Technical specifications for 1756-L55M13
-
Manufacturer:Allen-Bradley
-
Product Category:PLC Systems
-
Spare Part Number:1756-L55M13
-
Estimated shipping dimensions:3.5x14x14.5cm
-
Weight:0.35 kg
-
Tariff Code:8537101190
-
Counliy of origin:USA
-
Data and logic memory:1.5 MB
-
I/O memory:208 KB
-
Nonvolatile memory:Not supported
-
Backplane current at 5.1 V DC:1.23 A
-
Backplane current at 24 V DC:14 mA
-
Power dissipation:5.6 W
-
Thermal dissipation:19.1 BTU/h
-
Operating temperature:0-60 C
-
Storage temperature:-40-85 C
-
Relative humidity:5-95%, noncondensing
-
Operating shock:30 g, 11 ms
-
Nonoperating shock:50 g, 11 ms
-
Vibration:2 g at 10-500 Hz
-
Programming cable:1756-CP3 or 1747-CP3
Information
- Owns the chassis control task and scheduled program execution
- Produces and consumes data through configured communication modules
- Coordinates local and distributed I/O update paths
- Reports controller and chassis diagnostic status to engineering tools
1756-L55M13 operates with 1756 ControlLogix chassis, compatible 1756 power supply, communication modules, RSLogix 5000 project.
Typical engineered duties include ControlLogix5555 installed-base control, 1756-L55M13 controller migration planning, 1756-L55M13 shutdown replacement, 1756-L55M13 program recovery and validation.
Important Notice: A 1756-L55M13 replacement requires an engineered match of controller series, firmware, memory, project revision, chassis slot and communication dependencies before the machine is released.
Apter Power 1756-L55M13 Manuals and Guides
- Apter Power 1756-L55M13 Product Reference Manual
- Rockwell Automation Official Installation or User Manual
Important Notice: The first document is an Apter Power 1756-L55M13 model-specific technical reference. The second is a distinct document for installation, configuration or system engineering.
Technical notes
FAQ View All FAQ
-
Which chassis accepts 1756-L55M13?Install it in a compatible 1756 ControlLogix chassis with the approved power supply and keyed surrounding modules.
-
How should the project be prepared before replacing 1756-L55M13?Archive the online project, firmware information, controller properties, I/O tree and communication settings before shutdown.
-
What memory must be compared for 1756-L55M13?Confirm the installed catalog number against 1.5 MB of data/logic memory and 208 KB of I/O memory.
-
How is communication restored after fitting 1756-L55M13?Set the approved network path, download the validated project and confirm each configured bridge and I/O connection.
-
What power check applies to 1756-L55M13?Include its published backplane demand of 1.23 A at 5.1 V DC and 14 mA at 24 V DC in the chassis loading review.
-
How should 1756-L55M13 be commissioned?Verify controller mode, task execution, I/O ownership, inhibited modules, produced/consumed tags and output permissives.
-
Can a different ControlLogix controller replace 1756-L55M13 directly?Not without a migration review covering firmware, instructions, communication limits, memory and project conversion.
-
What maintenance records are needed for 1756-L55M13?Record the serial/revision data, firmware, project checksum, battery or memory condition, chassis diagnostics and final functional test.
Supporting new and legacy automation
-
Please try to be as accurate as possible with your search.
-
We can quote you on 1000s of specialist parts, even if they are not listed on our website.
-