330909-00-80-10-02-00 is installed with 3300 XL NSv Proximitor Sensor, matched NSv extension cable when required, small AISI 4140 steel target, compatible Bently Nevada monitor channel.
Engineered applications include Small-shaft radial vibration, Confined axial-position sensing, Process-compressor proximity loops, NSv transducer-system renewal.
Important Notice: Confirm the long-case mounting clearance and 3/8-24 thread engagement, support the armored lead, maintain required probe-tip separation and verify the one-metre NSv response over the intended gap range.
The first document presents model-specific technical identity and engineering data. The second provides a separate installation, connection and commissioning workflow.
330909-00-80-10-02-00 supports this documented 3300 XL NSv Proximity Transducer System engineering task.
330909-00-80-10-02-00 supports this documented 3300 XL NSv Proximity Transducer System engineering task.
330909-00-80-10-02-00 supports this documented 3300 XL NSv Proximity Transducer System engineering task.
330909-00-80-10-02-00 supports this documented 3300 XL NSv Proximity Transducer System engineering task.
Verify the complete 330909-00-80-10-02-00 marking and its documented 3300 XL NSv Proximity Transducer System position before field work.
Place the monitored machine and associated protection channel in the approved maintenance state before disconnecting 3300 NSv 3/8-24 armored proximity probe.
Protect every exposed connector and cable end from oil, moisture, dirt and impact while 330909-00-80-10-02-00 is open.
Record probe, extension-cable and Proximitor Sensor identities so the calibrated system length is preserved.
Route 330909-00-80-10-02-00 without sharp bends, crushing, abrasion or tensile loading at either coaxial termination.
Clean and finger-tighten each ClickLoc connection; never transfer connector torque or wiring practice from a different transducer family.
Set the static gap only after mechanical mounting and the complete matched loop have been confirmed.
Verify polarity, dynamic response and alarm action before returning the machinery-protection channel to service.