and verify end-to-end scaling against the feeder engineering record.
Technical reference: GE Multilin 750/760 Firmware 6.00 Release Details, GER-4012, and 750/760 Feeder Management Relay brochure. The order code defines the offered hardware options; settings and operational behavior depend on installed firmware and configuration.
FAQ View All FAQ
-
How should the three CT circuits be mapped and proven when commissioning 750-P5-G5-S5-HI-A20-R-E?Map the phase, zero-sequence and sensitive-ground circuits separately to their matching relay inputs. Compare each CT ratio, polarity and secondary wiring with the feeder drawing, then inject or otherwise prove each measurement path before enabling protection.
-
What must be checked before applying auxiliary power to 750-P5-G5-S5-HI-A20-R-E?Measure the panel's actual AC or DC auxiliary source and verify that it falls within the HI option range of 88–300 V DC or 70–265 V AC at 48–62 Hz. Check upstream protection and terminal polarity or phase connections before energizing; a different 750 supply option is not a safe reference.
-
How should the 4–20 mA analog channels of 750-P5-G5-S5-HI-A20-R-E be mapped to plant receivers?Confirm the configured quantity and engineering scale for each of the eight 4–20 mA channels, then compare the wiring and receiving-device input range channel by channel. Prove low, intermediate and high indications at the destination; an unassigned channel or mismatched input range can give a plausible but incorrect reading.
-
Does 750-P5-G5-S5-HI-A20-R-E provide 760 autoreclose functions?No 760 identity is present in this order code. Plan autoreclose only when the installed protection design provides it through a separately identified device or scheme.
-
How can the breaker-closed indication on 750-P5-G5-S5-HI-A20-R-E be proved against the field circuit?Operate the breaker in an approved test state and compare the red indicator with the actual auxiliary contact, relay input logic and control-system indication. The indicator color alone does not establish contact polarity or prove a correctly wired status circuit.
-
How should settings be moved into 750-P5-G5-S5-HI-A20-R-E?Record the original relay firmware and export its setting file. Compare CT ratios, element enables, time curves, I/O mappings and software compatibility before loading, then test the affected protection functions.
-
What should be verified at the front panel when replacing 750-P5-G5-S5-HI-A20-R-E?Confirm that the installed unit has the E enhanced display and that its navigation, displayed measurements, alarms and breaker status agree with the commissioned relay configuration. The display is an identity and operating check; the full order code and fitted firmware still govern replacement review.
-
Which acceptance tests are essential for 750-P5-G5-S5-HI-A20-R-E?Verify the three CT input groups, HI supply, breaker indication, assigned protection trips and all used 4–20 mA analog outputs. Record as-found and as-left values under the site's protection-test procedure.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-
We can't find any results for “”.
Related cases and sourcing guidance
View all case studiesYou May Also Like
Product Browsing History
-
Whatsapp: +86 18030235313
Send us a message. -
sales13@apterpower.com
Complete our online form. -
+86 18030235313
Speak to our team in your native language.